Installation instructions | When mounted in rows, the nominal device current can be limited to just 80% or must be overdimensioned accordingly. |
---|---|
Mounting type | on base element |
Color | black |
Number of positions | 1 |
Overvoltage category | II |
Insulating material | PPS |
Flammability rating according to UL 94 | V0 |
Fuse | Slow-blow |
---|---|
Fuse type | Automatic device |
Rated surge voltage | 2.5 kV |
Rated voltage | 250 V AC |
65 V DC | |
250 V (AC according to UL 1077) | |
72 V (DC according to UL 1077) | |
Rated current IN | 4 A |
Insulation resistance Riso | > 100 MΩ (500 V DC) |
Rated short-circuit switching capacity Icn | 24 A (250 V AC / 65 V DC) |
40 A (30 V DC) | |
Short-circuit switching capacity | 2000 A (250 V AC / UL 1077) |
2000 A (72 V DC / UL 1077) | |
Dielectric strength | 3000 V AC (Actuation area) |
1500 V AC (Installation area) | |
Switching cycles, max. | 6000 (At 1 x In, low-induction) |
3000 (At 1 x In, inductive) | |
500 (At 2 x In, inductive) | |
Degree of pollution | 2 |
Overvoltage category | II |
Insulating material group | IIIb |
Degree of protection | IP40 (Actuation area) |
---|---|
Ambient temperature (operation) | -20 °C ... 60 °C |
China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
---|---|
No hazardous substances above threshold values |
eCl@ss 10.0.1 | 27141116 |
---|---|
eCl@ss 11.0 | 27141116 |
eCl@ss 4.0 | 27141100 |
eCl@ss 4.1 | 27141100 |
eCl@ss 5.0 | 27141100 |
eCl@ss 5.1 | 27141100 |
eCl@ss 6.0 | 27141100 |
eCl@ss 7.0 | 27141116 |
eCl@ss 9.0 | 27141116 |
ETIM 2.0 | EC000899 |
---|---|
ETIM 3.0 | EC000899 |
ETIM 4.0 | EC000899 |
ETIM 5.0 | EC000899 |
ETIM 6.0 | EC000899 |
ETIM 7.0 | EC000899 |
UNSPSC 6.01 | 30211812 |
---|---|
UNSPSC 7.0901 | 39121411 |
UNSPSC 11 | 39121411 |
UNSPSC 12.01 | 39121411 |
UNSPSC 13.2 | 39121410 |
UNSPSC 18.0 | 39121410 |
UNSPSC 19.0 | 39121410 |
UNSPSC 20.0 | 39121410 |
UNSPSC 21.0 | 39121410 |
"$pageName" on