I/O module - AXL F DOR4/2 AC/220DC 1F - 2700608

Axioline F, Relay module, Relay outputs: 4 (floating), N/O contact, 220 V DC, 230 V AC, transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connectors

Price:

Overview

Technical data

Accessories

Approvals

Downloads

Drawings



Connection diagram  

Connection diagram
Connection of actuators

Block diagram  

Block diagram
Internal wiring of the terminal points



Diagram  

Diagram
DC load limit curve for REL-MLR-1X1/G 5 (1 - ohmic load, 2 - inductive load L/R = 50 ms)

Dimensional drawing  

Dimensional drawing
Dimensions



Back to top

Dimensions

Dimensional drawing
Caption Dimensions
Width 53.6 mm
Height 126.1 mm
Depth 54 mm
Note on dimensions The depth is valid when a TH 35-7,5 DIN rail is used (according to EN 60715).
Back to top

Ambient conditions

Ambient temperature (operation) -25 °C ... 60 °C (max. 6 A/channel for wall mounting on horizontal DIN rail; max. 4 A/channel for any mounting position)
-25 °C ... 50 °C (max. 8 A/channel for wall mounting on horizontal DIN rail; max. 6 A/channel for any mounting position)
-25 °C ... 40 °C (max. 8 A/channel for any mounting position)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Permissible humidity (operation) 5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport) 5 % ... 95 % (non-condensing)
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection IP20
Back to top

Connection data

Designation Axioline F connector
Connection method Push-in connection
Note on the connection method Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.
When selecting the cables, please note that in the case of a small conductor cross section and high current, the terminal point temperature may be up to 30 K above the ambient temperature.
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 1.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 1.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 16
Stripping length 8 mm
Back to top

General

Mounting type DIN rail
Color traffic grey A RAL 7042
Net weight 222 g
Note on weight specifications with connectors and bus base module
Degree of pollution 2
Mounting position any (observe temperature and current derating)
Back to top

Interfaces

Designation Axioline F local bus
Number 2
Connection method Bus base module
Transmission speed 100 Mbps
Back to top

Axioline potentials

Designation Axioline F local bus supply (UBus)
Supply voltage 5 V DC (via bus base module)
Current consumption max. 280 mA (all relays pick up)
Power consumption max. 1.4 W (all relays pick up)
Back to top

Relay outputs

Output name Relay outputs
Number of outputs 4 (floating)
Connection method Push-in connection
Connection technology 2-conductor
Switching current max. 8 A AC (cos phi = 1)
For DC see load limit curve, e.g., the following values:
max. 8 A DC (≤ 30 V, ohmic load)
max. 500 mA DC (110 V, ohmic load)
max. 250 mA DC (220 V DC, ohmic load)
max. 220 mA DC (125 V DC, L/R ≤ 50 ms, applications with UL approval)
max. 110 mA DC (250 V DC, L/R ≤ 50 ms, applications with UL approval)
Switching capacity max. 2000 VA
For DC see load limit curve, e.g., the following values:
max. 240 W (30 V DC)
max. 55 W (≥ 60 V DC)
max. 25 W (125 V DC, 250 V DC, applications with UL approval)
Contact type N/O contact
Output current max. 8 A (per channel, provide an external fuse)
max. 32 A (per module)
Nominal output voltage 220 V DC
230 V AC
Output voltage range 24 V DC ... 220 V DC -20 % / +15 %
24 V AC ... 230 V AC -20 % / +15 % (50/60 Hz)
Switching current max. 8 A AC (cos phi = 1)
For DC see load limit curve, e.g., the following values:
max. 8 A DC (≤ 30 V, ohmic load)
max. 500 mA DC (110 V, ohmic load)
max. 250 mA DC (220 V DC, ohmic load)
max. 220 mA DC (125 V DC, L/R ≤ 50 ms, applications with UL approval)
max. 110 mA DC (250 V DC, L/R ≤ 50 ms, applications with UL approval)
Switching capacity max. 2000 VA
Switching frequency max. 6 (per minute)
Mechanical service life 10x 106 cycles
Back to top

