Repeater power supply for supplying 2 and 3-conductor transmitters with HART transmission and wide range power supply, SIL, Push-in connection

Preço:

Visão geral

Dados técnicos

Acessórios

Certificações

Downloads

Desenhos



Block diagram  

Block diagram
Connection example

Block diagram  

Block diagram



Diagram  

Diagram
Signal transmission analog and digital at the same time

Dimensional drawing  

Dimensional drawing



Pictogram  

Pictogram

Voltar para cima

Note

Utilization restriction EMC: class A product, see manufacturer's declaration in the download area
Voltar para cima

Dimensions

Width 17.5 mm
Height 116 mm
Depth 114.5 mm
Voltar para cima

Ambient conditions

Ambient temperature (operation) -20 °C ... 60 °C (Any mounting position)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Maximum altitude ≤ 2000 m
Permissible humidity (operation) 10 % ... 95 % (non-condensing)
Noise immunity EN 61000-6-2
Voltar para cima

Input data

Signal input Repeater power supply operation
Current input signal 4 mA ... 20 mA
Transmitter supply voltage > 16 V (20 mA)
> 15.3 V (22.5 mA)
Signal input Signal conditioner operation
Current input signal 0 mA ... 20 mA
4 mA ... 20 mA
Voltage drop < 3.5 V (in input isolating amplifier operation)
Voltar para cima

Output data

Signal output Repeater power supply operation
Voltage output signal 1 V ... 5 V (internal resistance, 250 Ω, 0.1%)
Configurable via DIP switches
Current output signal 4 mA ... 20 mA (active)
4 mA ... 20 mA (14 ... 26 V ext. source voltage)
Transmission Behavior 1:1 to input signal
Load/output load current output < 600 Ω (20 mA)
< 525 Ω (22.5 mA)
Output ripple < 20 mVrms
Output behavior in the event of an error 0 mA (Cable break in the input)
≥ 22.5 mA (Cable short-circuit in the input)
Signal output Signal conditioner operation
Voltage output signal 0 V ... 5 V (internal resistance, 250 Ω, 0.1%)
1 V ... 5 V (internal resistance, 250 Ω, 0.1%)
Current output signal 0 mA ... 20 mA (active)
4 mA ... 20 mA (active)
0 mA ... 20 mA (14 ... 26 V ext. source voltage)
4 mA ... 20 mA (14 ... 26 V ext. source voltage)
Load/output load current output < 600 Ω (20 mA)
< 525 Ω (22.5 mA)
Output ripple < 20 mVrms
Output behavior in the event of an error 0 mA (Cable break in the input)
0 mA (Cable short-circuit in the input)
Voltar para cima

Power supply

Designation Repeater power supply operation
Nominal supply voltage range 24 V AC/DC ... 230 V AC/DC (50/60 Hz)
Supply voltage range 19.2 V AC/DC ... 253 V AC/DC (24 V AC/DC ... 230 V AC/DC (-20 % ... +10 %, 50/60 Hz))
Max. current consumption < 75 mA (24 V DC / 20 mA)
Power dissipation < 1.6 W (24 V DC / 20 mA)
Power consumption < 1.9 W
Designation Signal conditioner operation
Nominal supply voltage range 24 V ... 230 V AC/DC (-20 %/+10 %, 50/60 Hz)
Max. current consumption < 45 mA (24 V DC / 20 mA)
Power dissipation < 1.1 W (24 V DC/ 20 mA)
Power consumption < 1.1 W
Voltar para cima

Connection data

Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 1.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 1.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 16
Stripping length 8 mm
Connection method Push-in connection
Voltar para cima

General

No. of channels 1
Maximum transmission error < 0.1 % (of final value)
Transmission error, typical < 0.05 % (of final value)
Maximum temperature coefficient < 0.01 %/K
Step response (10-90%) < 600 µs (for 4 mA ... 20 mA step)
Status display Green LED (supply voltage)
Flammability rating according to UL 94 V0
Degree of pollution 2
Overvoltage category II
Electromagnetic compatibility Conformance with EMC directive
Interference emission EN 61000-6-4
Housing material PA 6.6-FR
Color gray
Designation Input/output/power supply
Electrical isolation 300 Vrms (Rated insulation voltage (overvoltage category II; degree of pollution 2, safe isolation as per EN 61010-1))
2.5 kV (50 Hz, 1 min., test voltage)
Conformance CE-compliant, additionally EN 61326-1
ATEX  II 3 G Ex nA IIC T4 Gc X
UL, USA/Canada UL 508 Listed
UL 61010 Listed
Class I, Div. 2, Groups A, B, C, D T4
Class I, Zone 2, Group IIC T4
SIL 2
Voltar para cima

Data communication (bypass)

HART function Yes
Protocols supported HART
Voltar para cima

Standards and Regulations

Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Flammability rating according to UL 94 V0
Conformance CE-compliant, additionally EN 61326-1
ATEX  II 3 G Ex nA IIC T4 Gc X
UL, USA/Canada UL 508 Listed
UL 61010 Listed
Class I, Div. 2, Groups A, B, C, D T4
Class I, Zone 2, Group IIC T4
Voltar para cima

Environmental Product Compliance

REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
Voltar para cima

Classificações

eCl@ss

eCl@ss 4.0 27210120
eCl@ss 4.1 27210120
eCl@ss 5.0 27210120
eCl@ss 5.1 27210100
eCl@ss 6.0 27210100
eCl@ss 7.0 27210120
eCl@ss 8.0 27210120
eCl@ss 9.0 27210120
Voltar para cima

ETIM

ETIM 4.0 EC002653
ETIM 5.0 EC002653
ETIM 6.0 EC002653
ETIM 7.0 EC002653
Voltar para cima

UNSPSC

UNSPSC 6.01 30211506
UNSPSC 7.0901 39121008
UNSPSC 11 39121008
UNSPSC 12.01 39121008
UNSPSC 13.2 39121008
Voltar para cima

Phoenix Contact S.A.

Sintra Business Park,
Edifício n°1
Zona Industrial da Abrunheira
2710-089 SINTRA

Horário: 9h -13h e 14h -18h
(+351) 21 911 2760
  • Criar PDF
  • Recomendar
  • Feedback

Este website usa cookies. Ao continuar a navegar, está a concordar com a nossa política de cookies. Saiba mais sobre a nossa política de privacidade.

Fechar