Current transformer - PACT RCP-4000A-UIRO-D190 - 2906233

Set consisting of a 4-way signal conditioner with screw connection technology and a Rogowski coil 600 mm in length/190 mm in diameter for AC current measurement on busbars and power lines.
The signal conditioner outputs 8 different standard signals on the output side and has one switching output.

Price:

Overview

Technical data

Accessories

Approvals

Downloads

Drawings



Block diagram  

Block diagram

Back to top

Dimensions

Width 6.2 mm
Height 110.5 mm
Depth 120.5 mm
Back to top

Ambient conditions

Ambient temperature (operation) -30 °C ... 80 °C (Measuring coil)
-40 °C ... 70 °C (Measuring transducer)
Ambient temperature (storage/transport) -40 °C ... 80 °C (Measuring coil)
-40 °C ... 85 °C (Measuring transducer)
Maximum altitude > 4000 m
Permissible humidity (operation) 5 % ... 95 % (non-condensing)
Measuring coil degree of protection IP67 (not assessed by UL)
Measuring transducer degree of protection IP20
Noise immunity EN 61000-6-2 When being exposed to interference, there may be minimal deviations.
Back to top

Measuring transducer supply

Nominal supply voltage 24 V DC
Nominal supply voltage range 9.6 V DC ... 30 V DC
Power consumption ≤ 1 W (at IOUT = 20 mA, 9.6 V DC, 600 Ω load)
Back to top

Measuring coil input data

Frequency measuring range 40 Hz ... 20000 Hz
Position error < 1 %
Linearity error 0.1 %
Back to top

Measuring transducer input data

Measuring ranges (current) 100 A 250 A 400 A 630 A 1000 A 1500 A 2000 A 4000 A
Configurable/programmable Via DIP switches
Back to top

Measuring transducer signal input

Input signal (at 50 Hz) 100 mV (1000 A)
Input impedance > 100 kΩ
Back to top

Measuring coil signal output

Output signal (at 50 Hz) 100 mV (no load, at 1,000 A)
Output voltage (in no-load operation) VOUT = M * dI/dt
Output voltage (sinusoidal, in no-load operation) 100 mV (VOUT = 2 * π * M * f * I (M = 0.318 μH; example: At 50 Hz; I = 1,000 A))
Back to top

Measuring transducer signal output

Current output signal 0 mA ... 20 mA (via DIP switch)
4 mA ... 20 mA (via DIP switch)
0 mA ... 10 mA (via DIP switch)
2 mA ... 10 mA (via DIP switch)
0 mA ... 21 mA (can be set via software)
Voltage output signal 0 V ... 10 V (via DIP switch)
2 V ... 10 V (via DIP switch)
0 V ... 5 V (via DIP switch)
1 V ... 5 V (via DIP switch)
0 V ... 10.5 V (can be set via software)
Load/output load current output ≤ 600 Ω (20 mA)
Back to top

General data, measuring coil

Length of measuring coil 600 mm
Diameter of measuring coil 8.3 mm ±0.2 mm
Length of signal cable 3000 mm
Conductor structure signal line 2x 0.22 mm (Signal (tinned))
1x 0.22 mm (Shielding (tinned))
Coil material Elastollan
Housing material PC
Insulation double insulation
Rated insulation voltage 1000 V AC (rms CAT III)
600 V AC (rms CAT IV)
Test voltage 10.45 kV (DC / 1 min.)
Basic accuracy <± 0.21 %
UL, USA/Canada UL 61010 Recognized
Back to top

General data for measuring transducer

Maximum transmission error ≤ 0.5 % (From the range end value)
Frequency range 16 Hz ... 1000 Hz
Housing material PBT
Test voltage 3 kV (50 Hz, 1 min.)
UL, USA/Canada UL 508 Listed
Back to top

General data

Standards/regulations IEC 61010-1
IEC 61010-2-032
Typical measuring error < 1 %
Back to top

Connection data

Connection name Measuring transducer side
Connection method Screw connection
Stripping length 10 mm
Screw thread M3
Conductor cross section solid 0.2 mm² ... 1.5 mm²
Conductor cross section flexible 0.2 mm² ... 1.5 mm²
Conductor cross section AWG 26 ... 16
Torque 0.5 Nm ... 0.6 Nm
Back to top

Standards and Regulations

Electromagnetic compatibility Conformance with EMC Directive 2004/108/EC
Noise emission EN 61000-6-4
Standards/regulations IEC 61010-1
IEC 61010-2-032
Rated insulation voltage 300 V
Pollution degree 2
Overvoltage category II
Electrical isolation Reinforced insulation in accordance with IEC 61010-1
Conformance CE-compliant
Back to top

Conformance/approvals

Designation CE
Identification CE-compliant
Back to top

Environmental Product Compliance

REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
Back to top

Classifications

eCl@ss

eCl@ss 4.0 27210900
eCl@ss 4.1 27210900
eCl@ss 5.0 27210900
eCl@ss 5.1 27210900
eCl@ss 6.0 27210900
eCl@ss 7.0 27210902
eCl@ss 8.0 27210902
eCl@ss 9.0 27210902
Back to top

ETIM

ETIM 3.0 EC002048
ETIM 4.0 EC002048
ETIM 5.0 EC002048
ETIM 6.0 EC002048
ETIM 7.0 EC002048
Back to top

UNSPSC

UNSPSC 13.2 39121032
Back to top