Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
---|
Ambient temperature (operation) | -20 °C ... 65 °C |
---|---|
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Maximum altitude | ≤ 2000 m |
Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
Degree of protection | IP20 |
Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
Designation | Supply |
---|---|
Nominal supply voltage | 24 V DC |
Supply voltage range | 19.2 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715)) |
Max. current consumption | < 25 mA |
Power consumption | < 600 mW |
Connection method | Screw connection |
---|---|
Stripping length | 12 mm |
Screw thread | M3 |
Conductor cross section solid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 26 ... 12 |
No. of channels | 1 |
---|---|
Status display | Red LED (error messages) |
Yellow LED (relay status messages) | |
Electrical isolation | Reinforced insulation according to EN 61010-1 |
Overvoltage category | II |
Degree of pollution | 2 |
Rated insulation voltage | 150 V AC (Input/relay outputs (reinforced insulation)) |
Test voltage, input/output/supply | 1.5 kV (50 Hz, 1 min.) |
Electromagnetic compatibility | Conformance with EMC directive |
Noise emission | EN 61000-6-4 |
Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
Color | green |
Housing material | PBT |
Mounting position | any |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
Designation | Electromagnetic RF field |
---|---|
Standards/regulations | EN 61000-4-3 |
Evaluation criterion | A |
Designation | Fast transients (burst) |
Standards/regulations | EN 61000-4-4 |
Evaluation criterion | A |
Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 |
Evaluation criterion | A |
Electromagnetic compatibility | Conformance with EMC directive |
---|---|
Noise emission | EN 61000-6-4 |
Connection in acc. with standard | CUL |
Designation | Electromagnetic RF field |
Standards/regulations | EN 61000-4-3 |
Evaluation criterion | A |
Standards/regulations | EN 61000-4-4 |
Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 |
Evaluation criterion | A |
Electrical isolation | Reinforced insulation according to EN 61010-1 |
Conformance | CE-compliant |
ATEX | II 3 G Ex nA nC IIC T4 Gc X |
UL, USA/Canada | UL 508 Recognized |
Class I, Div. 2, Groups A, B, C, D T4 |
Designation | CE |
---|---|
Identification | CE-compliant |
Designation | UL, USA/Canada |
Identification | UL 508 Recognized |
Class I, Div. 2, Groups A, B, C, D T4 | |
Designation | Shipbuilding approval |
Certificate | DNV GL TAA00000N1 |
Temperature | B |
Humidity | B |
Vibration | B |
EMC | A |
Enclosure | A |
REACh SVHC | Lead 7439-92-1 |
---|---|
Cadmium oxide 1306-19-0 | |
China RoHS | Environmentally Friendly Use Period = 50 years |
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
eCl@ss 10.0.1 | 27210120 |
---|---|
eCl@ss 11.0 | 27210120 |
eCl@ss 4.0 | 27210100 |
eCl@ss 4.1 | 27210100 |
eCl@ss 5.0 | 27210100 |
eCl@ss 5.1 | 27210100 |
eCl@ss 6.0 | 27210100 |
eCl@ss 7.0 | 27210120 |
eCl@ss 8.0 | 27210120 |
eCl@ss 9.0 | 27210120 |
UNSPSC 6.01 | 30211506 |
---|---|
UNSPSC 7.0901 | 39121008 |
UNSPSC 11 | 39121008 |
UNSPSC 12.01 | 39121008 |
UNSPSC 13.2 | 39121008 |
UNSPSC 18.0 | 39121008 |
UNSPSC 19.0 | 39121008 |
UNSPSC 20.0 | 39121008 |