The intelligent QUINT UPS for integration into established industrial networks: your systems continue to be supplied with uninterrupted power, even in the event of a mains failure. The battery management system with IQ Technology and a powerful battery charger ensures superior system availability.
QUINT4-UPS/24DC/24DC/40
-
Uninterruptible power supply
2907077
QUINT UPS, IQ Technology, DIN rail mounting, Screw connection, input: 24 V DC, output: 24 V DC / 40 A, charging current: 5 A
Tämä tuote edellyttää muita tuotteita, jotta sitä voidaan käyttää.
Pakolliset lisätarvikkeet
Tuotetiedot
Input voltage | 24 V DC |
Input voltage range | 18 V DC ... 30 V DC |
Electric strength, max. | 35 V DC (Protected against polarity reversal) |
Internal input fuse | no |
Typical national grid voltage | 24 V DC |
Voltage type of supply voltage | DC |
Inrush current | ≤ 9 A (≤ 4 ms) |
Reverse polarity protection | yes |
Fixed backup threshold | 22 V DC |
30 V DC | |
Dynamic activation threshold | > 1 V / 100 ms |
Switch-on time | max. 3 s |
Switch-on time during battery operation (Bat.-Start) | 8 s |
Voltage drop, input/output | 0.5 V DC |
Current consumption IN (UN, IOUT = IN, Icharge = 0) | 40.1 A |
Current consumption Imax (UN, IOUT = IStat.Boost, ICharge = max) | 51.2 A |
Current consumption INo-Load(UN, IOUT = 0, Icharge = 0) | 50 mA |
Current consumption Icharge (UN, IOUT = 0, Icharge = max) | 6.1 A |
Power consumption PN (UN, IOUT = IN, Icharge = 0) | 965 W |
Power consumption Pmax (UN, IOUT = IStat.Boost, Icharge = max) | 1120 W |
Power consumption PNo-Load (UN, IOUT = 0, Icharge = 0) | 1.3 W |
Power consumption Pcharge (UN, IOUT = 0, Icharge = max) | 147 W |
Signal state Bat.-Start | |
Connection labeling | 3.8 (+) |
Channel | DI (digital input) |
State | Bat.-Mode |
State condition | Low level (30 ms) |
Signal - state assignment | low - active |
Reference potential | 3.9 (SGnd, identical to 1.2, 2.2, 4.2) |
LED status indicator | Yellow (Bat.-Mode) |
Signal state PS Boost | |
Connection labeling | 3.7 (+) |
Channel (configurable) | DI (digital input) default, AI (analog input) |
State (configurable) | Charging current reduced |
State condition | Low level |
Signal - state assignment | low - active |
Unit signal | I (mA) |
Reference potential | 3.9 (SGnd, identical to 1.2, 2.2, 4.2) |
Signal state Remote | |
Connection labeling | 3.6 (+) |
Channel | DI (digital input) |
State (configurable) | Disconnection |
State condition | Low level |
Signal - state assignment | low - active |
Reference potential | 3.9 (SGnd, identical to 1.2, 2.2, 4.2) |
LED status indicator | Green, flashing (DC OK) |
Efficiency | typ. 98 % |
Number of outputs | 1 |
Short-circuit-proof | yes |
No-load proof | yes |
Switch-over time | 0 ms |
Output current limit | In mains mode according to connected upstream current limiting device |
> 45 A (Battery operation) | |
Power dissipation | 2.8 W (Mains operation) |
13 W (Mains operation) | |
3.51 W (Battery operation) | |
16.4 W (Battery operation) | |
UPS connection in parallel | no |
UPS connection in series | no |
Energy storage device connection in parallel | Yes, 5 (observe line protection) |
Energy storage device connection in series | no |
Mains operation | |
Output voltage | 24 V DC (UOUT = UIN - 0.5 V DC) |
Output voltage range | 18 V DC ... 30 V DC |
18 V DC ... 32 V DC | |
Output current IN | 40 A |
Static Boost (IStat.Boost) | 45 A |
Dynamic Boost (IDyn.Boost) | 60 A (5 s) |
Selective Fuse Breaking (ISFB) | 215 A (15 ms) |
Output power POUT (UN, IOUT = IN) | 960 W |
Output power POUT (UN, IOUT = Istat.Boost) | 1080 W |
Battery operation | |
Output voltage | 24 V DC (UOUT = UBAT - 0.5 V DC) |
Output voltage range | 19 V DC ... 32 V DC |
Output current IN | 40 A |
Static Boost (IStat.Boost) | 45 A |
Selective Fuse Breaking (ISFB) | 215 A (15 ms) |
