Power/input isolating amplifier - MACX MCR-EX-SL-RPSSI-I - 2865340

Ex i repeater power supply and input signal conditioner, HART. Transmits supplied or active 0/4 - 20 mA signals from the hazardous area to a load (active or passive) in the safe area. 3-way electrical isolation; SIL 2 according to IEC 61508, with screw connection

Preço:

Visão geral

Dados técnicos

Acessórios

Certificações

Downloads

Desenhos



Block diagram  

Block diagram

Dimensional drawing  

Dimensional drawing



Pictogram  

Pictogram

Voltar para cima

Note

Utilization restriction EMC: class A product, see manufacturer's declaration in the download area
Voltar para cima

Dimensions

Width 12.5 mm
Height 112.5 mm
Depth 114.5 mm
Voltar para cima

Ambient conditions

Ambient temperature (operation) -20 °C ... 60 °C (Any mounting position)
Ambient temperature (storage/transport) -40 °C ... 80 °C
Maximum altitude ≤ 2000 m
Permissible humidity (operation) 10 % ... 95 % (non-condensing)
Degree of protection IP20
Noise immunity EN 61000-6-2 When being exposed to interference, there may be minimal deviations.
Voltar para cima

Input data

Signal input Active current input, intrinsically safe
Current input signal 4 mA ... 20 mA
Transmitter supply voltage > 16 V (20 mA)
> 15.3 V (22.5 mA)
Underload/overload signal range 0 mA ... 24 mA (Extended transmission range for diagnostics)
Polarization and surge protection Yes
Signal input Passive current input, intrinsically safe
Current input signal 0 mA ... 20 mA
4 mA ... 20 mA
Voltage drop < 3.5 V (in input isolating amplifier operation)
Underload/overload signal range 0 mA ... 24 mA (Extended transmission range for diagnostics)
Voltar para cima

Output data

Signal output Current output (active and passive)
Current output signal 4 mA ... 20 mA (active)
4 mA ... 20 mA (14 ... 26 V ext. source voltage)
Transmission Behavior 1:1 to input signal
Load/output load current output < 1000 Ω (20 mA)
< 825 Ω (24 mA)
Output ripple < 20 mVrms
Output behavior in the event of an error 0 mA (Cable break in the input)
≥ 22.5 mA (Cable short-circuit in the input)
Signal output Current output (active and passive)
Current output signal 0 mA ... 20 mA (active)
4 mA ... 20 mA (active)
0 mA ... 20 mA (14 ... 26 V ext. source voltage)
4 mA ... 20 mA (14 ... 26 V ext. source voltage)
Transmission Behavior 1:1 to input signal
Load/output load current output < 1000 Ω (20 mA)
< 825 Ω (24 mA)
Output ripple < 20 mVrms
Output behavior in the event of an error 0 mA (Cable break in the input)
0 mA (Cable short-circuit in the input)
Voltar para cima

Power supply

Designation Repeater power supply operation
Nominal supply voltage 24 V DC
Supply voltage range 19.2 V DC ... 30 V DC (24 V DC -20%...+25%)
Max. current consumption < 76 mA (24 V DC / 20 mA / 1000 )
Power dissipation < 1.1 W (24 V DC / 20 mA / 1000 )
Power consumption < 1.8 W (20 mA / 1000 )
Designation Signal conditioner operation
Nominal supply voltage range 19.2 V DC ... 30 V DC (24 V DC -20%...+25%)
Max. current consumption < 44 mA (24 V DC / 20 mA / 1000 )
Power dissipation < 0.75 W (24 V DC / 20 mA / 1000 )
Voltar para cima

Connection data

Connection method Screw connection
Stripping length 7 mm
Screw thread M3
Conductor cross section solid 0.2 mm² ... 2.5 mm²
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section AWG 24 ... 14
Torque 0.5 Nm ... 0.6 Nm
Voltar para cima

Connection data 2

Connection name Test socket
Max. diameter 2 mm
Voltar para cima

General

No. of channels 1
Maximum transmission error < 0.1 % (of final value)
Transmission error, typical < 0.05 % (of final value)
Maximum temperature coefficient < 0.01 %/K
Temperature coefficient, typical < 0.004 %/K
Step response (10-90%) < 200 µs (for jump 4 mA ... 20 mA, load 600 Ω)
< 600 µs (for jump 0 mA ... 20 mA, load 600 Ω)
Status display Green LED (supply voltage)
Flammability rating according to UL 94 V0
Degree of pollution 2
Overvoltage category II
Electromagnetic compatibility Conformance with EMC directive
Interference emission EN 61000-6-4
Housing material PA 6.6-FR
Color gray
Designation Input/output/power supply
Electrical isolation 300 Vrms (Rated insulation voltage (overvoltage category II; degree of pollution 2, safe isolation as per EN 61010-1))
2.5 kV (50 Hz, 1 min., test voltage)
Designation Input/output
Electrical isolation 375 V (Peak value in accordance with EN 60079-11)
Designation Input/power supply
Electrical isolation 375 V (Peak value in accordance with EN 60079-11)
Conformance CE-compliant, additionally EN 61326
ATEX  II (1) G [Ex ia Ga] IIC
 II (1) D [Ex ia Da] IIIC
 II 3 (1) G Ex nA [ia Ga] IIC T4 Gc
 I (M1) [Ex ia Ma] I
IECEx [Ex ia Ga] IIC
[Ex ia Da] IIIC
Ex nA [ia Ga] IIC T4 Gc
[Ex ia Ma] I
UL, USA/Canada UL 61010 Listed
Class I Div 2; IS for Class I, II, III Div 1
SIL 2
Voltar para cima

