Safety module - AXL F SSDO8/3 1F - 2702264

Safety-related digital output module, IP20 protection, for the SafetyBridge system. The module has four safe digital outputs with two-channel occupancy or 8 safe digital outputs with single-channel occupancy

Price:

Overview

Technical data

Accessories

Approvals

Downloads

Drawings



Dimensional drawing  

Dimensional drawing

Back to top

Dimensions

Dimensional drawing
Width 53.6 mm
Height 126.1 mm
Depth 54 mm
Note on dimensions Housing dimensions
Back to top

Ambient conditions

Ambient temperature (operation) -35 °C ... 60 °C (Mounting position: any)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Permissible humidity (operation) 10 % ... 75 % (on average, 85% infrequently, non-condensing)
Permissible humidity (storage/transport) 10 % ... 75 % (non-condensing)
Air pressure (operation) 70 kPa ... 108 kPa (up to 3000 m above sea level)
Air pressure (storage/transport) 66 kPa ... 108 kPa (up to 3500 m above sea level)
Degree of protection IP20
Back to top

Interfaces

Designation Axioline F local bus
No. of channels 1
Connection method Bus base module
Back to top

Digital outputs

Output name Digital outputs
Connection method Direct plug-in technology
Connection technology 2, 3-wire
Number of outputs 4 (with two-channel assignment)
8
Type of protection Overload protection, freewheeling circuit for inductive loads,
Discharge circuit for accelerated discharge of capacitive loads
Output voltage 24 V DC
Output current max. 2 A (per channel)
max. 1.5 A (per channel according to CULUS)
max. 4 A (per group)
max. 3 A (per group according to CULUS)
max. 8 A (Total current of all outputs; Please observe the notes in the user manual.)
max. 6 A (Total current of all outputs according to CULUS)
Maximum output current per channel 2 A
Maximum output current per module / terminal block 8 A
Back to top

General

Mounting type DIN rail
Net weight 222 g
Note on weight specifications with connectors and bus base module
Back to top

Axioline potentials

Designation Axioline F local bus supply (UBus)
Supply voltage 5 V DC (via bus base module)
Current consumption typ. 260 mA (all outputs set; power supply by UO of 19.2 V DC to 30.2 V DC)
max. 280 mA
Designation Supply for digital output modules (UO)
Supply voltage 24 V DC
Supply voltage range 19.2 V DC ... 30.2 V DC (including all tolerances, including ripple)
Current consumption typ. 25 mA (all outputs set; power supply by UO with 30.2 V DC; without power supply to the actuator)
Type of protection Protection against polarity reversal, EMC protective circuit, undervoltage detection
Back to top

Safety-related characteristic data

Designation IEC 61508 - High demand
Safety Integrity Level (SIL) max. 3 (two channel; dependent in parameterization and wiring)
Designation IEC 61508 - Low demand
Safety Integrity Level (SIL) max. 3 (two channel; dependent in parameterization and wiring)
Designation EN ISO 13849
Performance level (PL) max. e (two channel; dependent in parameterization and wiring)
Category max. 4 (two channel; dependent in parameterization and wiring)
Designation EN 62061
Safety Integrity Level Claim Limit (SIL CL) max. 3 (two channel; dependent in parameterization and wiring)
Back to top

Standards and Regulations

Protection class III, (IEC 61140, EN 61140, VDE 0140-1)
Back to top

Environmental Product Compliance

REACh SVHC
Lead 7439-92-1
China RoHS Environmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values
Back to top

Classifications

eCl@ss

eCl@ss 5.1 27242600
eCl@ss 6.0 27242600
eCl@ss 7.0 27242604
eCl@ss 8.0 27242604
eCl@ss 9.0 27242604
Back to top

ETIM

ETIM 5.0 EC001599
ETIM 6.0 EC001599
ETIM 7.0 EC001599
Back to top

UNSPSC

UNSPSC 13.2 32151602