Panel feed-through terminal block, connection method: Screw connection with tension sleeve, Cable lug connection, number of positions: 1, load current: 150 A, cross section: 16 mm2 - 50 mm2, connection direction of the conductor to plug-in direction: 0 °, width: 18.8 mm, color: gray


Product Details




Plate thickness 1 mm ... 6 mm

Result Test passed
Air clearances and creepage distances | 6․ Insulation coordination
Rated surge voltage (III/3) 4 kV
minimum creepage distance (III/3) 3.2 mm
minimum clearance value - non-homogenous field (III/3) 3 mm
Insulating material group I
Comparative tracking index (IEC 60112:2003-01) CTI 600
Rated insulation voltage (III/3) 250 V
Specification IEC 60947-7-1:2002-07
Application Plastic panel 1.0 ... 6.0 mm
Internal part not molded
Electrical properties
Rated surge voltage (III/2) 8 kV
Pollution degree 3
Rated voltage (III/3) 690 V
Power-frequency withstand voltage
Result Test passed
Temperature-rise test
Requirement temperature-rise test Increase in temperature ≤ 45 K
Result Test passed
Surge voltage test
Result Test passed
Air clearances and creepage distances | 5․ Insulation coordination
Rated surge voltage (III/3) 4 kV
minimum creepage distance (III/3) 3.2 mm
minimum clearance value - non-homogenous field (III/3) 3 mm
Insulating material group I
Comparative tracking index (IEC 60112:2003-01) CTI 600
Rated insulation voltage (III/3) 250 V
Specification IEC 60947-7-1:2002-07
Application Metal wall 1.0 mm ... 6.0 mm
Internal part not molded
Air clearances and creepage distances | 4․ Insulation coordination
Rated surge voltage (III/3) 8 kV
minimum creepage distance (III/3) 12.5 mm
minimum clearance value - non-homogenous field (III/3) 8 mm
Insulating material group I
Comparative tracking index (IEC 60112:2003-01) CTI 600
Rated insulation voltage (III/3) 1000 V
Specification IEC 60947-7-1:2002-07
Application Plastic panel 1.0 ... 6.0 mm
Internal part molded
Air clearances and creepage distances | 3․ Insulation coordination
Rated surge voltage (III/3) 8 kV
minimum creepage distance (III/3) 12.5 mm
minimum clearance value - non-homogenous field (III/3) 8 mm
Insulating material group I
Comparative tracking index (IEC 60112:2003-01) CTI 600
Rated insulation voltage (III/3) 1000 V
Specification IEC 60947-7-1:2002-07
Application Metal panel 1.0 mm ... 2.0 mm
Internal part molded
Air clearances and creepage distances | 2․ Insulation coordination
Rated surge voltage (III/3) 8 kV
minimum creepage distance (III/3) 10 mm
minimum clearance value - non-homogenous field (III/3) 8 mm
Insulating material group I
Comparative tracking index (IEC 60112:2003-01) CTI 600
Rated insulation voltage (III/3) 800 V
Specification IEC 60947-7-1:2002-07
Application Metal panel 2.0 mm ... 4.5 mm
Internal part molded
Air clearances and creepage distances | 1․ Insulation coordination
Rated surge voltage (III/3) 8 kV
minimum creepage distance (III/3) 8 mm
minimum clearance value - non-homogenous field (III/3) 8 mm
Insulating material group I
Comparative tracking index (IEC 60112:2003-01) CTI 600
Rated insulation voltage (III/3) 690 V
Specification IEC 60947-7-1:2002-07
Application Metal wall 4.5 mm ... 6.0 mm
Internal part molded

rated voltage (III/3) 690 V
rated voltage (III/2) 1000 V
rated voltage (II/2) 1000 V
Rated surge voltage 8 kV
Nominal current IN 150 A
Maximum load current 150 A

Type of packaging packed in cardboard

Oscillation/broadband noise
Needle-flame test
Time of exposure 30 s
Result Test passed
Shocks

