Capacity module - QUINT4-CAP/24DC/10/8KJ - 2320571

QUINT capacity module, with maintenance-free energy storage based on double-layer capacitor, DIN rail mounting, input: 24 V DC, output: 24 V DC / 10 A / 8 kJ incl. mounted UTA 107 universal DIN rail adapter

Price:

Overview

Technical data

Accessories

Approvals

Downloads

Drawings



Block diagram  

Block diagram

Pictogram  

Pictogram



Pictogram  

Pictogram

Back to top

Dimensions

Width 118 mm
Height 130 mm
Depth 125 mm
Installation distance right/left 0 mm / 0 mm
Installation distance top/bottom 50 mm / 50 mm
Back to top

Ambient conditions

Degree of protection IP20
Ambient temperature (operation) -25 °C ... 60 °C (> 40 °C Derating: 1 %/K)
Ambient temperature (start-up type tested) -40 °C
Ambient temperature (storage/transport) -40 °C ... 60 °C
Max. permissible relative humidity (operation) ≤ 95 %
Climatic class 3K3 (in acc. with EN 60721)
Degree of pollution 2
Installation height ≤ 4000 m
Back to top

Input data

Input voltage 24 V DC (SELV)
Input voltage range 22.5 V DC ... 30 V DC
Fixed backup threshold < 22 V DC
Voltage type of supply voltage DC
Current consumption IN (UN, IOUT = IN, Icharge = 0) 13.5 A
Current consumption INo-Load(UN, IOUT = 0, Icharge = 0) 0.1 A (No-load)
Current consumption Icharge (UN, IOUT = 0, Icharge = max) 1 A (charging process)
Buffer time 5 min. (1 A)
1 min. (5 A)
30 s (10 A)
Charging time approx. 22 min.
Recharging time approx. 12 min.
Back to top

Output data

Connection in parallel no
Connection in series No
Back to top

Output data, mains operation

Output voltage 24 V DC (depending on the input voltage)
Output current IN 10 A
Static Boost (IStat.Boost) 60 A (15 ms)
Dynamic Boost (IDyn.Boost) 20 A (5 s)
Nominal load power dissipation 6 W
Short-circuit-proof yes (with input fuse)
Idling-proof yes
Back to top

Output data, battery operation

Output voltage 22 V DC (typical)
Output current IN 10 A (depending on output current)
Static Boost (IStat.Boost) 12.5 A
Short-circuit-proof yes
Idling-proof yes
Back to top

General

Net weight 1.6 kg
Efficiency > 97 % (with charged energy storage device)
MTBF (IEC 61709, SN 29500) 1387186 h (40 °C)
Degree of protection IP20
Protection class III (Special application (SELV input voltage, hazardous voltages are generated in the device).)
Mounting position horizontal DIN rail NS 35, EN 60715
Assembly instructions alignable: horizontally 0 mm, vertically 50 mm
Back to top

Input connection data

Connection method Screw connection
Stripping length 6.5 mm
Conductor cross section solid 0.2 mm² ... 2.5 mm²
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section AWG 30 ... 12
Torque 0.5 Nm ... 0.6 Nm
Back to top

Output connection data

Connection method Screw connection
Stripping length 6.5 mm
Conductor cross section solid 0.2 mm² ... 2.5 mm²
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section AWG 30 ... 12
Torque 0.5 Nm ... 0.6 Nm
Back to top

Signal connection data

Connection method Push-in connection
Conductor cross section solid 0.2 mm² ... 0.75 mm²
Conductor cross section flexible 0.2 mm² ... 1.5 mm²
Flexible conductor cross section (ferrule with plastic sleeve) 0.2 mm² ... 0.75 mm²
Flexible conductor cross section flexible (ferrule, w/o plastic sleeve) 0.2 mm² ... 1 mm²
Conductor cross section AWG 24 ... 18
Stripping length 8 mm
Back to top

Interfaces

Number of interfaces 1
Connection method MINI-USB Type B
Connection marking 5.1
Locking Screw
Transmission physics USB 2.0
Back to top

Standards

EMC requirements for noise immunity EN 61000-6-1
EN 61000-6-2
EMC requirements for noise emission EN 61000-6-3
EN 61000-6-4
Back to top

EMC data

Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Noise emission EN 55016
EN 61000-6-3
Electrostatic discharge EN 61000-4-2
Contact discharge 6 kV (Test Level 3)
Discharge in air 8 kV (Test Level 3)
Electromagnetic HF field EN 61000-4-3
Frequency range 80 MHz ... 6 GHz
Test field strength 10 V/m
Comments Criterion A
Conducted interference EN 61000-4-6
Frequency range 0.15 MHz ... 80 MHz
Voltage 10 V
Comments Criterion A
Criterion A Normal operating behavior within the specified limits.
Criterion B Temporary impairment to operational behavior that is corrected by the device itself.
Back to top

Environmental Product Compliance

REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 25;
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
Back to top

Classifications

eCl@ss

eCl@ss 5.0 27242700
eCl@ss 5.1 27242700
eCl@ss 6.0 27040600
eCl@ss 7.0 27040603
eCl@ss 8.0 27049201
eCl@ss 9.0 27049201
Back to top

ETIM

ETIM 5.0 EC000382
ETIM 6.0 EC002850
ETIM 7.0 EC002850
Back to top

UNSPSC

UNSPSC 13.2 39121004
UNSPSC 18.0 26111710
UNSPSC 19.0 26111710
UNSPSC 20.0 26111710
UNSPSC 21.0 26111710
Back to top