Output power POUT (UN, IOUT = IN) | 960 W |
Output power POUT (UN, IOUT = Istat.Boost) | 1080 W |
Signal supply 24 V DC, 20 mA, SGnd | |
Connection labeling | 3.1 (+), 3.9 (SGnd) |
Reference potential | 3.9 (SGnd, identical to 1.2, 2.2, 4.2) |
Signal state Alarm | |
Connection labeling | 3.2, 3.3 |
Channel | DO (digital output) |
Switching voltage | max. 30 V AC/DC |
Switch contact (floating) | OptoMOS |
State (configurable) | Group alarm |
State condition (configurable) | Alarm threshold |
Current carrying capacity | max. 100 mA |
State - signal assignment | NC (Normally Closed) |
LED status indicator | red (Alarm) |
Signal state Bat. mode | |
Connection labeling | 3.4 (+) |
Channel | DO (digital output) |
Semiconductor output | MOSFET |
State (configurable) | Bat.-Mode |
State condition (configurable) | UIN < 18 V DC, UIN > 30 V DC, Bat.-Start |
State - signal assignment | active - high |
Reference potential | 3.9 (SGnd, identical to 1.2, 2.2, 4.2) |
LED status indicator | Yellow (Bat.-Mode) |
Signal state Ready | |
Connection labeling | 3.5 (+) |
Channel | DO (digital output) |
Semiconductor output | MOSFET |
State (configurable) | Ready |
State condition (configurable) | SOC = 100 % |
State - signal assignment | active - high |
Reference potential | 3.9 (SGnd, identical to 1.2, 2.2, 4.2) |
LED status indicator | Green (state of charge - SOC) |
Nominal voltage UN | 24 V DC |
End-of-charge voltage (temperature-compensated) | 25 V DC ... 32 V DC |
End-of-charge voltage (configurable) | 27.6 V DC |
Charging current (configurable) | max. 5 A |
Nominal capacity (without additional charger) | 7 Ah ... 135 Ah |
Max. capacity | 135 Ah |
Charging time | 500 min (38 Ah) |
Buffer time | 33 min (38 Ah) |
Deep discharge protection (configurable) | 19.2 V DC |
Battery technology | VRLA, VRLA-WTR, LI-ION |
Charge characteristic curve | IU0U |
IQ-Technology | yes |
Temperature sensor | yes |
Temperature compensation (configurable) | 42 mV/K |
Input | |
Position | 1.x |
Conductor connection | |
Connection method | Screw connection |
rigid | 0.5 mm² ... 16 mm² |
flexible | 0.5 mm² ... 16 mm² |
flexible with ferrule without plastic sleeve | 0.5 mm² ... 16 mm² |
flexible with ferrule with plastic sleeve | 0.5 mm² ... 16 mm² |
rigid (AWG) | 8 ... 6 (Cu) |
Stripping length | 10 mm (rigid/flexible) |
Tightening torque | 1.2 Nm ... 1.5 Nm |
Drive form screw head | Slotted L |
Output | |
Position | 2.x |
Conductor connection | |
Connection method | Screw connection |
rigid | 0.5 mm² ... 16 mm² |
flexible | 0.5 mm² ... 16 mm² |
flexible with ferrule without plastic sleeve | 0.5 mm² ... 16 mm² |
flexible with ferrule with plastic sleeve | 0.5 mm² ... 16 mm² |
rigid (AWG) | 8 ... 6 (Cu) |
Stripping length | 10 mm (rigid/flexible) |
8 mm (Ferrule) | |
Tightening torque | 1.2 Nm ... 1.5 Nm |
Drive form screw head | Slotted L |
Signal | |
Position | 3.x |
Conductor connection | |
Connection method | Push-in connection |
rigid | 0.2 mm² ... 1 mm² |
flexible | 0.2 mm² ... 1 mm² |
flexible with ferrule without plastic sleeve | 0.2 mm² ... 0.75 mm² |
0.5 mm² (recommended) | |
flexible with ferrule with plastic sleeve | 0.2 mm² ... 0.75 mm² |
rigid (AWG) | 24 ... 16 (Cu) |
Stripping length | 8 mm (rigid/flexible) |
Battery | |
Position | 4.x |
Connection technology | |
Position marking | 4.1 (+), 4.2 (-), 4.3 () |
Conductor connection | |
Connection method | Screw connection |
rigid | 0.5 mm² ... 16 mm² |
flexible | 0.5 mm² ... 16 mm² |
flexible with ferrule without plastic sleeve | 0.5 mm² ... 16 mm² |
flexible with ferrule with plastic sleeve | 0.5 mm² ... 16 mm² |
rigid (AWG) | 20 ... 6 (Cu) |
Stripping length | 10 mm (rigid/flexible) |
Tightening torque | 1.2 Nm ... 1.5 Nm |
Drive form screw head | Slotted L |
LED signaling | |
Types of signaling | DC OK (green) |
