UPS modules with integrated energy storage are particularly space saving: UPS module and energy storage are combined in one housing. The TRIO AC-UPS ensures seamless transition to battery operation thanks to the pure sine curve. Connected industrial PCs can be shut down safely via the integrated USB interface.



AC operation
Input voltage 120 V AC
Input voltage range 96 V AC ... 138 V AC
Voltage type of supply voltage AC
Frequency range (fN) 45 Hz ... 55 Hz
55 Hz ... 65 Hz
Current consumption 6 A (max.)
Power factor (cos phi) 0.8
Input fuse 10 A 400 V gRL
Permissible backup fuse B10 B16 Listed breaker
Digital Control (configurable)
Designation Remote
Low signal Connection to SGnd with < 2.7 kΩ
High signal Open (> 35 kΩ between Remote and SGnd)
Digital Control Low-Active (configurable)
Battery-operated start 120 V AC low signal Connection to SGnd with < 2.7 kΩ
Battery-operated start 120 V AC high signal Open (> 200 kΩ between Bat.-Start and SGnd)

Classification according to IEC 62040-3 VFD-SS-311
Efficiency > 95 % (100 % load, with charged energy storage)
~ 81 % (100 % load )
Nominal output voltage 120 V AC
Form of output voltage Pure sine
Nominal output current (IN) 6 A
Bridging time 60 s
UPS connection in series no
Apparent power 750 VA
Nominal power 600 W (Real power)
Crest factor 2.8
Switch-over time < 10 ms
Connection in parallel no
Connection in series No
Mains operation
Nominal output voltage 120 V AC
Nominal output current (IN) 6 A (750 VA)
Battery operation
Nominal output voltage 120 V AC
Nominal output current (IN) 6 A (750 VA)
Frequency (after automatic detection in mains operation) 50 Hz
60 Hz
Signal: Alarm
Output voltage 24 V (SELV)
Continuous load current ≤ 20 mA
Signal: Battery mode
Output voltage 24 V (SELV)
Continuous load current ≤ 20 mA
Signal: Ready
Output voltage 24 V (SELV)
Continuous load current ≤ 20 mA
Signal:
Signal ground SGnd Reference potential for Bat.-Mode, Ready, Remote, and Bat.-Start
Signal: Alarm
Output voltage 24 V (SELV)
Continuous load current ≤ 20 mA
Signal: Battery mode
Output voltage 24 V (SELV)
Continuous load current ≤ 20 mA
Signal: Ready
Output voltage 24 V (SELV)
Continuous load current ≤ 20 mA
Signal:
Signal ground SGnd Reference potential for Bat.-Mode, Ready, Remote, and Bat.-Start
Signal: Alarm
Output voltage 24 V (SELV)
Continuous load current ≤ 20 mA
Signal: Battery mode
Output voltage 24 V (SELV)
Continuous load current ≤ 20 mA
Signal: Ready
Output voltage 24 V (SELV)
Continuous load current ≤ 20 mA
Signal:
Signal ground SGnd Reference potential for Bat.-Mode, Ready, Remote, and Bat.-Start
Signal: Alarm
Output voltage 24 V (SELV)
Continuous load current ≤ 20 mA
Signal: Battery mode
Output voltage 24 V (SELV)
Continuous load current ≤ 20 mA
Signal: Ready
Output voltage 24 V (SELV)
Continuous load current ≤ 20 mA
Signal:
Signal ground SGnd Reference potential for Bat.-Mode, Ready, Remote, and Bat.-Start
Signal: Alarm
Output voltage 24 V (SELV)
Continuous load current ≤ 20 mA
Signal: Battery mode
Output voltage 24 V (SELV)
Continuous load current ≤ 20 mA
Signal: Ready
Output voltage 24 V (SELV)
Continuous load current ≤ 20 mA
Signal:
Signal ground SGnd Reference potential for Bat.-Mode, Ready, Remote, and Bat.-Start
Signal: Alarm
Output voltage 24 V (SELV)
Continuous load current ≤ 20 mA
Signal: Battery mode
Output voltage 24 V (SELV)
Continuous load current ≤ 20 mA
Signal: Ready
Output voltage 24 V (SELV)
Continuous load current ≤ 20 mA
Signal:
Signal ground SGnd Reference potential for Bat.-Mode, Ready, Remote, and Bat.-Start

Nominal voltage UN 24 V DC
Charge current 0.7 A ... 1.1 A
Nominal capacity 4 Ah
Nominal capacity range 4 Ah
Charging time 7 h
Buffer period 20 min. (100 W)
4 min. (300 W)
1 min. (600 W)
Latest startup date (battery only) 6 Months (0 °C ... 20 °C)
Latest startup (battery only) - range 6 Months ... 3 Months (20 °C ... 30 °C)
3 Months ... 1 Months (30 °C ... 40 °C)
Battery technology Lead rechargeable battery module
Memory medium Lead rechargeable battery module
Accumulator type 2x Panasonic UP-VW1220P1 / BB Battery HR4.2-12FR
Can be extended with external battery 1x 24 V 4 Ah
Battery fuse 40 A, 32 V

Input
Connection method Push-in connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 4 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Stripping length 10 mm
Output
Connection method Push-in connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 4 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Stripping length 10 mm
Signal
Connection method Push-in connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 1.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 1.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 16
Stripping length 8 mm