Data communication (bypass)

HART function Yes
Protocols supported HART
Voltar para cima

Safety characteristic data

Integrity requirement IEC 61508 - Low demand
Equipment type Type A
Safety Integrity Level (SIL) 2
Safe Failure Fraction (SFF) 90.7 %
λSU 4.867 x 10-7 (486.7 FIT)
λSD 0
λDU 5 x 10-8 (50 FIT)
λDD 0
Probability of a hazardous failure on demand (PFDAVG) 2.40 x 10-4 (1 year)
4.76 x 10-4 (2 years)
7.13 x 10-4 (3 years)
9.50 x 10-4 (4 years)
11.9 x 10-4 (5 years)
Diagnostic coverage (DC) DCS=0 %, DCD=0 %
Integrity requirement IEC 61508 - High demand
Equipment type Type A
Safety Integrity Level (SIL) 2
Safe Failure Fraction (SFF) 90.7 %
λSU 4.867 x 10-7 (486.7 FIT)
λSD 0
λDU 5 x 10-8 (50 FIT)
λDD 0
Probability of a hazardous failure per hour (PFHD) 4,99 x 10-8
Diagnostic coverage (DC) DCS=0 %, DCD=0 %
Voltar para cima

Safety data

Operation Repeater power supply operation
Max. output voltage Uo 25.2 V
Max. output current Io 93 mA
Max. output power Po 587 mW
Group IIC
Max. external inductivity Lo 2 mH
Max. external capacity Co 107 nF
Group IIB
Max. external inductivity Lo 4 mH
Max. external capacity Co 820 nF
Safety-related maximum voltage Um 253 V AC (125 V DC)
Operation Signal conditioner operation
Input voltage Ui ≤ 30 V
Input current Ii ≤ 150 mA
Max. internal inductance Li negligible
Max. internal capacitance Ci negligible
Voltar para cima

EMC data

Designation Electromagnetic RF field
Standards/regulations EN 61000-4-3
Typical deviation from the measuring range final value 1 %
Designation Fast transients (burst)
Standards/regulations EN 61000-4-4
Typical deviation from the measuring range final value 1 %
Designation Conducted interferences
Standards/regulations EN 61000-4-6
Typical deviation from the measuring range final value 1 %
Voltar para cima

Standards and Regulations

Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Designation Electromagnetic RF field
Standards/regulations EN 61000-4-3
EN 61000-4-4
Designation Conducted interferences
Standards/regulations EN 61000-4-6
Flammability rating according to UL 94 V0
Conformance CE-compliant, additionally EN 61326
ATEX  II (1) G [Ex ia Ga] IIC
 II (1) D [Ex ia Da] IIIC
 II 3 (1) G Ex nA [ia Ga] IIC T4 Gc
 I (M1) [Ex ia Ma] I
IECEx [Ex ia Ga] IIC
[Ex ia Da] IIIC
Ex nA [ia Ga] IIC T4 Gc
[Ex ia Ma] I
UL, USA/Canada UL 61010 Listed
Class I Div 2; IS for Class I, II, III Div 1
DNV GL-Temperature B
DNV GL-Humidity B
DNV GL-Vibration A
DNV GL-EMC A
DNV GL-Enclosure Required protection according to the Rules shall be provided upon installation on board
Group IIC
IIB
Voltar para cima

Environmental Product Compliance

China RoHS Environmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
Voltar para cima

Classificações

eCl@ss

eCl@ss 4.0 27210120
eCl@ss 4.1 27210120
eCl@ss 5.0 27210120
eCl@ss 5.1 27210120
eCl@ss 6.0 27210120
eCl@ss 7.0 27210120
eCl@ss 8.0 27210120
eCl@ss 9.0 27210120
Voltar para cima

ETIM

ETIM 4.0 EC002653
ETIM 5.0 EC002653
ETIM 6.0 EC002653
Voltar para cima

UNSPSC

UNSPSC 6.01 30211506
UNSPSC 7.0901 39121008
UNSPSC 11 39121008
UNSPSC 12.01 39121008
UNSPSC 13.2 39121008
Voltar para cima

Phoenix Contact S.A.

Sintra Business Park,
Edifício n°1
Zona Industrial da Abrunheira
2710-089 SINTRA

Horário: 9h -13h e 14h -18h
(+351) 21 911 2760
  • Criar PDF
  • Recomendar
  • Feedback

Este website usa cookies. Ao continuar a navegar, está a concordar com a nossa política de cookies. Saiba mais sobre a nossa política de privacidade.