I/O module - IBS RT 24 AI 8-T - 2723194

INTERBUS-RT analog input/output module, 8 inputs, 24 V DC, 2-wire connection method, IP20 protection, without connector set

Price:

Overview

Technical data

Accessories

Downloads

Drawings



Connection diagram  

Connection diagram
a = current sensor
b = voltage sensor

Dimensional drawing  

Dimensional drawing



Back to top

Dimensions

Width 125 mm
Height 44 mm
Length 146 mm
Back to top

Interfaces

Interface INTERBUS remote bus (incoming/outgoing)
Connection method D-SUB-9
Transmission physics Copper
Back to top

Power supply

Max. current consumption 150 mA
I/O voltage ± 24 V DC 5 % (ripple)
I/O voltage range 19.2 V DC ... 30 V DC
Back to top

Inputs

No. of channels 8
Connection technology 2-wire (optionally 3, 4-wire)
Voltage input signal 0 V ... 5 V
1 V ... 5 V
-5 V ... 5 V
0 V ... 10 V
-10 V ... 10 V
Basic error limit 0.5 %
Current input signal 0 mA ... 20 mA
4 mA ... 20 mA
-20 mA ... 20 mA
Basic error limit 0.5 %
Measured value representation 16 bits
Measured value resolution 12 bits
A/D conversion time 4.5 ms (per module)
Back to top

General

Weight 260 g
Back to top

Environmental Product Compliance

China RoHS Environmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values
Back to top

Classifications

eCl@ss

eCl@ss 4.0 27250303
eCl@ss 4.1 27250303
eCl@ss 5.0 27250303
eCl@ss 5.1 27242601
eCl@ss 6.0 27242601
eCl@ss 7.0 27242601
Back to top

ETIM

ETIM 2.0 EC001431
ETIM 3.0 EC001596
ETIM 4.0 EC001596
ETIM 5.0 EC001596
ETIM 6.0 EC001596
Back to top

UNSPSC

UNSPSC 6.01 43172015
UNSPSC 7.0901 43201404
UNSPSC 11 43172015
UNSPSC 12.01 43201404
UNSPSC 13.2 43201404
Back to top

PHOENIX CONTACT (Ireland) Ltd

C6 The Exchange
Calmount Park
Ballymount
Dublin 12
D12 XE18
Ireland
(01)2051-300
  • Create PDF
  • Recommend
  • Feedback

This website uses cookies, by continuing to browse, you agree to our cookie policy. Read our privacy policy for more information.