Type 3 surge protection device - BLT-T3-230-A - 1038841

Type 3 surge protection for universal installation in installation boxes, sill-type trunking, underfloor installations. Circuit with thermal monitoring, acoustic fault warning.

Price:

Overview

Technical data

Accessories

Downloads

Drawings



Dimensional drawing  

Dimensional drawing

Circuit diagram  

Circuit diagram



Back to top

Dimensions

Height 31 mm
Width 12.5 mm
Depth 36 mm
Back to top

Ambient conditions

Degree of protection IP20 (Installed)
Ambient temperature (operation) -20 °C ... 70 °C
Ambient temperature (storage/transport) -20 °C ... 70 °C
Altitude ≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation) 5 % ... 95 %
Back to top

General

EN type T3
IEC power supply system TN-S
TT
Number of ports One
Mode of protection L-N
L-PE
N-PE
Mounting type in device sockets and conductor routing systems made of insulating material
Color light grey RAL 7035
Housing material PA 6.6-FR
Degree of pollution 2
Flammability rating according to UL 94 V-0
Type Socket mounting module
Number of positions 2
Surge protection fault message Acoustic
Back to top

Protective circuit

Nominal voltage UN 230 V AC (TN-S)
230 V AC (TT - only in use with RCD)
Nominal frequency fN 50 Hz (60 Hz)
Maximum continuous voltage UC 255 V AC
Residual current IPE ≤ 5 µA
Reference test voltage UREF 255 V AC
Max. discharge current Imax (8/20) µs 4 kA
Combination wave UOC 6 kV
Voltage protection level Up ≤ 1.5 kV
TOV behavior at UT (L-N) 440 V AC (5 s / withstand mode)
440 V AC (120 min / withstand mode)
TOV behavior at UT (L-PE) 440 V AC (5 s / withstand mode)
440 V AC (120 min / withstand mode)
1455 V AC (200 ms / safe failure mode)
TOV behavior at UT (N-PE) 1200 V AC (200 ms / safe failure mode)
Response time tA (L-N) ≤ 25 ns
Response time tA (L-PE) ≤ 100 ns
Response time tA (N-PE) ≤ 100 ns
Max. required back-up fuse 16 A (MCB B)
Short-circuit current rating ISCCR 1.5 kA AC
Back to top

Connection data

Connection method Single wires
Back to top

Standards and Regulations

Standards/specifications IEC 61643-11 2011
EN 61643-11 2012
Back to top

Environmental Product Compliance

REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
Back to top

Classifications

eCl@ss

eCl@ss 6.0 27130800
eCl@ss 7.0 27130806
eCl@ss 8.0 27130806
eCl@ss 9.0 27130806
Back to top

ETIM

ETIM 5.0 EC000942
ETIM 6.0 EC000942
ETIM 7.0 EC000942
Back to top

PHOENIX CONTACT Ltd

Unit 15C, 906-930 Great South Road, Penrose
Auckland 1061
New Zealand

Phone: 0508 474 636
Toll Free (Local)
09 950 8495
  • Create PDF
  • Recommend
  • Feedback

This website uses cookies, by continuing to browse, you agree to our cookie policy. Read our privacy policy for more information.

Close