Signal conditioner - MINI MCR-2-U-UI-PT - 2902021

3-way signal conditioner, with configurable input/output, for electrical isolation and conversion of analog signals in the mV and V range, unipolar as well as bipolar. Push-in connection technology, standard configuration.

Price:

Overview

Technical data

Accessories

Approvals

Downloads

Drawings



Block diagram  

Block diagram

Pictogram  

Pictogram



Back to top

Dimensions

Width 6.2 mm
Height 110.5 mm
Depth 120.5 mm
Back to top

Ambient conditions

Ambient temperature (operation) -40 °C ... 70 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Permissible humidity (operation) 5 % ... 95 % (non-condensing)
Degree of protection IP20
Noise immunity EN 61000-6-2 When being exposed to interference, there may be minimal deviations.
Back to top

Input data

Number of inputs 1
Configurable/programmable Yes
Voltage input signal -50 mV ... 50 mV (via DIP switch)
0 mV ... 50 mV (via DIP switch)
-60 mV ... 60 mV (via DIP switch)
0 mV ... 60 mV (via DIP switch)
-75 mV ... 75 mV (via DIP switch)
0 mV ... 75 mV (via DIP switch)
-80 mV ... 80 mV (via DIP switch)
0 mV ... 80 mV (via DIP switch)
-100 mV ... 100 mV (via DIP switch)
0 mV ... 100 mV (via DIP switch)
-120 mV ... 120 mV (via DIP switch)
0 mV ... 120 mV (via DIP switch)
-150 mV ... 150 mV (via DIP switch)
0 mV ... 150 mV (via DIP switch)
-200 mV ... 200 mV (via DIP switch)
0 mV ... 200 mV (via DIP switch)
-240 mV ... 240 mV (via DIP switch)
0 mV ... 240 mV (via DIP switch)
-300 mV ... 300 mV (via DIP switch)
0 mV ... 300 mV (via DIP switch)
-500 mV ... 500 mV (via DIP switch)
0 mV ... 500 mV (via DIP switch)
-600 mV ... 600 mV (via DIP switch)
0 mV ... 600 mV (via DIP switch)
-750 mV ... 750 mV (via DIP switch)
0 mV ... 750 mV (via DIP switch)
-800 mV ... 800 mV (via DIP switch)
0 mV ... 800 mV (via DIP switch)
-1 V ... 1 V (via DIP switch)
0 V ... 1 V (via DIP switch)
-1.2 V ... 1.2 V (via DIP switch)
0 V ... 1.2 V (via DIP switch)
-1.5 V ... 1.5 V (via DIP switch)
0 V ... 1.5 V (via DIP switch)
-2 V ... 2 V (via DIP switch)
0 V ... 2 V (via DIP switch)
-2.4 V ... 2.4 V (via DIP switch)
0 V ... 2.4 V (via DIP switch)
-3 V ... 3 V (via DIP switch)
0 V ... 3 V (via DIP switch)
-5 V ... 5 V (via DIP switch)
0 V ... 5 V (via DIP switch)
-6 V ... 6 V (via DIP switch)
0 V ... 6 V (via DIP switch)
-7.5 V ... 7.5 V (via DIP switch)
0 V ... 7.5 V (via DIP switch)
-8 V ... 8 V (via DIP switch)
0 V ... 8 V (via DIP switch)
-10 V ... 10 V (via DIP switch)
0 V ... 10 V (via DIP switch)
-12 V ... 12 V (via DIP switch)
0 V ... 12 V (via DIP switch)
-15 V ... 15 V (via DIP switch)
0 V ... 15 V (via DIP switch)
-20 V ... 20 V (via DIP switch)
0 V ... 20 V (via DIP switch)
-24 V ... 24 V (via DIP switch)
0 V ... 24 V (via DIP switch)
-30 V ... 30 V (via DIP switch)
0 V ... 30 V (via DIP switch)
max. input voltage 33 V
Input resistance of voltage input > 10 kΩ
Back to top

