Monitoring relay - EMD-BL-3V-400-PT - 2903526

Monitoring relay for monitoring 3-phase voltages of 400 V AC ±30%, window or window with phase sequence, 1 PDT, with push-in connection

Price:

Overview

Technical data

Approvals

Downloads

Drawings



Block diagram  

Block diagram

Back to top

Dimensions

Width 17.5 mm
Height 88 mm
Depth 65.5 mm
Back to top

Ambient conditions

Ambient temperature (operation) -25 °C ... 55 °C
Ambient temperature (storage/transport) -25 °C ... 70 °C
Permissible humidity (operation) 15 % ... 85 %
Degree of protection IP40 (housing) / IP20 (connection terminal blocks)
Noise immunity EN 61000-6-2
Back to top

Input data

Nominal input voltage UN ±30 % (3~ 400/230 V)
Maximum temperature coefficient ≤ 0.05 %
Function Window, phase sequence
Min. setting range 70 % ... 120 % (From UN)
Max. setting range 80 % ... 130 % (From UN)
Min setting range of the voltage threshold value 280 V AC ... 480 V AC
Max. setting range of the voltage threshold value 320 V AC ... 519 V AC
Setting range for response delay 0.1 s ... 10 s
Basic accuracy ≤ 5 % (of the nominal value)
Setting accuracy ± 5 % (of scale end value)
Repeat accuracy ≤ 2 %
Recovery time > 500 ms
Back to top

Contact side

Contact type 1 floating PDT
Maximum switching voltage 250 V AC (in acc. with IEC 60664-1)
Interrupting rating (ohmic load) max. 1250 VA (5 A / 250 V AC)
Output fuse 5 A (fast-blow)
Back to top

Power supply

Supply voltage ±30 % (= measuring voltage)
Back to top

General

Mechanical service life 15x 106 cycles
Operating mode 100% operating factor
Mounting position any
Assembly instructions on standard DIN rail NS 35 in accordance with EN 60715
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Overvoltage category III, 300 V basic insulation (DIN EN 60947-5-1)
Housing insulation material Polyamide PA 6.6, self-extinguishing
Color gray
Rated insulation voltage 519 V (Supply circuit/measuring circuit (DIN EN 60947-5-1))
Conformance CE-compliant
UL, USA/Canada UL/C-UL listed UL 508
Back to top

Connection data

Connection method Push-in connection
Stripping length 8 mm
Conductor cross section solid 0.14 mm² ... 2.5 mm²
Conductor cross section flexible 0.14 mm² ... 2.5 mm²
Conductor cross section AWG 26 ... 14
Back to top

Standards and Regulations

Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Noise emission EN 61000-6-3
Noise immunity EN 61000-6-2
Low Voltage Directive Conformance with Low Voltage Directive 2006/95/EC (valid until 2016-04-19) / 2014/35/EU (valid from 2016-04-20)
Conformance CE-compliant
UL, USA/Canada UL/C-UL listed UL 508
Back to top

Environmental Product Compliance

China RoHS Environmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values
Back to top

Classifications

eCl@ss

eCl@ss 5.0 27371801
eCl@ss 5.1 27371800
eCl@ss 6.0 27371800
eCl@ss 7.0 27371801
eCl@ss 8.0 27371801
eCl@ss 9.0 27371801
Back to top

ETIM

ETIM 2.0 EC001438
ETIM 3.0 EC001438
ETIM 4.0 EC001438
ETIM 5.0 EC001438
ETIM 6.0 EC001438
ETIM 7.0 EC001438
Back to top

UNSPSC

UNSPSC 6.01 30211916
UNSPSC 7.0901 39121535
UNSPSC 11 39121535
UNSPSC 12.01 39121535
UNSPSC 13.2 41113620
Back to top

PHOENIX CONTACT Ltd

Unit 15C, 906-930 Great South Road, Penrose
Auckland 1061
New Zealand

Phone: 0508 474 636
Toll Free (Local)
09 950 8495
  • Create PDF
  • Recommend
  • Feedback

This website uses cookies, by continuing to browse, you agree to our cookie policy. Read our privacy policy for more information.