- Home
- Products
- Surge protection
- Surge protection for power supplies
- Type 2 surge arrester - VAL-SEC-T2-4+0-440-FM
Type 2 surge arrester - VAL-SEC-T2-4+0-440-FM
1076468
Plug-in surge arrester, in accordance with Type 2/Class II, for 3-phase power supply networks with separate N and PE (5-conductor system: L1, L2, L3, N, PE), with remote indication contact.
Product Details
General | |
Note | Usable in all low-voltage systems between L-N or L-PEN. Only usable in IT Systems between L-PE and N-PE, if the exposed-conductive-parts (bodies) of the equipment of the low-voltage installation is connected to the earthing arrangement of the transformer substation. (interconnected earthing arrangement of the HV-transformer substation with the bodies of the LV-installation. RE = RA accordance to IEC 60364-4-442 / VDE 0100-442 Fig. 44D / Example a) |
IEC test classification | II |
T2 | |
EN type | T2 |
IEC power supply system | TN-S |
IT | |
Type | DIN rail module, two-section, divisible |
Product type | Surge arrester |
Number of positions | 3 |
Surge protection fault message | Optical, remote indicator contact |
Insulation characteristics | |
Overvoltage category | III |
Pollution degree | 2 |
Nominal frequency fN | 50 Hz (60 Hz) |
Indicator/remote signaling | |
Connection name | Remote fault indicator contact |
Switching function | Changeover contact |
Operating voltage | 5 V AC ... 250 V AC |
125 V DC (200 mA DC) | |
Operating current | 5 mA AC ... 1 A AC |
1 A DC (30 V DC) |
Connection method | Screw connection |
Screw thread | M5 |
Tightening torque | 4.5 Nm |
Stripping length | 16 mm |
Conductor cross section flexible | 2.5 mm² ... 16 mm² |
Conductor cross section solid | 2.5 mm² ... 25 mm² |
Conductor cross section AWG | 12 ... 4 |
Connection method | Fork-type cable lug |
Conductor cross section flexible | 1.5 mm² ... 6 mm² |
Remote fault indicator contact | |
Connection method | Plug-in/screw connection via COMBICON |
Screw thread | M2 |
Tightening torque | 0.25 Nm |
Conductor cross section flexible | 0.14 mm² ... 1.5 mm² |
Conductor cross section solid | 0.14 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 |
Dimensional drawing |
|
Width | 49.2 mm |
Height | 97.9 mm |
Depth | 74.5 mm (incl. DIN rail 7.5 mm) |
Horizontal pitch | 2.7 Div. |
Color | light grey RAL 7035 |
traffic grey A RAL 7042 | |
Flammability rating according to UL 94 | V-0 |
CTI value of material | 600 |
Insulating material | PA6.6-FR 20% GF |
PBT-FR | |
Material group | I |
Housing material | PA 6.6-FR 20 % GF |
PBT-FR |
Mode of protection | L-N |
L-PE | |
N-PE | |
Direction of action | 3L-N/PE |
Nominal voltage UN | 400/690 V AC (TN-S) |
400 V AC (IT) | |
Nominal frequency fN | 50 Hz (60 Hz) |
Maximum continuous voltage UC | 440 V AC |
Rated load current IL | 40 A (Biconnect M4 fork-type cable lug 6 mm²) |
63 A (TWIN ferrule 2 x 10 mm²) | |
Standby power consumption PC | ≤ 720 mVA |
Nominal discharge current In (8/20) µs | 20 kA |
Maximum discharge current Imax (8/20) µs | 40 kA |
Short-circuit current rating ISCCR | 25 kA (for a backup fuse of up to 315 A gG) |
50 kA (for a backup fuse of up to 200 A gG) | |
Voltage protection level Up (L-N) | ≤ 4 kV |
Voltage protection level Up (L-PE) | ≤ 1.9 kV |
Voltage protection level Up (N-PE) | ≤ 1.9 kV |
Residual voltage Ures (L-N) | ≤ 4 kV (at In) |
≤ 3.5 kV (at 10 kA) | |
≤ 3.2 kV (at 5 kA) | |
≤ 3.1 kV (at 4 kA) | |
≤ 2.85 kV (at 2 kA) | |
Residual voltage Ures (L-PE) | ≤ 1.9 kV (at In) |
≤ 1.65 kV (at 10 kA) | |
≤ 1.5 kV (at 5 kA) | |
≤ 1.45 kV (at 4 kA) | |
≤ 1.35 kV (at 2 kA) | |
Residual voltage Ures (N-PE) | ≤ 1.9 kV (at In) |
≤ 1.65 kV (at 10 kA) | |
≤ 1.5 kV (at 5 kA) | |
≤ 1.45 kV (at 4 kA) | |
≤ 1.35 kV (at 2 kA) | |
TOV behavior at UT | 581 V AC (5 s / withstand mode) |
762 V AC (120 min / safe failure mode) | |
Response time tA | ≤ 25 ns |
Max. backup fuse with V-type through wiring | 40 A (gG / Biconnect M4 fork-type cable lug, 6 mm²) |
63 A (gG / TWIN ferrule 2x 10mm²) | |
Max. backup fuse with branch wiring | 315 A (gG) |
Ambient conditions | |
Degree of protection | IP20 |
Ambient temperature (operation) | -40 °C ... 80 °C |
Ambient temperature (storage/transport) | -40 °C ... 80 °C |
Altitude | ≤ 2000 m (amsl (above mean sea level)) |
Permissible humidity (operation) | 5 % ... 95 % |
Shock (operation) | 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
Vibration (operation) | 5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
Standards/specifications | IEC 61643-11 |
EN 61643-11 | |
Standards/specifications | EN 61643-11 |
Mounting type | DIN rail: 35 mm |
Item number | 1076468 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Sales Key | 00 |
Product Key | CL1351 |
Catalog Page | Page 53 (C-4-2019) |
GTIN | 4055626784809 |
Weight per Piece (including packing) | 430.6 g |
Weight per Piece (excluding packing) | 404.74 g |
Customs tariff number | 85363030 |
Country of origin | DE |
ECLASS
ECLASS-9.0 | 27130805 |
ECLASS-10.0.1 | 27130805 |
ECLASS-11.0 | 27130805 |
ECLASS-12.0 | 27171202 |
ETIM
ETIM 8.0 | EC000941 |
UNSPSC
UNSPSC 21.0 | 39121600 |
Compatible Products
-
-
Marker pen X-PEN 0,35 - 0811228
-
Label EML (20XE)R - 0803452
-
Label EML (20XE)R YE - 0803453
-
Zack marker strip ZBN 18:UNBEDRUCKT - 2809128
-
Marker for terminal blocks ZBN 18,LGS:L1-N,ERDE - 2749576
-
Marker for terminal blocks ZBN 18,LGS:ERDE - 2749589
-
Flat zack marker sheet ZBFM 5/WH:UNBEDRUCKT - 0803595
-
Type 2 surge protection plug VAL-SEC-T2-440-P - 2909969