Monitoring relay - EMD-SL-PH-690 - 2905597

Monitoring relay for monitoring phase sequence, phase failure, and asymmetry for 208 V AC ... 690 V AC from 3-phase voltages, 2 PDTs, with screw connection

Price:

Overview

Technical data

Approvals

Downloads

Drawings



Block diagram  

Block diagram

Back to top

Dimensions

Width 22.5 mm
Height 90 mm
Depth 113 mm
Back to top

Ambient conditions

Ambient temperature (operation) -25 °C ... 70 °C (C300)
-25 °C ... 55 °C (B300)
Ambient temperature (storage/transport) -25 °C ... 70 °C
Permissible humidity (operation) 15 % ... 85 %
Degree of protection IP40 (Housing)
IP20 (Connection terminal blocks)
Noise immunity EN 61326-1
Back to top

Input data

Nominal input voltage UN 690 V (3~ 208 V ... 690 V)
Input voltage range 177 V ... 794 V (3~)
Function Undervoltage, phase sequence, phase failure
Min setting range of the voltage threshold value 177 V AC
Max. setting range of the voltage threshold value 794 V AC
Setting range for response delay 0.1 s ... 10 s
Basic accuracy ≤ 3 % (of scale end value)
Setting accuracy ≤ 5 % (of scale end value)
Repeat accuracy ≤ 2 %
Asymmetry 25 %
Recovery time > 500 ms
Back to top

Contact side

Contact type 2 floating PDT contacts
Maximum switching voltage 400 V AC
Interrupting rating (ohmic load) max. 1250 VA (5 A/250 V AC at +55 °C)
150 VA (5 A/30 V DC at +55°C)
75 VA (2.5 A/30 V DC at +70°C)
Output fuse 5 A (fast-blow)
Back to top

Power supply

Supply voltage ±15 % (= measuring voltage)
Back to top

General

Mechanical service life 20x 106 cycles
Operating mode 100% operating factor
Mounting position any
Assembly instructions on standard DIN rail NS 35 in accordance with EN 60715
Electromagnetic compatibility Conformance with EMC Directive 2004/108/EC
Housing insulation material Polyamide PA, self-extinguishing
Color green
Back to top

Connection data

Connection method Screw connection
Stripping length 8 mm
Conductor cross section solid 0.5 mm² ... 2.5 mm²
Conductor cross section flexible 0.5 mm² ... 2.5 mm²
Conductor cross section AWG 20 ... 14
Tightening torque 1 Nm
Back to top

Standards and Regulations

Electromagnetic compatibility Conformance with EMC Directive 2004/108/EC
Noise emission EN 61326-1
Noise immunity EN 61326-1
Standards/regulations IEC 60664-1
Rated insulation voltage 250 V (Output circuit)
Rated surge voltage 6 kV
Pollution degree 3
Overvoltage category III
Low Voltage Directive Conformance with LV directive 2006/95/EC
Back to top

Environmental Product Compliance

China RoHS Environmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values
Back to top

Classifications

eCl@ss

eCl@ss 10.0.1 27371803
eCl@ss 5.0 27371800
eCl@ss 5.1 27371800
eCl@ss 6.0 27371800
eCl@ss 7.0 27371803
eCl@ss 8.0 27371803
eCl@ss 9.0 27371803
Back to top

ETIM

ETIM 4.0 EC001441
ETIM 5.0 EC001441
ETIM 6.0 EC001441
ETIM 7.0 EC001441
Back to top

UNSPSC

UNSPSC 13.2 41113637
UNSPSC 18.0 39121106
UNSPSC 19.0 39121106
UNSPSC 20.0 39121106
UNSPSC 21.0 39121106
Back to top

PHOENIX CONTACT (I) Pvt. Ltd.

A-58/2, Okhla Industrial Area, Phase - II,
New Delhi-110 020
+91.11.30262800
  • Create PDF
  • Recommend
  • Feedback