TRIO-PM/1AC/24DC/2500W
-
Power supply unit
1635194
Primary-switched power supply unit, TRIO POWER, Screw connection, Panel mounting, input: 1-phase, output: 24 V DC / 104 A, adjustable from 24 V DC ... 28 V DC
Tuotetiedot
AC operation | |
Nominal input voltage range | 100 V AC ... 240 V AC |
Input voltage range | 100 V AC ... 240 V AC -15 % ... +10 % |
Derating | 90 V AC ... 180 V AC (≤ 1500 W) |
85 V AC ... 90 V AC (≤1350 W) | |
3.33%/K, >55℃ | |
Typical national grid voltage | 120 V AC |
230 V AC | |
Inrush current | < 30 A (25 °C) |
Inrush current integral (I2t) | < 4.121 A2s |
Frequency range (fN) | 50 Hz ... 60 Hz ±5 % |
Mains buffering time | typ. 16 ms (120 V AC) |
typ. 16 ms (230 V AC@80% load) | |
Buffer period | typ. 10 ms (120 V AC) |
typ. 10 ms (230 V AC) | |
Current consumption | 16.7 A (100 V AC) |
11.7 A (230 V AC) | |
20 A (85 V AC) | |
15 A (180 V AC) | |
Protective circuit | Transient protection |
Power factor (cos phi) | 0.97 (230 V AC) |
Device mains fuse | 25 A internal (device protection) |
Discharge current to PE | < 2 mA |
DC operation | |
Input voltage range | 140 V DC ... 340 V DC -15 %; +10 % |
100 V DC ... 240 V DC -15 %; +10 % (UL) | |
Derating | 127 V DC ... 254 V DC () |
Current consumption | 13.8 A (100 V DC) |
12.3 A (240 V DC) |
Efficiency | typ. 91.49 % (120 V AC) |
typ. 93.42 % (230 V AC) | |
Nominal output voltage | 24 V DC |
Setting range of the output voltage (USet) | 24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted) |
Nominal output current (IN) | 104 A |
Static Boost (IStat.Boost) | 125 A |
Dynamic Boost (IDyn.Boost) | max. 145.83 A (5 s) |
Derating | 55 °C ... 70 °C |
Output current limit | 145.8 A |
Output power (PN) | 2500 W |
Output power (PStat. Boost) | 3000 W |
Output power (PDyn. Boost) | max. 3500 W (5 s) |
Connection in parallel | max. 4 |
Connection in series | max. 2 |
Residual ripple | typ. 240 mVPP (maximum) |
Control deviation | < 2 % (change in load, static 10 % ... 90 %) |
< 0.2 % (change in input voltage ±10 %) | |
Rise time | ≤ 2 s (UOut = 10 % ... 90 %) |
Minimum no-load power dissipation | < 8 W (120 V AC) |
Maximum no-load power dissipation | < 12 W (230 V AC) |
Minimum nominal load power dissipation | < 140 W (120 V AC) |
Power loss nominal load max. | < 180 W (230 V AC) |
Integrated fuse protection | yes |
Input | |
Position | 1.x |
Connection technology | |
Position marking | 1.1 (L/+), 1.2 (N/-), 1.3 () |
Conductor connection | |
Connection method | Screw connection |
rigid | 1.3 mm² ... 3 mm² |
2.5 mm² (recommended) | |
flexible | 1.3 mm² ... 3 mm² |
2.5 mm² (recommended) | |
flexible with ferrule without plastic sleeve | 1.3 mm² ... 3 mm² |
2.5 mm² (recommended) | |
flexible with ferrule with plastic sleeve | 1.3 mm² ... 3 mm² |
2.5 mm² (recommended) | |
rigid (AWG) | 10 ... 18 (Cu) |
13 (recommended) | |
AWG | 6 ... 4 |
6 (recommended) | |
Stripping length | 10 mm (rigid/flexible) |
8 mm (Ferrule) | |
Output | |
Position | 2.x |
Connection technology | |
Position marking | 2.1 (+), 2.2 (-) |
Conductor connection | |
Connection method | Copper busbars (Screw connection) |
rigid | 0.2 mm² ... 30 mm² |
25 mm² (recommended) | |
flexible | 0.2 mm² ... 30 mm² |
25 mm² (recommended) | |
flexible with ferrule without plastic sleeve | 0.2 mm² ... 30 mm² |
25 mm² (recommended) | |
flexible with ferrule with plastic sleeve | 0.2 mm² ... 30 mm² |
25 mm² (recommended) | |
rigid (AWG) | 6 ... 3 (Cu) |
3 (recommended) | |
AWG | 18 ... 10 (Cu) |
Stripping length | 10 mm (rigid/flexible) |
8 mm (Ferrule) | |
Conductor connection | |
rigid (AWG) | 32 ... 22 (Cu) |
24 (recommended) | |
Signal | |
Position | 3.x |
Connection technology | |
Position marking | 3.1 - 3.10, 4.1 - 4.10 |
Conductor connection | |
Connection method | Pin strip |
rigid | 0.1 mm² ... 0.4 mm² |
0.34 mm² (recommended) | |
flexible | 0.1 mm² ... 0.4 mm² |
0.34 mm² (recommended) | |
flexible with ferrule without plastic sleeve | 0.1 mm² ... 0.4 mm² |
0.34 mm² (recommended) | |
flexible with ferrule with plastic sleeve | 0.1 mm² ... 0.4 mm² |
0.34 mm² (recommended) | |
rigid (AWG) | 30 ... 22 |
22 (recommended) | |
