Extension module - AXC F XT IB - 2403018

Left-alignable INTERBUS master, for the connection of INTERBUS remote bus components to a compatible modular controller from the PLCnext Control range.

Price:

Overview

Technical data

Accessories

Downloads

Drawings



Dimensional drawing  

Dimensional drawing

Back to top

Dimensions

Dimensional drawing
Width 35 mm
Height 126.1 mm
Depth 54 mm
Note on dimensions The depth is valid when a TH 35-7,5 DIN rail is used (according to EN 60715).
Back to top

Ambient conditions

Ambient temperature (operation) -25 °C ... 60 °C (up to 2000 m above sea level)
-25 °C ... 55 °C (2000 m above sea level ... 3000 m above sea level)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Permissible humidity (operation) 5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport) 5 % ... 95 % (non-condensing)
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level (at an operating temperature of up to 55°C, maximum))
Air pressure (storage/transport) 58 kPa ... 106 kPa (up to 4500 m above mean sea level)
Degree of protection IP20
Back to top

Connection data

Designation Axioline F connector
Connection method Push-in connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 1.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 1.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 16
Stripping length 8 mm
Back to top

General

Mounting type DIN rail
Color traffic grey A RAL 7042
Net weight 157.8 g
Diagnostics messages Bus error in INTERBUS Yes
Peripheral fault in INTERBUS Yes
Mounting type DIN rail mounting
Back to top

Data interfaces

Interface INTERBUS remote bus
Number 1
Connection method D-SUB-9 female connector
Back to top

Axioline potentials

Designation Supply of the logic voltage UL
Supply voltage 24 V DC
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current consumption typ. 110 mA (without IBS OPTOSUB ... FO adapter)
max. 185 mA (with IBS OPTOSUB ... FO adapter)
Protective circuit Polarity reversal protection of the supply voltage Polarity protection diode
Transient protection Suppressor diode
Back to top

Standards and Regulations

Immunity to ESD Noise immunity test in accordance with EN 61000-6-2 Electrostatic discharge (ESD) EN 61000-4-2/IEC 61000-4-2 Criterion B, 6 kV contact discharge, 8 kV air discharge
Immunity to EF Noise immunity test in accordance with EN 61000-6-2 Electromagnetic fields EN 61000-4-3/IEC 61000-4-3 Criterion A, Field intensity: 10 V/m
Immunity to burst Noise immunity test in accordance with EN 61000-6-2 Fast transients (burst) EN 61000-4-4/IEC 61000-4-4 Criterion B, 2 kV
Immunity to surge Noise immunity test in accordance with EN 61000-6-2 Transient overvoltage (surge) EN 61000-4-5/IEC 61000-4-5 Criterion B, DC supply lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical), fieldbus cable shield: ±1 kV
Immunity to conducted interference Noise immunity test in accordance with EN 61000-6-2 Conducted interference EN 61000-4-6/IEC 61000-4-6 Criterion A, Test voltage 10 V
Interference emission Noise emission test according to EN 61000-6-3 Class B
Mechanical tests Shock in acc. with EN 60068-2-27/IEC 60068-2-27 30g, 11 ms period, half-sine shock pulse
Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g
Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g
Back to top

Environmental Product Compliance

REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
Back to top

Classifications

eCl@ss

eCl@ss 10.0.1 27242608
eCl@ss 11.0 27242608
eCl@ss 9.0 27242608
Back to top

ETIM

ETIM 5.0 EC001604
ETIM 6.0 EC001604
ETIM 7.0 EC001604
Back to top

PHOENIX CONTACT
SEA Pte. Ltd.

105 Eunos Avenue 3
#04-00
Singapore 409836
+65 6228 4900