Output data

Number of outputs 1
Configurable/programmable Yes
Voltage output signal 0 V ... 5 V (via DIP switch)
1 V ... 5 V (via DIP switch)
-5 V ... 5 V (via DIP switch)
0 V ... 10 V (via DIP switch)
2 V ... 10 V (via DIP switch)
-10 V ... 10 V (via DIP switch)
Current output signal 0 mA ... 20 mA (via DIP switch)
4 mA ... 20 mA (via DIP switch)
Max. output current 22 mA
Short-circuit current < 32 mA
Load/output load voltage output ≥ 10 kΩ
Load/output load current output ≤ 600 Ω (at 20 mA)
Ripple < 20 mVPP (at 600 Ω)
< 20 mVPP (at 600 Ω)
Back to top

Power supply

Nominal supply voltage 24 V DC
Supply voltage range 9.6 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
Typical current consumption 25 mA (Current output, at 24 V DC incl. load)
54 mA (Current output, at 12 V DC incl. load)
Power consumption ≤ 800 mW (at IOUT = 20 mA, 9.6 V DC, 600 Ω load)
Back to top

Connection data

Connection method Push-in connection
Stripping length 10 mm
Conductor cross section solid 0.14 mm² ... 2.5 mm² (with ferrule)
0.14 mm² ... 2.5 mm² (without ferrule)
Conductor cross section flexible 0.14 mm² ... 2.5 mm²
Conductor cross section AWG 24 ... 12 (flexible)
Back to top

General

No. of channels 1
Maximum transmission error ≤ 0.1 % (of final value)
Maximum temperature coefficient 0.01 %/K
Limit frequency (3 dB) 30 Hz (via DIP switch)
5 kHz (via DIP switch)
Step response (10-90%) < 8.5 ms (with 30 Hz filter)
Protective circuit Transient protection
Electrical isolation Reinforced insulation in accordance with IEC 61010-1
Overvoltage category II
Degree of pollution 2
Rated insulation voltage 300 V
Test voltage, input/output/supply 3 kV (50 Hz, 1 min.)
Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Noise immunity EN 61000-6-2 When being exposed to interference, there may be minimal deviations.
Color gray
Housing material PBT
Mounting position any
Assembly instructions The T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715.
Conformance CE-compliant
ATEX  II 3 G Ex nA IIC T4 Gc X
UL, USA/Canada UL 508 Listed
Class I, Div. 2, Groups A, B, C, D T6
Class I, Zone 2, Group IIC T6
Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 2
Back to top

EMC data

Designation Electromagnetic RF field
Standards/regulations EN 61000-4-3
Designation Fast transients (burst)
Standards/regulations EN 61000-4-4
Designation Conducted interferences
Standards/regulations EN 61000-4-6
Back to top

Standards and Regulations

Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Standards/regulations EN 61000-4-2
Designation Electromagnetic RF field
Standards/regulations EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
Designation Conducted interferences
Standards/regulations EN 61000-4-6
Electrical isolation Reinforced insulation in accordance with IEC 61010-1
Conformance CE-compliant
ATEX  II 3 G Ex nA IIC T4 Gc X
UL, USA/Canada UL 508 Listed
Class I, Div. 2, Groups A, B, C, D T6
Class I, Zone 2, Group IIC T6
Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 2
Back to top

Environmental Product Compliance

China RoHS Environmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
Back to top

Classifications

eCl@ss

eCl@ss 4.0 27210120
eCl@ss 4.1 27210120
eCl@ss 5.0 27210120
eCl@ss 5.1 27210100
eCl@ss 6.0 27210100
eCl@ss 7.0 27210120
eCl@ss 8.0 27210120
eCl@ss 9.0 27210120
Back to top

ETIM

ETIM 4.0 EC002653
ETIM 5.0 EC002653
ETIM 6.0 EC002653
ETIM 7.0 EC002653
Back to top

UNSPSC

UNSPSC 6.01 30211502
UNSPSC 7.0901 39121004
UNSPSC 11 39121004
UNSPSC 12.01 39121004
UNSPSC 13.2 39121008
Back to top

PHOENIX CONTACT Ltd

Unit 15C, 906-930 Great South Road, Penrose
Auckland 1061
New Zealand

Phone: 0508 474 636
Toll Free (Local)
09 950 8495
  • Create PDF
  • Recommend
  • Feedback

This website uses cookies, by continuing to browse, you agree to our cookie policy. Read our privacy policy for more information.

Close