Stripping length | 10 mm (rigid/flexible) |
8 mm (Ferrule) |
LED signaling | |
Types of signaling | LED |
Function | Visual operating state display |
Color | red, green |
LED signaling | |
Types of signaling | LED |
Function | Visual operating state display |
Color | red, green |
LED signaling | |
Types of signaling | LED |
Function | Visual operating state display |
Color | red, green |
LED signaling | |
Types of signaling | LED |
Function | Visual operating state display |
Color | red, green |
LED signaling | |
Types of signaling | LED |
Function | Visual operating state display |
Color | red, green |
LED signaling | |
Types of signaling | LED |
Function | Visual operating state display |
Color | red, green |
Signal output DC OK | |
Position | 4.x |
Type of signaling | DC OK switch contact - signal state operation (UN = 24 V DC, IOut = IN) |
Position marking | 3.1 (13) |
Function | Operating state forwarding |
Switching voltage | max. 30 V DC (SELV) |
Current carrying capacity | max. 10 mA |
Number of phases | 1.00 |
Insulation voltage input/output | 4 kV AC (type test) |
1.5 kV AC (routine test) |
Product type | Power supply |
Product family | TRIO POWER |
MTBF (IEC 61709, SN 29500) | > 500000 h (25 °C) |
Insulation characteristics | |
Protection class | I |
Degree of pollution | 2 |
Life expectancy (electrolytic capacitors) | |
Temperature | 25 °C |
Additional text | 8 years |
Item dimensions | |
Width | 108 mm |
Height | 41 mm |
Depth | 322 mm |
Mounting type | Panel mounting |
With protective coating | no |
Flammability rating according to UL 94 | V0 (Housing, terminal blocks) |
Hood version | Aluminum (AlMg3) |
Side element version | Aluminum |
Ambient conditions | |
Degree of protection | IP20 |
Ambient temperature (operation) | -20 °C ... 70 °C (>55℃ Derating: 3.33%/K) |
Ambient temperature (storage/transport) | -40 °C ... 70 °C |
Ambient temperature (start-up type tested) | -40 °C ... 70 °C |
Maximum altitude | ≤ 5000 m (> 2000 m, Derating: 10 %/1000 m) |
Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
Shock (operation) | 11 ms, 15g, per spatial direction (IEC 60068-2-27) |
Vibration (operation) | 10 Hz ... 18.2 Hz, amplitude ±0.75 mm (IEC 60068-2-6) |
18.2 Hz ... 150 Hz, 1g, 90 min. |
Overvoltage category | |
EN 61010-1 | III (≤ 2000 m) |
II (≤ 5000 m) | |
Overvoltage category | |
EN 61010-2-201 | III (≤ 2000 m) |
II (≤ 5000 m) | |
Safety of power supply units up to 1500 V (insulation distances) | |
Standard designation | Safety of power supply units up to 1500 V (insulation distances) |
Electrical safety | |
Standard designation | Electrical safety |
Standards/specifications | IEC 61010-2-201 (SELV) |
Safety for measurement, control, and laboratory equipment | |
Standard designation | Safety for equipment for measurement, control, and laboratory use |
Standards/specifications | IEC 61010-1 |
Protective extra-low voltage | |
Standard designation | Protective extra-low voltage |
Standards/specifications | IEC 61010-1 (SELV) |
IEC 61010-2-201 (PELV) | |
Safe isolation | |
Standard designation | Safe isolation |
Standards/specifications | IEC 61010-2-201 |
Limitation of harmonic line currents | |
Standard designation | Limitation of harmonic line currents |
Standards/specifications | EN 61000-3-2 |
Mains variation/undervoltage | |
Standard designation | Mains variation/undervoltage |
Standards/specifications | SEMI F47 - 0706 |
UL | |
Identification | UL/C-UL Listed UL 61010-1 |
UL | |
Identification | UL/C-UL Listed UL 61010-2-201 |
ANSI/UL 121201 | |
Identification | (EN) WARNING: Explosion Hazard - Do not connect or disconnect equipment unless power has been switched off or the area is known to be non-hazardous. (FR) AVERTISSEMENT : risque d'explosion - ne pas connecter ou déconnecter les équipements sauf si l'alimentation a été coupée ou si la zone est réputée non dangereuse. |
(EN) If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. (FR) Si l'équipement est utilisé d'une manière non spécifiée par le fabricant, la protection fournie par cet équipement peut être altérée. |
|
