Head-mounted transducer - MCR-SL-HT-PT 100-I - 2864516

Price:

Overview

Technical data

Accessories

Approvals

Downloads

Drawings



Connection diagram  

Connection diagram

Block diagram  

Block diagram
Block diagram MCR-SL-HT-PT 100-I



Dimensional drawing  

Dimensional drawing

Pictogram  

Pictogram



Circuit diagram  

Circuit diagram

Back to top

Ambient conditions

Ambient temperature (operation) -40 °C ... 85 °C
Degree of protection IP00, IP54 (integrated in the connecting head)
Noise immunity EN 61326-1 (IEC 61326) and NAMUR NE 21
Back to top

Input data

Configurable/programmable Yes, programmable
Sensor types (RTD) that can be used Pt 100 ; minimum measurement range 10 K
Connection technology 2, 3, 4-wire
Back to top

Output data

Output name Current output
Configurable/programmable Yes
Current output signal 4 mA ... 20 mA
20 mA ... 4 mA
Output current with wire break ≤ 3.6 mA or ≥ 21 mA (adjustable)
Output current with short-circuit ≤ 3.6 mA or ≥ 21 mA (adjustable)
Output current range with overrange/underrange ≤ 20.5 mA / ≥ 3.8 mA (linear increase/decrease)
Load/output load current output max (Vsupply - 10 V) / 0.023 A (current output)
Back to top

Power supply

Designation Loop-powered
Supply voltage range 10 V DC ... 35 V DC
Max. current consumption < 3.5 mA
Back to top

Connection data

Connection method Screw connection
Stripping length 8 mm
Screw thread M3
Conductor cross section solid 0.2 mm² ... 1.75 mm²
Conductor cross section flexible 0.2 mm² ... 1.75 mm²
Conductor cross section AWG 24 ... 15
Back to top

General

Transmission error resistance thermometer 0.2 K
Step response (10-90%) < 2 s
Switch-on delay 4 s
Noise emission EN 61326-1 (IEC 61326) and NAMUR NE 21
Noise immunity EN 61326-1 (IEC 61326) and NAMUR NE 21
Color green
Housing material Polycarbonate, PC
Mounting position any
Assembly instructions Connection head according to DIN 43729 form B
Configuration Using MCR-PI-CONF-WIN configuration software package
Conformance CE-compliant
UL, USA/Canada Class I, Div. 2, Groups A, B, C, D
Back to top

Standards and Regulations

Noise emission EN 61326-1 (IEC 61326) and NAMUR NE 21
Noise immunity EN 61326-1 (IEC 61326) and NAMUR NE 21
Connection in acc. with standard CUL
Conformance CE-compliant
UL, USA/Canada Class I, Div. 2, Groups A, B, C, D
Back to top

Environmental Product Compliance

China RoHS Environmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values
Back to top

Classifications

eCl@ss

eCl@ss 4.0 27210120
eCl@ss 4.1 27210120
eCl@ss 5.0 27210120
eCl@ss 5.1 27200200
eCl@ss 6.0 27200200
eCl@ss 7.0 27200206
eCl@ss 8.0 27200206
eCl@ss 9.0 27210129
Back to top

ETIM

ETIM 2.0 EC001446
ETIM 3.0 EC001446
ETIM 4.0 EC001446
ETIM 5.0 EC001446
ETIM 6.0 EC002919
ETIM 7.0 EC002919
Back to top

UNSPSC

UNSPSC 6.01 30211506
UNSPSC 7.0901 39121008
UNSPSC 11 39121008
UNSPSC 12.01 39121008
UNSPSC 13.2 41112105
Back to top

PHOENIX CONTACT Ltd

Unit 15C, 906-930 Great South Road, Penrose
Auckland 1061
New Zealand

Phone: 0508 474 636
Toll Free (Local)
09 950 8495
  • Create PDF