Number of levels | 1 |
---|---|
Number of connections | 2 |
Nominal cross section | 25 mm² |
Color | silver |
Insulating material | PA |
Flammability rating according to UL 94 | V0 |
Rated surge voltage | 8 kV |
Degree of pollution | 3 |
Overvoltage category | III |
Insulating material group | I |
Maximum power dissipation for nominal condition | 3.26 W |
Maximum load current | 125 A (for 35 mm² conductor cross section) |
Open side panel | No |
Shock protection test specification | DIN EN 50274 (VDE 0660-514):2002-11 |
Back of the hand protection | guaranteed |
Finger protection | guaranteed |
Test specification, oscillation, broadband noise | DIN EN 50155 (VDE 0115-200):2018-05 |
Test spectrum | Service life test category 2, bogie-mounted |
Test frequency | f1 = 5 Hz to f2 = 250 Hz |
ASD level | 6.12 (m/s2)2/Hz |
Acceleration | 3.12 g |
Test duration per axis | 5 h |
Test directions | X-, Y- and Z-axis |
Shock form | Semi-sinusoidal |
Acceleration | 30g |
Shock duration | 18 ms |
Number of shocks per direction | 3 |
Test directions | X-, Y- and Z-axis (pos. and neg.) |
Note | Please observe the current carrying capacity of the DIN rails. |
---|---|
Connection method | Screw connection |
Screw thread | M6 |
Stripping length | 14 mm |
Tightening torque, min | 3.2 Nm |
Tightening torque max | 3.7 Nm |
Conductor cross section solid min. | 0.75 mm² |
Conductor cross section solid max. | 35 mm² |
Conductor cross section AWG min. | 18 |
Conductor cross section AWG max. | 2 |
Conductor cross section flexible min. | 0.75 mm² |
Conductor cross section flexible max. | 25 mm² |
Min. AWG conductor cross section, flexible | 18 |
Max. AWG conductor cross section, flexible | 3 |
Conductor cross section flexible, with ferrule without plastic sleeve min. | 0.75 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve max. | 25 mm² |
Conductor cross section flexible, with ferrule with plastic sleeve min. | 0.75 mm² |
Conductor cross section flexible, with ferrule with plastic sleeve max. | 16 mm² |
2 conductors with same cross section, solid min. | 0.75 mm² |
2 conductors with same cross section, solid max. | 10 mm² |
2 conductors with same cross section, stranded min. | 0.75 mm² |
2 conductors with same cross section, stranded max. | 10 mm² |
Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, minimum | 0.75 mm² |
Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, maximum | 10 mm² |
Internal cylindrical gage | B8 |
China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
---|---|
No hazardous substances above threshold values |
eCl@ss 10.0.1 | 27141141 |
---|---|
eCl@ss 11.0 | 27141141 |
eCl@ss 4.0 | 27141100 |
eCl@ss 4.1 | 27141100 |
eCl@ss 5.0 | 27141100 |
eCl@ss 5.1 | 27141100 |
eCl@ss 6.0 | 27141100 |
eCl@ss 7.0 | 27141141 |
eCl@ss 8.0 | 27141141 |
eCl@ss 9.0 | 27141141 |
ETIM 2.0 | EC000901 |
---|---|
ETIM 3.0 | EC000901 |
ETIM 4.0 | EC000901 |
ETIM 5.0 | EC000901 |
ETIM 6.0 | EC000901 |
ETIM 7.0 | EC000901 |
UNSPSC 6.01 | 30211811 |
---|---|
UNSPSC 7.0901 | 39121410 |
UNSPSC 11 | 39121410 |
UNSPSC 12.01 | 39121410 |
UNSPSC 13.2 | 39121410 |
UNSPSC 18.0 | 39121410 |
UNSPSC 19.0 | 39121410 |
UNSPSC 20.0 | 39121410 |
UNSPSC 21.0 | 39121410 |