Brief article description | Panel feed-through terminal block |
---|---|
Range of articles | HDFK 25 |
Pitch | 15.1 mm |
Number of positions | 1 |
Nominal current | 101 A |
---|---|
Nom. voltage | 500 V |
Maximum load current | 125 A (with 35 mm² conductor cross section) |
Rated voltage (III/3) | 500 V |
Rated surge voltage (III/3) | 6 kV |
Connection method | Screw connection with tension sleeve |
---|---|
Connection direction of the conductor to plug-in direction | 0 ° |
Conductor cross section solid | 6 mm² ... 35 mm² |
Conductor cross section flexible | 10 mm² ... 25 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve | 4 mm² ... 25 mm² |
Conductor cross section, flexible, with ferrule, with plastic sleeve | 4 mm² ... 25 mm² |
2 conductors with same cross section, solid | 2.5 mm² ... 10 mm² |
2 conductors with same cross section, flexible | 4 mm² ... 10 mm² |
2 conductors with same cross section, flexible, with ferrule without plastic sleeve | 2.5 mm² ... 10 mm² |
2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve | 2.5 mm² ... 10 mm² |
Internal cylindrical gage | B8 |
Stripping length | 19 mm |
Torque | 4 Nm ... 4.5 Nm |
Connection method | Screw connection with tension sleeve |
---|---|
Connection direction of the conductor to plug-in direction | 0 ° |
Conductor cross section solid | 6 mm² ... 35 mm² |
Conductor cross section flexible | 10 mm² ... 25 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve | 4 mm² ... 25 mm² |
Conductor cross section, flexible, with ferrule, with plastic sleeve | 4 mm² ... 25 mm² |
2 conductors with same cross section, solid | 2.5 mm² ... 10 mm² |
2 conductors with same cross section, flexible | 4 mm² ... 10 mm² |
2 conductors with same cross section, flexible, with ferrule without plastic sleeve | 2.5 mm² ... 10 mm² |
2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve | 2.5 mm² ... 10 mm² |
Internal cylindrical gage | B8 |
Stripping length | 19 mm |
Torque | 4 Nm ... 4.5 Nm |
Note | WEEE/RoHS-compliant, free of whiskers according to IEC 60068-2-82/JEDEC JESD 201 |
---|---|
Contact material | Cu alloy |
Surface characteristics | tin-plated |
Housing color | gray (7042) |
---|---|
Insulating material | PA |
Insulating material group | I |
CTI according to IEC 60112 | 600 |
Flammability rating according to UL 94 | V0 |
Glow wire flammability index GWFI according to EN 60695-2-12 | 850 |
Glow wire ignition temperature GWIT according to EN 60695-2-13 | 775 |
Temperature for the ball pressure test according to EN 60695-10-2 | 125 °C |
Dimensional drawing |
![]() |
---|---|
Caption | Schematische Abbildung - weitere Details siehe Produktfamilienzeichnung im Download Center |
Pitch | 15.1 mm |
Type of packaging | packed in cardboard |
---|---|
Pieces per package | 50 |
Denomination packing units | Pcs. |
Test for conductor damage and slackening | IEC 60947-7-1:2002-07 |
---|---|
Test passed |
Pull-out test | IEC 60947-7-1:2002-07 |
---|---|
Conductor cross section / conductor type / tensile force | 6 mm² / solid / > 80 N |
10 mm² / flexible / > 90 N | |
35 mm² / stranded / > 190 N | |
25 mm² / flexible / > 135 N |
Clearances and creepage distances | Metal wall 1.0 mm ... 6.0 mm IEC 60947-7-1:2002-07 |
---|---|
Application | Metal wall 1.0 mm ... 6.0 mm |
Specification | IEC 60947-7-1:2002-07 |
Minimum clearance - inhomogeneous field (III/3) | 5.5 mm |
Minimum creepage distance value (III/3) | 6.3 mm |
Specification | IEC 60947-7-1:2002-07 |
---|---|
Requirement temperature-rise test | Increase in temperature ≤ 45 K |
Connection in acc. with standard | CSA |
---|---|
Safety note |
• Only electrically qualified personnel may install and operate the product. To recognize and prevent danger, the qualified personnel must be familiar with the basics of electrical engineering. |
• Observe the technical data provided here and refer to the documents listed under “Downloads”. The download area contains important information, such as installation notes, technical drawings, and 3D data. | |
• The cable entry funnel is not safe to touch. Never connect or disconnect the terminal when it is energized. Take appropriate steps to ensure touch protection. | |
There is no electrical contact to the housing. Ensure protective grounding is established for green-yellow color versions. |
Specification | IEC 60695-2-11:2000-10 |
---|---|
Temperature | 960 °C |
Time of exposure | 30 s |
China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
---|---|
No hazardous substances above threshold values |
eCl@ss 10.0.1 | 27141134 |
---|---|
eCl@ss 11.0 | 27141134 |
eCl@ss 4.0 | 27141100 |
eCl@ss 4.1 | 27141100 |
eCl@ss 5.0 | 27141100 |
eCl@ss 5.1 | 27141100 |
eCl@ss 6.0 | 27141100 |
eCl@ss 7.0 | 27141134 |
eCl@ss 8.0 | 27141134 |
eCl@ss 9.0 | 27141134 |
ETIM 2.0 | EC001283 |
---|---|
ETIM 3.0 | EC001283 |
ETIM 4.0 | EC001283 |
ETIM 5.0 | EC001283 |
ETIM 6.0 | EC001283 |
ETIM 7.0 | EC001283 |
UNSPSC 6.01 | 30211811 |
---|---|
UNSPSC 7.0901 | 39121410 |
UNSPSC 11 | 39121410 |
UNSPSC 12.01 | 39121410 |
UNSPSC 13.2 | 39121410 |
UNSPSC 18.0 | 39121410 |
UNSPSC 19.0 | 39121410 |
UNSPSC 20.0 | 39121410 |
UNSPSC 21.0 | 39121410 |
"$pageName" on