Electrical isolation

Test section Relay contact / logic 4 kV Rated surge voltage (safe isolation according to EN 61010-2-201/IEC 61010-2-201)
Relay contact / logic 5 kV Pulse test voltage according to EN 61850/IEC 61850
Contact/functional ground 4 kV Rated surge voltage (safe isolation according to EN 61010-2-201/IEC 61010-2-201)
Contact/functional ground 5 kV Pulse test voltage according to EN 61850/IEC 61850
Contact / contact (open contact) 1 kV 50 Hz 1 min.
Contact / contact (adjacent connectors 2.5 kV Pulse test voltage according to EN 61850/IEC 61850
Back to top

Standards and Regulations

Immunity to ESD Noise immunity test in accordance with EN 61000-6-2 Electrostatic discharge (ESD) EN 61000-4-2/IEC 61000-4-2 Criterion A, 6 kV contact discharge, 8 kV air discharge
Immunity to EF Noise immunity test in accordance with EN 61000-6-2 Electromagnetic fields EN 61000-4-3/IEC 61000-4-3 Criterion A, 20 V/m up to 1 GHz, 10 V/m up to 3 GHz
Immunity to burst Noise immunity test in accordance with EN 61000-6-2 Fast transients (burst) EN 61000-4-4/IEC 61000-4-4 Criterion A, 4 kV
Immunity to surge Noise immunity test in accordance with EN 61000-6-2 Transient overvoltage (surge) EN 61000-4-5/IEC 61000-4-5 Criterion A, ±4 kV (asymmetrical)
Immunity to conducted interference Noise immunity test in accordance with EN 61000-6-2 Conducted interference EN 61000-4-6/IEC 61000-4-6 Criterion A, Test voltage 10 V
Interference emission Noise emission test according to EN 61000-6-3 Class B
Mechanical tests Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g
Shock in acc. with EN 60068-2-27/IEC 60068-2-27 20g (contact interruption) / 5g (contact closure)
Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g
Developed according to standard IEC 61850-3 Electrostatic discharge (ESD) EN 61000-4-2/IEC 61000-4-2 Criterion A, 6 kV contact discharge, 8 kV air discharge
IEC 61850-3 Electromagnetic fields EN 61000-4-3/IEC 61000-4-3 Criterion A, 20 V/m up to 1 GHz, 10 V/m up to 3 GHz
IEC 61850-3 Fast transients (burst) EN 61000-4-4/IEC 61000-4-4 Criterion A, 4 kV
IEC 61850-3 Transient overvoltage (surge) EN 61000-4-5/IEC 61000-4-5 Criterion A, ±4 kV (asymmetrical)
IEC 61850-3 Conducted interference EN 61000-4-6/IEC 61000-4-6 Criterion A, Test voltage 10 V
IEC 61850-3 Immunity to magnetic fields, EN 61000-4-8/IEC 61000-4-8 300 A/m continuous, 1000 A/m for 1 s
IEC 61850-3 Immunity to attenuated oscillating magnetic fields, EN 61000-4-10/IEC 61000-4-10 100 A/m
IEC 61850-3 Immunity to conducted common-mode interference, EN 61000-4-16/IEC 61000-4-16 30 V continuous, 300 V for 1 s
IEC 61850-3 Attenuated oscillating waves, EN 61000-4-18/IEC 61000-4-18 2.5 kV asymmetrical
IEC 61850-3 Radio interference properties EN 55022 Class B
Overvoltage category III (EN 61010-2-201/UL 61010-2-201), up to 2000 m above sea level
II (EN 61010-2-201/UL 61010-2-201), up to 3000 m above sea level
Back to top

Classifications

eCl@ss

eCl@ss 10.0.1 27242604
eCl@ss 11.0 27242604
eCl@ss 5.1 27242600
eCl@ss 6.0 27242600
eCl@ss 7.0 27242604
eCl@ss 8.0 27242604
eCl@ss 9.0 27242604
Back to top

ETIM

ETIM 5.0 EC001599
ETIM 6.0 EC001599
ETIM 7.0 EC001599
Back to top

UNSPSC

UNSPSC 13.2 32151602
UNSPSC 18.0 32151602
UNSPSC 19.0 32151602
UNSPSC 20.0 32151602
UNSPSC 21.0 32151602