Alarm (red) | |
Bat.-Mode (yellow) | |
SOC (red, green) | |
Data (red, green) |
Product type | DC UPS |
Product family | QUINT UPS |
MTBF (IEC 61709, SN 29500) | > 1980000 h (25 °C) |
> 1205000 h (40 °C) | |
> 604200 h (60 °C) | |
Environmental protection directive | RoHS Directive 2011/65/EU |
WEEE | |
Reach | |
Insulation characteristics | |
Protection class | III (without PE) |
Degree of pollution | 2 |
Life expectancy (electrolytic capacitors) | |
Time | 126720 h |
Item dimensions | |
Width | 47 mm |
Height | 130 mm |
Depth | 125 mm |
125 mm (Device depth (DIN rail mounting)) | |
Item dimensions with alternative mounting | |
Width | 123 mm |
Height | 130 mm |
Depth | 49 mm |
Installation dimensions | |
Installation distance right/left (active) | 5 mm / 5 mm (POut ≥50% ) |
Installation distance right/left (passive) | 0 mm / 0 mm (POut ≥50% ) |
Installation distance right/left (active, passive) | 0 mm / 0 mm (POut ≤50 %) |
Installation distance top/bottom (active) | 50 mm / 50 mm (POut ≥50% ) |
Installation distance top/bottom (passive) | 40 mm / 20 mm (POut ≥50% ) |
Installation distance top/bottom (active, passive) | 40 mm / 20 mm (POut ≤50 %) |
Mounting type | DIN rail mounting |
Mounting position | On horizontal DIN rail NS 35/7.5 and NS 35/15 acc. to EN 60715 |
Flammability rating according to UL 94 (housing / terminal blocks) | V0 |
Housing material | Metal |
Hood version | Stainless steel X6Cr17 |
Side element version | Aluminum AlMg3 |
Ambient conditions | |
Degree of protection | IP20 |
Ambient temperature (operation) | -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Ambient temperature (start-up type tested) | -40 °C |
Maximum altitude | ≤ 4000 m |
Climatic class | 3K3 (EN 60721) |
Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
Vibration (operation) | 2.3g |
Overvoltage category | |
EN 61010-1 | II (≤ 4000 m) |
EN 61010-2-201 | II (≤ 4000 m) |
Protective extra-low voltage | |
Standard designation | Protective extra-low voltage |
Standards/specifications | IEC 61010-1 (SELV) |
IEC 61010-2-201 (PELV) |
UL approval | |
Identification | UL/C-UL Listed UL 61010-1 |
UL approval | |
Identification | UL/C-UL Listed UL 61010-2-201 |
UL approval | |
Identification | UL/C-UL Listed ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location) |
CSA | |
Identification | CAN/CSA-C22.2 No. 61010-1-12 |
CSA | |
Identification | CAN/CSA-IEC 61010-2-201 |
CSA | |
Identification | CAN/CSA-C22.2 No. 213 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location) |
CB scheme | |
Identification | IEC 61010-1 |
IEC 61010-2-201 | |
DNV | |
Identification | Class Guideline DNVGL-CG-0339 |
Note | Location classes: Temperature D (see Application/Limitation), Humidity B, Vibration A/C, EMC B |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
EMC requirements for noise emission | EN 61000-6-3 |
EN 61000-6-4 | |
EMC requirements for noise immunity | EN 61000-6-1 |
EN 61000-6-2 | |
Noise immunity | Immunity in accordance with EN 61000-6-1 (residential), EN 61000-6-2 (industrial), and EN 61000-6-5 (power station equipment zone), IEC/EN 61850-3 (power supply) |
Noise emission | |
Standards/regulations | Additional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply) |
Electrostatic discharge | |
Standards/regulations | EN 61000-4-2 |
Electrostatic discharge | |
Contact discharge | 8 kV (Test Level 4) |
Discharge in air | 15 kV (Test Level 4) |
Comments | Criterion B |
Electromagnetic HF field | |
Standards/regulations | EN 61000-4-3 |
Electromagnetic HF field | |
Frequency range | 80 MHz ... 1 GHz |
Test field strength | 20 V/m (Test Level 3) |
Frequency range | 1 GHz ... 6 GHz |
Test field strength | 10 V/m (Test Level 3) |
Frequency range | 1 GHz ... 6 GHz |
Test field strength | 10 V/m (Test Level 3) |
Comments | Criterion A |