Dimensional drawing
Pitch 18.8 mm
Height 54 mm
Plate thickness 1 mm ... 6 mm
Width 18.8 mm
External dimensions
Length_external 43 mm
Width 18.8 mm
Height_external 54 mm
Internal dimensions
Length_inside 48.5 mm

Mechanical strength
Result Test passed

Safety note
Safety note • Only electrically qualified personnel may install and operate the product.
To recognize and prevent danger, the qualified personnel must be familiar with the basics of electrical engineering.
• Observe the technical data provided here and refer to the documents listed under “Downloads”. The download area contains important information, such as installation notes, technical drawings, and 3D data.
• The cable entry funnel is not safe to touch. Never connect or disconnect the terminal when it is energized. Take appropriate steps to ensure touch protection.
• To maintain the nominal voltage, align the cable lugs straight and centered, and cast the terminals on the inside.
 There is no electrical contact to the housing. Make sure that protective grounding is provided for green/yellow color variants and articles marked with PE.

Connection technology
Nominal cross section 50 mm2
Conductor connection exterior
2 conductors with same cross section, solid 6 mm2 ... 16 mm2
Torque 6 Nm ... 8 Nm
Conductor cross section flexible, with ferrule without plastic sleeve 10 mm2 ... 50 mm2
Internal cylindrical gage B10
2 conductors with same cross section, flexible, with ferrule without plastic sleeve 6 mm2 ... 16 mm2
Conductor cross section solid 16 mm2 ... 50 mm2
Stripping length 24 mm
2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve 6 mm2 ... 10 mm2
Connection method Screw connection with tension sleeve
2 conductors with same cross section, flexible 10 mm2 ... 16 mm2
Conductor cross section, flexible, with ferrule, with plastic sleeve 10 mm2 ... 50 mm2
Conductor cross section flexible 16 mm2 ... 50 mm2
Connection direction of the conductor to plug-in direction 0 °
Conductor connection interior
Torque 6 Nm ... 8 Nm
Stripping length 24 mm
Connection method Cable lug connection
Connection direction of the conductor to plug-in direction 0 °

Material data - housing
Insulating material group I
Temperature for the ball pressure test according to EN 60695-10-2 125 °C
Glow wire flammability index GWFI according to EN 60695-2-12 850
CTI according to IEC 60112 600
Housing color gray (7042)
Insulating material PA
Flammability rating according to UL 94 V0
Glow wire ignition temperature GWIT according to EN 60695-2-13 775
Material data - contact
Contact material Cu alloy
Surface characteristics tin-plated
Note WEEE/RoHS-compliant, free of whiskers according to IEC 60068-2-82/JEDEC JESD 201

Number of positions 1
Number of potentials 1
Number of levels 1
Number of connections 2
Insulation characteristics
Overvoltage category III
Degree of pollution 3


Order Key 0709123
Packing unit 10 pc
Minimum order quantity 1 pc
Sales Key 014
Catalog Page Page 619 (C-1-2013)
GTIN 4017918004941
Weight per Piece (including packing) 92,2 GRM
Weight per Piece (excluding packing) 86,1 GRM
Customs tariff number 85369010
Country of origin GR



CSA

Approval Specification Data
Usegroup B C
Nominal voltage UN 600 V 600 V
Nominal current IN 125 A 125 A
AWG/kcmil 6 6
Min. cross section 6 mm² 6 mm²

UL Recognized

Approval Specification Data
Usegroup B C
Nominal voltage UN 600 V 600 V
Nominal current IN 170 A 170 A
AWG/kcmil 6 6
Min. cross section 6 mm² 6 mm²

KEMA-KEUR

Approval Specification Data
Nominal voltage UN 690 V
Nominal current IN 150 A
AWG/kcmil 6
Max. cross section 50 mm²

IECEE CB Scheme

Approval Specification Data
Nominal voltage UN 690 V
Nominal current IN 150 A
AWG/kcmil 6
Max. cross section 50 mm²

EAC


China RoHS Environmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values


Your advantages

Well-known connection principle allows worldwide use
Low temperature rise, thanks to maximum contact force
Tool-free snap-in principle enables easy mounting on the device panel
Automatic panel thickness compensation enables universal use
Reliable seal even with low-viscosity molding compounds