new

Surge protection device - TTC-6P-1X2-F-24DC-PT-I - 1065318

Surge protection, consisting of protective plug and base element, with integrated status indicator for a 2-wire floating signal circuit. Indirect grounding via gas-filled surge arrester.

Price:

Overview

Technical data

Accessories

Approvals

Downloads

Drawings



Diagram  

Diagram

Dimensional drawing  

Dimensional drawing



Pictogram  

Pictogram

Circuit diagram  

Circuit diagram



Back to top

Dimensions

Height 105.8 mm
Width 6.2 mm +0.1 mm
Depth 100 mm (incl. DIN rail 7.5 mm)
Back to top

Ambient conditions

Ambient temperature (operation) -40 °C ... 85 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Altitude ≤ 4000 m (amsl (above mean sea level))
Degree of protection IP20
Back to top

General

Housing material PBT
Flammability rating according to UL 94 V-0
Color traffic grey A RAL 7042
light grey RAL 7035
Mounting type DIN rail: TH 35 - 7.5 mm
Type DIN rail module, two-section, divisible
Direction of action Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Back to top

Protective circuit

IEC test classification C1
C2
C3
D1
Nominal voltage UN 24 V DC
Maximum continuous voltage UC 30 V DC
21 V AC
Rated current 600 mA (56 °C)
Operating effective current IC at UC ≤ 5 µA
Residual current IPE ≤ 1 µA
Nominal discharge current In (8/20) µs (line-line) 5 kA
Nominal discharge current In (8/20) µs (line-earth) 5 kA
Nominal discharge current In (8/20) µs (line-signal ground) 5 kA
Pulse discharge current Iimp (10/350) µs (line-line) 0.5 kA
Pulse discharge current Iimp (10/350) µs (line-earth) 0.5 kA
Pulse discharge current Iimp (10/350) µs (line-signalground) 0.5 kA
Total discharge current Itotal (8/20) µs 10 kA
Voltage protection level Up (line-line) ≤ 200 V (C1 - 1 kV/500 A)
≤ 320 V (C2 - 10 kV / 5 kA)
≤ 50 V (C3 - 25 A)
≤ 55 V (C3 - 100 A)
Voltage protection level Up (line-earth) ≤ 900 V (C1 - 1 kV/500 A)
≤ 1.05 kV (C2 - 10 kV / 5 kA)
≤ 1.3 kV (C3 - 25 A)
≤ 1.4 kV (C3 - 100 A)
Voltage protection level Up (line-signalground) ≤ 750 V (C1 - 1 kV/500 A)
≤ 750 V (C2 - 10 kV / 5 kA)
≤ 700 V (C3 - 25 A)
≤ 750 V (C3 - 100 A)
Voltage protection level Up static (line-line) ≤ 50 V (C1 - 1 kV/500 A)
≤ 120 V (C2 - 10 kV / 5 kA)
Voltage protection level Up static (line-earth) ≤ 900 V (C1 - 1 kV/500 A)
≤ 1.05 kV (C2 - 10 kV / 5 kA)
Voltage protection level Up static (line-signalground) ≤ 750 V (C1 - 1 kV/500 A)
≤ 750 V (C2 - 10 kV / 5 kA)
Response time tA (line-line) ≤ 1 ns
Response time tA (line-signalground) ≤ 100 ns
Response time tA (line-earth) ≤ 100 ns
Input attenuation aE, sym. typ. 0.3 dB (≤ 250 kHz / 150 Ω)
Cut-off frequency fg (3 dB), sym. in 150 Ohm system typ. 940 kHz
Capacity (line-line) typ. 2.2 nF
Resistance per path 1.65 Ω ±20 %
Max. required back-up fuse 630 mA (FF)
Impulse durability (line-line) C1 - 1 kV / 500 A
C2 - 10 kV / 5 kA
C3 - 100 A
Impulse durability (line-earth) C1 - 1 kV / 500 A
C2 - 10 kV / 5 kA
C3 - 100 A
D1 - 500 A
Impulse durability (line-signalground) C1 - 1 kV / 500 A
C2 - 10 kV / 5 kA
C3 - 100 A
D1 - 500 A
Pulse reset time (line-line) ≤ 700 ms
Pulse reset time (line-earth) ≤ 30 ms
Pulse reset time (line-signalground) ≤ 1500 ms
Back to top

Additional technical data

Max. total discharge current I total max (8/20) µs 20 kA (1x)
Back to top

Connection data

Connection method Push-in connection
Stripping length 8 mm
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section solid 0.2 mm² ... 4 mm²
Conductor cross section AWG 24 ... 12
Back to top

Standards and Regulations

Standards/specifications IEC 61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012
EN 61643-21 2001 + A1:2009 + A2:2013
Back to top

Environmental Product Compliance

REACh SVHC
Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
Back to top

Classifications

eCl@ss

eCl@ss 6.0 27130800
eCl@ss 7.0 27130807
eCl@ss 8.0 27130807
eCl@ss 9.0 27130807
Back to top

ETIM

ETIM 5.0 EC000943
ETIM 6.0 EC000943
ETIM 7.0 EC000943
Back to top

PHOENIX CONTACT
SEA Pte. Ltd.

105 Eunos Avenue 3
#04-00
Singapore 409836
+65 6228 4900
  • Create PDF
  • Recommend
  • Feedback