Extension module - PSR-SPP- 24DC/TS/SDI8/SDIO4 - 2986041

The figure shows a version with a screw connection

PSR-TRISAFE-M I/O extension module with 8 safe inputs and 4 safe parameterizable channels (choice of safe inputs or outputs), 2 clock/signal outputs; up to SILCL 3, Cat. 4/PL e, SIL 3, EN 50156, plug-in spring-cage terminal block

Price:

Overview

Technical data

Accessories

Approvals

Downloads

Drawings



Connection diagram  

Connection diagram
PSR-TBUS DIN rail connectors are used for cross-wiring between the modules.

Circuit diagram  

Circuit diagram



Back to top

Note

Utilization restriction EMC: class A product, see manufacturer's declaration in the download area
Back to top

Dimensions

Width 22.5 mm
Height 112 mm
Depth 114.5 mm
Back to top

Ambient conditions

Ambient temperature (operation) -20 °C ... 55 °C
Ambient temperature (storage/transport) -20 °C ... 70 °C
Max. permissible relative humidity (operation) 75 % (On average, 85 % occasionally)
Max. permissible humidity (storage/transport) 75 % (On average, 85 % occasionally)
Air pressure (operation) 70 kPa ... 108 kPa (up to 3000 m above sea level)
Air pressure (storage/transport) 66 kPa ... 108 kPa (up to 3500 m above sea level)
Maximum altitude max. 2000 m (See Appendix "Using PSR-TRISAFE modules at altitudes greater than 2000 m above sea level")
Back to top

Power supply

Rated control circuit supply voltage US 24 V DC (Electrical supply via PSR-TBUS)
18 V DC ... 30 V DC (Incl. all tolerances, incl. residual ripple)
Rated control supply current IS Electrical supply via PSR-TBUS
typ. 51.6 mA (No inputs or outputs set, A1/A2 open)
typ. 66 mA (All inputs and safe outputs set)
Filter time typ. 20 ms (Load-dependent, in the event of voltage dips at US)
Status display 1 x green LED, 1 x red LED
Protective circuit Yes, within the scope of the operating voltage limits
Back to top

Digital inputs

Description of the input Digital input
Number of inputs 12 (Of which 4 can be configured as input or output)
Input voltage range "0" signal 0 V DC ... 5 V DC (for safe Off)
Input voltage range "1" signal 11 V DC ... 30 V DC
Current consumption typ. 4 mA
Cable length max. 2000 m
Status display 12 LEDs (green)
Back to top

Digital outputs

Number of outputs 4 (If the configurable inputs/outputs are used as outputs)
Nominal output voltage 24 V DC (Supply via A1/A2)
Nominal output voltage range 18 V DC ... 30 V DC (Incl. all tolerances, incl. residual ripple)
Max. capacitive load max. 1 µF (Electronic components)
Max. inductive load See "Protective circuit"
Test pulses < 1 ms
Short-circuit protection Yes
Note on protection circuit Yes, within the scope of the operating voltage limits
Status display 4x LED green
Back to top

Clock/signal outputs

Output description Digital
Number of outputs 2
Voltage 24 V DC (Supply via A1/A2)
Limiting continuous current 50 mA
Test pulses ~ 1 ms
Short-circuit protection Yes
Back to top

Times

Response time max. 30 ms (plus response time of PSR-TS-SDOR4)
Recovery time < 10 s
Back to top

General

Nominal operating mode 100% operating factor
Net weight 130 g
Mounting position On horizontal DIN rail
Mounting type DIN rail mounting
Degree of protection IP20
IP54
Min. degree of protection of inst. location IP54
Housing material Polyamide PA non-reinforced
Housing color yellow
Back to top

Connection data

Connection method Spring-cage connection
pluggable Yes
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 1.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 1.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 16
Stripping length 8 mm
Back to top

Safety-related characteristic data

Stop category 0
Designation IEC 61508 - High demand
Safety Integrity Level (SIL) 2 (1-channel parameterization)
3 (2-channel parameterization)
Designation IEC 61508 - Low demand
Safety Integrity Level (SIL) 2 (1-channel parameterization)
3 (2-channel parameterization)
Designation EN ISO 13849
Performance level (PL) d (1-channel parameterization)
e (2-channel parameterization)
Category 2 (1-channel parameterization)
4 (2-channel parameterization)
Designation EN 62061
Safety Integrity Level Claim Limit (SIL CL) 2 (1-channel parameterization)
3 (2-channel parameterization)
Designation EN 50156
Safety Integrity Level (SIL) max. 3 (Reference IEC 61508)
Back to top

Standards and Regulations

Designation Air clearances and creepage distances between the power circuits
Standards/regulations DIN EN 50178
Pollution degree 2
Overvoltage category III
Vibration (operation) 2g
Shock (operation) 10g (Δt = 11 ms, three shocks in each space direction)
10g (Δt = 16 ms, continuous shock, 1000 shocks in each space direction)
Back to top

Environmental Product Compliance

REACh SVHC Lead 7439-92-1
China RoHS Environmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values
Back to top

Classifications

eCl@ss

eCl@ss 4.0 40020600
eCl@ss 4.1 40020600
eCl@ss 5.0 27371900
eCl@ss 5.1 27371900
eCl@ss 6.0 27371800
eCl@ss 7.0 27371819
eCl@ss 8.0 27371819
eCl@ss 9.0 27371819
Back to top

ETIM

ETIM 2.0 EC001449
ETIM 3.0 EC001449
ETIM 4.0 EC001417
ETIM 5.0 EC001449
ETIM 6.0 EC001449
ETIM 7.0 EC001449
Back to top

UNSPSC

UNSPSC 6.01 30211901
UNSPSC 7.0901 39121501
UNSPSC 11 39121501
UNSPSC 12.01 39121501
UNSPSC 13.2 39121501