Signal isolator - MACX MCR-EX-SL-RPSS-2I-2I-SP - 2924676

Ex i measuring transducer repeater power supply, 2-channel, HART-transparent. Supplies Ex i 2-conductor measuring transducers and transmits the 4…20 mA signal from the Ex area to the safe area. 5-way electrical isolation, Push-in connection, up to SIL 3, PL.

Price:

Overview

Technical data

Accessories

Approvals

Downloads

Drawings



Block diagram  

Block diagram

Pictogram  

Pictogram



Back to top

Note

Utilization restriction EMC: class A product, see manufacturer's declaration in the download area
Back to top

Dimensions

Width 12.5 mm
Height 116 mm
Depth 114.5 mm
Back to top

Ambient conditions

Ambient temperature (operation) -20 °C ... 60 °C (Any mounting position)
Ambient temperature (storage/transport) -40 °C ... 80 °C
Maximum altitude ≤ 2000 m
Permissible humidity (operation) 10 % ... 95 % (non-condensing)
Degree of protection IP20
Noise immunity EN 61000-6-2 When being exposed to interference, there may be minimal deviations.
Back to top

Input data

Signal input Intrinsically safe
Current input signal 4 mA ... 20 mA
Transmitter supply voltage > 16 V (at 20 mA)
Underload/overload signal range 0 mA ... 24 mA
Back to top

Output data

Signal output Current output
Current output signal 4 mA ... 20 mA (active)
Transmission Behavior 1:1 to input signal
Load/output load current output ≤ 450 Ω (20 mA)
≤ 375 Ω (24 mA)
Output behavior in the event of an error < 3.6 mA (In the event of cable break at the input (as per NE 43))
> 22.5 mA (In the event of cable short circuit at the input (as per NE 43))
Back to top

Power supply

Nominal supply voltage 24 V DC
Supply voltage range 19.2 V DC ... 30 V DC (24 V DC -20%...+25%)
Max. current consumption < 100 mA (24 V / 20 mA)
Power dissipation < 1.4 W (at 24 V DC / 20 mA)
Back to top

Connection data

Connection method Push-in connection
Stripping length 8 mm
Conductor cross section solid 0.2 mm² ... 1.5 mm²
Conductor cross section flexible 0.2 mm² ... 1.5 mm²
Conductor cross section AWG 24 ... 16
Back to top

Connection data 2

Connection name Test socket
Max. diameter 2.3 mm
Back to top

General

No. of channels 2
Maximum transmission error < 0.1 % (of final value)
Transmission error, typical < 0.05 % (of final value)
Maximum temperature coefficient < 0.01 %/K
Step response (10-90%) < 1.3 ms (for 4 mA ... 20 mA step)
Status display Green LED (supply voltage)
Degree of pollution 2
Overvoltage category II
Electromagnetic compatibility Conformance with EMC directive
Interference emission EN 61000-6-4
Housing material PA 6.6-FR
Color gray
Designation Input/output, power supply
Electrical isolation 300 Vrms (Rated insulation voltage (overvoltage category II; degree of pollution 2, safe isolation as per EN 61010-1))
2.5 kV AC (50 Hz, 1 min., test voltage)
Designation Input/output
Electrical isolation 375 V (Peak value in accordance with EN 60079-11)
Designation Input/power supply
Electrical isolation 375 V (Peak value in accordance with EN 60079-11)
Designation Output 1/output 2/ power supply
Electrical isolation 1.5 kV (50 Hz, 1 min., test voltage)
Conformance CE-compliant, additionally EN 61326
ATEX  II (1) G [Ex ia Ga] IIC
 II (1) D [Ex ia Da] IIIC
 II 3(1) G Ex nA [ia Ga] IIC T4 Gc
IECEx [Ex ia Ga] IIC
[Ex ia Da] IIIC
Ex nA [ia Ga] IIC T4 Gc
UL, USA/Canada Class I Div 2; IS for Class I, II, III Div 1
SIL 3
Back to top

Data communication (bypass)

HART function Yes
Protocols supported HART
Back to top

Safety data

Max. output voltage Uo 25.2 V
Max. output current Io 93 mA
Max. output power Po 587 mW
Group IIC
Max. external inductivity Lo 2 mH
Max. external capacitance Co 107 nF
Group IIB
Max. external inductivity Lo 4 mH
Max. external capacitance Co 820 nF
Safety-related maximum voltage Um 253 V AC (125 V DC)
Back to top

Standards and Regulations

Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Conformance CE-compliant, additionally EN 61326
ATEX  II (1) G [Ex ia Ga] IIC
 II (1) D [Ex ia Da] IIIC
 II 3(1) G Ex nA [ia Ga] IIC T4 Gc
IECEx [Ex ia Ga] IIC
[Ex ia Da] IIIC
Ex nA [ia Ga] IIC T4 Gc
UL, USA/Canada Class I Div 2; IS for Class I, II, III Div 1
DNV GL-Temperature B
DNV GL-Humidity B
DNV GL-Vibration A
DNV GL-EMC A
DNV GL-Enclosure Required protection according to the Rules shall be provided upon installation on board
Group IIC
IIB
Back to top

Environmental Product Compliance

REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
Back to top

Classifications

eCl@ss

eCl@ss 4.0 27210100
eCl@ss 4.1 27210100
eCl@ss 5.0 27210100
eCl@ss 5.1 27210100
eCl@ss 6.0 27210100
eCl@ss 7.0 27210120
eCl@ss 8.0 27210120
eCl@ss 9.0 27210120
Back to top

ETIM

ETIM 4.0 EC002653
ETIM 5.0 EC002653
ETIM 6.0 EC002653
ETIM 7.0 EC002653
Back to top

UNSPSC

UNSPSC 6.01 30211506
UNSPSC 7.0901 39121008
UNSPSC 11 39121008
UNSPSC 12.01 39121008
UNSPSC 13.2 39121008
Back to top

PHOENIX CONTACT Ltd

Unit 15C, 906-930 Great South Road, Penrose
Auckland 1061
New Zealand

Phone: 0508 474 636
Toll Free (Local)
09 950 8495
  • Create PDF