(EN) This equipement must be installed in a suitable, tool secured/key locked enclosure. (FR) Cet équipement doit être installé dans un boîtier approprié, verrouillé par une clé ou dont l'ouverture nécessite l'utilisation d'un outil. |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
EMC requirements for noise emission | EN 61000-6-3 |
Noise immunity | Immunity in accordance with EN 61000-6-1 (residential), EN 61000-6-2 (industrial) |
Conducted noise emission | EN 55016 EN 61000-6-3 |
Flicker | |
Standards/regulations | EN 61000-3-3 |
Frequency range | 0 kHz ... 2 kHz |
Electrostatic discharge | |
Standards/regulations | EN 61000-4-2 |
Electrostatic discharge | |
Contact discharge | 6 kV (Test Level 3) |
Discharge in air | 15 kV (Test Level 3) |
Comments | Criterion A |
Electromagnetic HF field | |
Standards/regulations | EN 61000-4-3 |
Electromagnetic HF field | |
Frequency range | 80 MHz ... 1 GHz |
Test field strength | 10 V/m (Test Level 3) |
Frequency range | 1 GHz ... 6 GHz |
Test field strength | 10 V/m (Test Level 3) |
Comments | Criterion A |
Fast transients (burst) | |
Standards/regulations | EN 61000-4-4 |
Fast transients (burst) | |
Input | asymmetrical 2 kV (Test Level 3) |
Comments | Criterion A |
Surge voltage load (surge) | |
Standards/regulations | EN 61000-4-5 |
Surge voltage load (surge) | |
Input | symmetrical 2 kV (Test Level 4 - symmetrical) |
asymmetrical 1 kV (Test Level 2 - asymmetrical) | |
Comments | Criterion A |
Conducted interference | |
Standards/regulations | EN 61000-4-6 |
Conducted interference | |
Input/Output | asymmetrical |
Frequency range | 0.15 MHz ... 80 MHz |
Comments | Criterion A |
Voltage | 6 V |
Power frequency magnetic field | |
Standards/regulations | EN 61000-4-8 |
Voltage dips | |
Standards/regulations | EN 61000-4-11 |
Voltage | 230 V AC |
Frequency | 50 Hz |
Criteria | |
Criterion A | Normal operating behavior within the specified limits. |
Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
Tuotenumero | 1635194 |
Pakkausyksikkö | 1 Kappaletta |
Vähimmäistilausmäärä | 1 Kappaletta |
Tuoteavain | CMHW13 |
Tuotekoodi | CMHW13 |
GTIN | 4067923157835 |
Paino kappaletta kohti (sis. pakkauksen) | 2 392 g |
Paino kappaletta kohti (ilman pakkausta) | 2 000 g |
Tullitariffinumero | 85044095 |
Alkuperämaa | CN |
ECLASS
ECLASS-13.0 | 27040701 |
ECLASS-11.0 | 27040701 |
ECLASS-12.0 | 27040701 |
ETIM
ETIM 9.0 | EC002540 |
EU RoHS | |
Täyttää RoHS-direktiivin vaatimukset | Kyllä |
poikkeussäännökset siltä osin kuin ne ovat tiedossa | 6(c), 7(c)-I |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-25
Löydät tuotekohtaisen Kiinan RoHS-ilmoitusluettelon kunkin tuotteen latausalueelta Valmistajan ilmoitus -kohdasta. EFUP-E-merkinnän sisältäville tuotteille ei tarvita Kiinan RoHS-ilmoitusluetteloa, eikä sitä tarvitse siksi laatia.
|
EU REACH SVHC | |
Huomautus REACH-kandidaattiaineesta (CAS-nro) | Lead (CAS-nro: 7439-92-1) |
Yhteensopivat tuotteet
-
QUINT4-UPS/24DC/24DC/40 - Uninterruptible power supply 2907077
-
VAL-SPP-T2-275-1+1-UT-R - Type 2 surge arrester 1466212
-
VAL-SEC-T2-2+0-380DC-FM - Type 2 surge arrester 2907876
-
VAL-SEC-T2-2+0-48DC-FM - Type 2 surge arrester 2907865
-
VAL-US-120/40/1+1-FM - Type 1 surge protection device 2910349
-
VAL-US-120/40/1+0-FM - Type 1 surge protection device 2910348
-
PLT-SEC-T3-120-FM-UT - Type 3 surge protection device 2907918
-
CBMC E4 24DC/1-4A NO - Electronic circuit breaker 2906031
-
CBMC EG4 24DC/1-8A NO - Electronic circuit breaker 1065730
-
CBMC E4 24DC/1-10A NO - Electronic circuit breaker 2906032
-
CBM E4 24DC/0.5-10A NO-R - Electronic circuit breaker 2905743
-
CAPAROC E4 12-24DC/1-4A - Electronic circuit breaker 1115657
-
CAPAROC E4 12-24DC/1-10A - Electronic circuit breaker 1115658
-
CBM E8 24DC/0.5-10A NO-R - Electronic circuit breaker 2905744
Edut
High power density and high efficiency with a compact design
Customized use through flexible panel mounting options
Robust and reliable due to integrated protective functions
Easy power increase with parallel connection with integrated O-ring diode
Smart diagnostics with comprehensive monitoring via LED signaling, CAN bus interface, and EOL (End Of Life) reminder
PHOENIX CONTACT OY
Niittytie 11, 01300 Vantaa