The illustration shows the versions with screw connection

Ex i repeater power supply and input signal conditioner, HART. Transmits supplied or active 0/4 - 20 mA signals from the hazardous area to a load (active or passive) in the safe area. 3-way electrical isolation; SIL 2 according to IEC 61508, with push-in connection

Price:

Overview

Technical data

Accessories

Approvals

Downloads

Your advantages

  • 0/4 mA ... 20 mA input, intrinsically safe, [Ex ia], powered and not powered
  • Measuring transducer supply voltage > 16 V
  • 0/4 mA ... 20 mA output, active up to 1000  load or passive
  • Bidirectional HART signal transmission
  • Error indication according to NAMUR NE 43
  • SIL 2 according to IEC 61508/EN 61508
  • Installation in Ex zone 2 permitted
  • 3-way electrical isolation
  • Power supply possible via DIN rail connector
  • Plug-in connection terminals, push-in connection technology
  • Housing width: 12.5 mm
  • Minimal power dissipation
  • High transmission accuracy