new

Capacity module - QUINT4-CAP/24DC/3.8/1KJ/PT - 2320526

QUINT capacity module with maintenance-free double-layer capacitor-based energy storage for DIN rail mounting, input: 24 V DC, output: 24 V DC / 3.8 A / 1 kJ

Price:

Overview

Technical data

Accessories

Approvals

Downloads

Drawings



Block diagram  

Block diagram

Pictogram  

Pictogram



Pictogram  

Pictogram

Back to top

Dimensions

Width 85 mm
Height 102.5 mm
Depth 90 mm
Installation distance right/left 0 mm / 0 mm
Installation distance top/bottom 50 mm / 50 mm
Back to top

Ambient conditions

Degree of protection IP20
Ambient temperature (operation) -25 °C ... 60 °C
Ambient temperature (start-up type tested) -40 °C
Ambient temperature (storage/transport) -40 °C ... 60 °C
Max. permissible relative humidity (operation) ≤ 95 %
Climatic class 3K3 (in acc. with EN 60721)
Degree of pollution 2
Installation height ≤ 4000 m
Back to top

Input data

Input voltage 24 V DC (SELV)
Input voltage range 22.5 V DC ... 30 V DC
Current consumption (maximum) 4.3 A (max.)
Current consumption (idle) 0.08 A (No-load)
Current consumption (charging process) 0.43 A (charging process)
Fixed backup threshold < 22 V DC
Back to top

Output data

Nominal output voltage 24 V DC (depending on the input voltage)
Nominal output current (IN) 3.8 A
Connection in parallel Yes, up to 2 modules with decoupling module
Connection in series No
Power loss nominal load max. < 2 W
Back to top

General

Net weight 0.48 kg
Memory medium Dual layer capacitor
Efficiency > 97 % (with charged energy storage device)
MTBF (IEC 61709, SN 29500) 996550 h (40 °C)
1631804 h (25 °C)
449865 h (60 °C)
Degree of protection IP20
Protection class III
Mounting position Any, on NS 35 DIN rail
Assembly instructions alignable: horizontally 0 mm, vertically 50 mm
Back to top

Connection data, input

Connection method Push-in connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Stripping length 10 mm
Back to top

Connection data, output

Connection method Push-in connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Stripping length 10 mm
Back to top

Signaling

Signalization designation UIn OK
Output name Transistor output, active
Output voltage 24 V (UN - 1 V (typical))
Continuous load current 20 mA
Status display LED
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Signalization designation Ready
Output name Transistor output, active
Output voltage 24 V (UN - 1 V (typical))
Continuous load current 20 mA
Status display LED
Signalization designation Reference potential for Ready, UIn OK, and Remote
Back to top

EMC data

Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Noise emission EN 61000-6-3
Electrostatic discharge EN 61000-4-2
Contact discharge 6 kV (Test Level 3)
Discharge in air 8 kV (Test Level 3)
Electromagnetic HF field EN 61000-4-3
Frequency range 80 MHz ... 6 GHz
Test field strength 10 V/m
Comments Criterion A
Fast transients (burst) EN 61000-4-4
Input 2 kV (Test Level 3 - asymmetrical)
Output 2 kV (Test Level 3 - asymmetrical)
Signal 2 kV (Test Level 4 - asymmetrical)
Comments Criterion B
Surge voltage load (surge) EN 61000-4-5
Input 1 kV (Test Level 3 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Output 1 kV (Test Level 3 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Signal 1 kV (Test Level 1 - asymmetrical)
Comments Criterion B
Conducted interference EN 61000-4-6
Frequency range 0.15 MHz ... 80 MHz
Voltage 10 V
Comments Criterion A
Criterion A Normal operating behavior within the specified limits.
Criterion B Temporary impairment to operational behavior that is corrected by the device itself.
Back to top

Environmental Product Compliance

REACh SVHC Lead 7439-92-1
Back to top

Classifications

eCl@ss

eCl@ss 5.1 27242213
eCl@ss 8.0 27049201
eCl@ss 9.0 27049201
Back to top

ETIM

ETIM 5.0 EC000382
ETIM 6.0 EC000382
ETIM 7.0 EC000382
Back to top

UNSPSC

UNSPSC 13.2 39121004
UNSPSC 18.0 26111710
UNSPSC 19.0 26111710
UNSPSC 20.0 26111710
UNSPSC 21.0 26111710