Fast transients (burst) | |
Standards/regulations | EN 61000-4-4 |
Fast transients (burst) | |
Input | 4 kV (Test Level 4 - asymmetrical) |
Output | 4 kV (Test Level 4 - asymmetrical) |
Signal | 4 kV (Test Level 4 - asymmetrical) |
Comments | Criterion B |
Surge voltage load (surge) | |
Standards/regulations | EN 61000-4-5 |
Surge voltage load (surge) | |
Input | 1 kV (Test Level 3 - symmetrical) |
2 kV (Test Level 3 - asymmetrical) | |
Output | 1 kV (Test Level 3 - symmetrical) |
2 kV (Test Level 3 - asymmetrical) | |
Signal | 1 kV (Test Level 2 - asymmetrical) |
Comments | Criterion B |
Conducted interference | |
Standards/regulations | EN 61000-4-6 |
Conducted interference | |
Input/output/signal | asymmetrical |
Frequency range | 0.15 MHz ... 80 MHz |
Comments | Criterion A |
Voltage | 10 V (Test Level 3) |
Power frequency magnetic field | |
Standards/regulations | EN 61000-4-8 |
Frequency | 16.67 Hz |
50 Hz | |
60 Hz | |
Test field strength | 100 A/m |
Additional text | 60 s |
Comments | Criterion A |
Frequency | 50 Hz |
60 Hz | |
Frequency range | 50 Hz ... 60 Hz |
Test field strength | 1 kA/m |
Additional text | 3 s |
Frequency | 0 Hz |
Test field strength | 300 A/m |
Additional text | DC, 60 s |
Criteria | |
Criterion A | Normal operating behavior within the specified limits. |
Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
Tuotenumero | 2907077 |
Pakkausyksikkö | 1 Kappaletta |
Vähimmäistilausmäärä | 1 Kappaletta |
Tuoteavain | CMUI43 |
Tuotekoodi | CMUI43 |
Luettelosivu | Sivu 325 (C-4-2019) |
GTIN | 4055626170053 |
Paino kappaletta kohti (sis. pakkauksen) | 709 g |
Paino kappaletta kohti (ilman pakkausta) | 549 g |
Tullitariffinumero | 85371091 |
Alkuperämaa | CN |
ECLASS
ECLASS-11.0 | 27040705 |
ECLASS-12.0 | 27040705 |
ECLASS-13.0 | 27040705 |
ETIM
ETIM 9.0 | EC000382 |
UNSPSC
UNSPSC 21.0 | 39121000 |
UL Listed
Hyväksyntätunnus: E123528cUL Listed
Hyväksyntätunnus: E123528EAC
Hyväksyntätunnus: RU-DE.B.00184/20ABS
Hyväksyntätunnus: 23-2416092-PDADNV
Hyväksyntätunnus: TAA00002K4RINA
Hyväksyntätunnus: ELE382621XGLR
Hyväksyntätunnus: LR21417906TANK
Hyväksyntätunnus: TA22372MBV
Hyväksyntätunnus: 69394/A0 BVKC
Hyväksyntätunnus: R-R-PCK-2907077cUL Listed
Hyväksyntätunnus: E199827UL Listed
Hyväksyntätunnus: E199827cULus Listed
cULus Listed
EU RoHS | |
Täyttää RoHS-direktiivin vaatimukset | Kyllä |
poikkeussäännökset siltä osin kuin ne ovat tiedossa | 7(a), 7(c)-I |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-25
Löydät tuotekohtaisen Kiinan RoHS-ilmoitusluettelon kunkin tuotteen latausalueelta Valmistajan ilmoitus -kohdasta. EFUP-E-merkinnän sisältäville tuotteille ei tarvita Kiinan RoHS-ilmoitusluetteloa, eikä sitä tarvitse siksi laatia.
|
EU REACH SVHC | |
Huomautus REACH-kandidaattiaineesta (CAS-nro) | Lead (CAS-nro: 7439-92-1) |
SCIP | 839f657e-9ce2-4700-be6f-2da74178cb63 |
EF3.0 Ilmastonmuutos | |
CO2e kg | 19,91 kg CO2e |
Yhteensopivat tuotteet
-
UPS-BAT/PB/24DC/7AH - Battery module 1274118
-
UPS-BAT/PB/24DC/12AH - Battery module 1274119
-
UPS-BAT/PB/24DC/20AH - Battery module 1348516
-
UPS-BAT/PB/24DC/40AH - Battery module 1354641
-
UPS-BAT/LI/24DC/128WH - Battery module 1396415
-
UPS-BAT/VRLA-WTR/24DC/13AH - Battery module 2320416
-
UPS-BAT/VRLA-WTR/24DC/26AH - Battery module 2320429
Edut
Easy integration into networks using PROFINET, EtherNet/IP, EtherCAT® and USB interfaces
Evaluation of state of health (SOH) and state of charge (SOC), thanks to the intelligent battery management system (BMS)
Automatic recognition of the battery capacities and technologies (VRLA-WTR, LI-ION)
Monitoring of output current and voltage, as well as manual connection and disconnection of the system
SFB Technology selectively trips standard miniature circuit breakers. Loads connected in parallel continue working.
PHOENIX CONTACT OY
Niittytie 11, 01300 Vantaa