Interface MINI-USB type B
Maximum cable length 3 m

Types of signaling LED
Signal output: Transistor output, active
Signalization designation Alarm
Status display LED
Color red
Signal output: Transistor output, active
Signalization designation Battery mode
Status display LED
Color yellow
Signal output: Transistor output, active
Signalization designation Ready
Signal output
Status display LED
Color green
Signal output
Signalization designation Battery charge
Status display LED
Color yellow
Signal output
Signalization designation Service
Status display LED
Color red

Number of phases 1.00

Product type Uninterruptible power supply, AC
MTBF (IEC 61709, SN 29500) > 206000 h (40 °C)
Insulation characteristics
Protection class I
Overvoltage category II
Degree of pollution 3
Life expectancy (electrolytic capacitors)
Time 32861 h

Width 210 mm
Height 170 mm
Depth 136 mm
Installation dimensions
Installation distance right/left 0 mm / 0 mm
Installation distance top/bottom 50 mm / 50 mm

Mounting type DIN rail mounting

Color gray
Type of housing DX51D+AZ (steel sheet / Galvalume)
Hood version PC + ABS

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) 0 °C ... 40 °C
Ambient temperature (storage/transport) -15 °C ... 40 °C (with charged energy storage device)
Maximum altitude ≤ 3000 m (> 2000 m, observe derating)
Climatic class 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation) ≤ 95 % (25 °C, non-condensing)
Shock 20g in all directions (EN 60068-2-27)
30g in each space direction with UWA 130
Vibration (operation) 5 Hz ... 100 Hz, 0.7g (EN 60068-2-6)

Standards
Standard uninterruptible power supply systems EN 62040-1

UL approvals UL/C-UL Recognized UL 1778

Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Conducted noise emission EN 62040-02 (Class C2)
Interference emission Noise emission in accordance with EN 62040-2
Noise immunity Immunity according to EN 61000-6-1 (residential), EN 61000-6-2 (industrial), and EN 61000-6-5 (power station equipment zone), IEC/EN 61850-3 (energy supply)
Immunity in accordance with EN 62040-2
Electrostatic discharge
Standards/regulations EN 61000-4-2
Electrostatic discharge
Contact discharge 6 kV (Test Level 3)
Discharge in air 8 kV (Test Level 3)
Comments Criterion A
Electromagnetic HF field
Standards/regulations EN 61000-4-3
Electromagnetic HF field
Frequency range 80 MHz ... 3 GHz
Test field strength 10 V/m
Comments Criterion A
Fast transients (burst)
Standards/regulations EN 61000-4-4
Fast transients (burst)
Input 2 kV (Test Level 3 - asymmetrical)
2 kV (Test Level 3 - asymmetrical)
Output 2 kV (Test Level 3 - asymmetrical)
Signal 2 kV (Test Level 3 - asymmetrical)
2 kV (Test Level 3 - asymmetrical)
Comments Criterion A (B for USB)
Surge voltage load (surge)
Standards/regulations EN 61000-4-5
Input 1 kV (Test Level 2 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Output 1 kV (Test Level 2 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Signal 1 kV (Test Level 2 - asymmetrical)
Comments Criterion A
Conducted interference
Standards/regulations EN 61000-4-6
Conducted interference
Frequency range 0.15 MHz ... 80 MHz
Comments Criterion A
Voltage 10 V
Power frequency magnetic field
Standards/regulations EN 61000-4-8
Frequency 60 Hz
Test field strength 100 A/m
Comments Criterion A
Emitted interference
Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Criterion A Normal operating behavior within the specified limits.
Criterion B Temporary impairment to operational behavior that is corrected by the device itself.

Tuotenumero 2905908
Pakkausyksikkö 1 Kappaletta
Vähimmäistilausmäärä 1 Kappaletta
Tuoteavain CMUO15
Tuotekoodi CMUO15
Luettelosivu Sivu 332 (C-4-2019)
GTIN 4055626007397
Paino kappaletta kohti (sis. pakkauksen) 6 359 g
Paino kappaletta kohti (ilman pakkausta) 6 098 g
Tullitariffinumero 85044030
Alkuperämaa DE


ECLASS

ECLASS-9.0 27040705
ECLASS-10.0.1 27040705
ECLASS-11.0 27040705

ETIM

ETIM 8.0 EC000382

UNSPSC

UNSPSC 21.0 39121000

cUL Recognized

Approval ID: FILE E 342453

UL Recognized

Approval ID: FILE E 342453

EAC

Approval ID: RU S-DE.BL08.W.00764

DNV GL

Approval ID: TAA00002JM

UL Recognized

Approval ID: FILE E 342453

EAC

Approval ID: RU S-DE.BL08.W.00764

cUL Recognized

Approval ID: FILE E 342453

DNV GL

Approval ID: TAA00002JM

EAC

Approval ID: RU-DE.B.00184/20

EAC

Approval ID: RU-DE.B.00184/20

cUL Recognized

Approval ID: FILE E 359066

UL Recognized

Approval ID: FILE E 359066

cUL Recognized

Approval ID: FILE E 359066

UL Recognized

Approval ID: FILE E 359066

REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 3
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”

Edut

Smooth transition, thanks to the pure sine curve: the sine generated in battery operation is synchronous with the mains previously used for supply
Space saving: UPS module and energy storage combined in one housing
Long buffer times with integrated VRLA energy storage, can be extended with additional energy storage
USB interface for connection to higher-level controllers such as industrial PCs
Startup from energy storage possible, even without mains input