Dimensions

Height 45 mm
Width 17.7 mm
Depth 52 mm
Horizontal pitch 1 Div.
Complete module height 90 mm
Complete module width 17.7 mm
Complete module depth 65.5 mm
Back to top

Ambient conditions

Ambient temperature (operation) -40 °C ... 85 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Altitude ≤ 2000 m (amsl (above mean sea level))
Degree of protection IP20
Back to top

General

Housing material PA 6.6
Flammability rating according to UL 94 V-0
Color sky blue RAL 5015
Mounting type on base element
Type Male
Number of positions 4
Direction of action Line-Line & Line-Signal Ground/Shield & Signal Ground/Shield-Earth Ground
Arrester can be tested with CHECKMASTER from software version: From SW rev. 1.00
Back to top

Protective circuit

IEC test classification C1
C2
C3
D1
Nominal voltage UN 24 V DC
Maximum continuous voltage UC 30 V DC
21 V AC
Rated current 500 mA (40 °C)
Operating effective current IC at UC ≤ 5 µA
Residual current IPE ≤ 4 µA
Nominal discharge current In (8/20) µs (line-line) 308 A
Nominal discharge current In (8/20) µs (line-earth) 10 kA
Pulse discharge current Iimp (10/350) µs (line-earth) 1 kA
2 kA (in total)
Total discharge current Itotal (8/20) µs 20 kA
Total discharge current Itotal (10/350) µs 2 kA
Max. discharge current Imax (8/20) µs maximum (line-line) 308 A
Max. discharge current Imax (8/20) µs maximum (line-earth) 20 kA (in total)
Nominal pulse current Ian (10/1000) µs (line-line) 59 A
Output voltage limitation at 1 kV/µs (line-line) spike ≤ 45 V
Output voltage limitation at 1 kV/µs (line-earth) spike ≤ 1 kV
Output voltage limitation at 1 kV/µs (line-line) static ≤ 45 V
Output voltage limitation at 1 kV/µs (line-earth) static ≤ 1 kV
Residual voltage at In (line-line) ≤ 70 V
Residual voltage with Ian (10/1000) µs (line-line) ≤ 65 V
Voltage protection level Up (line-line) ≤ 60 V (C1 - 500 V / 250 A)
≤ 50 V (C3 - 10 A)
≤ 50 V (C3 - 25 A)
Voltage protection level Up (line-earth) ≤ 1 kV (C1 - 1 kV/500 A)
≤ 1 kV (C2 - 2 kV/1 kA)
≤ 1 kV (C2 - 10 kV / 5 kA)
≤ 1 kV (D1 - 1 kA)
Response time tA (line-line) ≤ 1 ns
Response time tA (line-earth) ≤ 100 ns
Input attenuation aE, sym. typ. 0.1 dB (≤ 1 MHz / 50 Ω)
typ. 0.1 dB (≤ 500 kHz / 150 Ω)
typ. 0.1 dB (≤ 100 kHz / 600 Ω)
Cut-off frequency fg (3 dB), sym. in 50 Ohm system typ. 7 MHz
Cut-off frequency fg (3 dB), sym. in 150 Ohm system typ. 2.5 MHz
Cut-off frequency fg (3 dB), sym. in 600 Ohm system typ. 600 kHz
Resistance in series 0 Ω
Surge protection fault message none
Max. required back-up fuse 500 mA (T)
Impulse durability (line-line) C1 - 0.5 kV / 250 A
C3 - 10 A
C3 - 25 A
Impulse durability (line-earth) C1 - 1 kV / 500 A
C2 - 2 kV / 1 kA
C2 - 10 kV / 5 kA
D1 - 1 kA
Alternating current carrying capacity (line-earth) 5 A - 1 s
Back to top

Connection data

Connection method Screw connection (in connection with the base element)
Screw thread M3
Tightening torque 0.5 Nm
Stripping length 8 mm
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section solid 0.2 mm² ... 4 mm²
Conductor cross section AWG 24 ... 12
Back to top

Standards and Regulations

Standards/specifications EN 61643-21 A2:2013
EN 60079-0 2012
EN 60079-11 2012
EN 60079-26 2007
IEC 61643-21 A2:2012
IEC 60079-0 2011
IEC 60079-11 2011
IEC 60079-26 2006
Back to top

General

Maximum inner capacitance Ci 1.1 nF
Max. internal inductance Li 1 µH
Maximum inner time factor (Ri/Li) ≤ 10 µs
Max. input current Ii 500 mA (T4 / ≤ 80°C)
500 mA (T5 / ≤ 55 °C)
500 mA (T6 / ≤ 40 °C)
Max. input voltage Ui 30 V DC
max. input power Pi 850 mW (T4 / ≤ 80°C)
700 mW (T5 / ≤ 55 °C)
700 mW (T6 / ≤ 40 °C)
Ambient temperature (operation) -40 °C ... 80 °C (T4)
-40 °C ... 55 °C (T5)
-40 °C ... 40 °C (T6)
Back to top

Conformity / approvals

ATEX  II 1G Ex ia IIC T4...T6 Ga
 II 1D Ex ia IIIC T135°C...T85°C Da
IECEx Ex ia IIC T4...T6 Ga
Ex ia IIIC T135 °C...T85 °C Da
Back to top

Environmental Product Compliance

China RoHS Environmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values
Back to top

Classifications

eCl@ss

eCl@ss 4.0 27140201
eCl@ss 4.1 27130801
eCl@ss 5.0 27130801
eCl@ss 5.1 27130800
eCl@ss 6.0 27130800
eCl@ss 7.0 27130807
eCl@ss 8.0 27130807
eCl@ss 9.0 27130807
Back to top

ETIM

ETIM 2.0 EC000943
ETIM 3.0 EC000943
ETIM 4.0 EC000943
ETIM 5.0 EC000943
ETIM 6.0 EC000943
ETIM 7.0 EC000943
Back to top

UNSPSC

UNSPSC 6.01 30212010
UNSPSC 7.0901 39121610
UNSPSC 11 39121610
UNSPSC 12.01 39121610
UNSPSC 13.2 39121620