PSR-MC32-3NO-1NC-24-230UC-SC
-
Safety relays
2700524
Safety relay for emergency stop, safety doors, and light grids up to SIL 3, Cat. 4, PL e, 1 or 2-channel operation, automatic or manual, monitored start, 3 enabling current paths, 1 signaling current path, US = 24 ... 230 V AC/DC, plug-in screw terminal block
Free download available.
Downloads
Product details
Note on application | |
Note on application | Only for industrial use |
Product type | Safety relays |
Product family | PSRmini |
Application | Emergency stop |
Safety door | |
Solenoid switch | |
Transponder | |
Light grid | |
Relay type | Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3 |
Data management status | |
Article revision | 01 |
Times | |
Typical response time | < 150 ms (automatic start) |
< 100 ms (manual, monitored start) | |
Typ. starting time with Us | < 200 ms (when controlled via A1) |
Typical release time | < 20 ms (when actuation is via the sensor circuit) |
Restart time | < 1 s |
Recovery time | < 500 ms |
Maximum power dissipation for nominal condition | 17.3 W (at IL² = 72 A²) |
Nominal operating mode | 100% operating factor |
Air clearances and creepage distances between the power circuits | |
Rated insulation voltage | 250 V AC |
Rated surge voltage/insulation | Basic insulation 4 kV between enabling current path (23/24) and enabling current path (33/34) and signaling current path (41/42) |
Basic insulation 4 kV between all current paths and housing | |
Safe isolation, reinforced insulation 6 kV between all other circuits | |
Supply | |
Designation | A1/A2 |
Rated control circuit supply voltage US | 24 V AC/DC ... 230 V AC/DC -15 % / +10 % |
Rated control supply current IS | typ. 103 mA (24 V DC) |
typ. 47 mA (48 V DC) | |
typ. 38 mA (110 V AC) | |
typ. 21 mA (230 V AC) | |
Power consumption at US | 2.7 W (with DC) |
2.9 W (with AC) | |
Apparent power | typ. 5 VA (at US) |
Inrush current | < 80 A (Δt = 50 µs at Us) |
Filter time | 2 ms (at A1 in the event of voltage dips at Us) |
Protective circuit | US: surge protection; 275 V varistor / 411 V suppressor diode |
Digital: Sensor circuit (S10, S12, S13, S22) | |
Description of the input | safety-related sensor inputs |
Number of inputs | 4 |
Input voltage range "0" signal | 0 V DC ... 5 V DC (for safe Off; at S10/S12/S13) |
Input current range "0" signal | 0 mA ... 2 mA (for safe Off; at S10/S12/S13) |
Inrush current | < 5 mA (with Us/Ix at S10/S12/S13) |
> -5 mA (with Us/Ix to S22) | |
Filter time | max. 1.5 ms (to S10-S12; test pulse width; at 24 V DC) |
7.5 ms (to S10-S12; test pulse rate; at 24 V DC) | |
Test pulse rate = 5 x Test pulse width | |
Concurrence | ∞ |
Max. permissible overall conductor resistance | 150 Ω |
Protective circuit | Inputs: protection against polarity reversal, surge protection; 38.6 V suppressor diode |
Current consumption | < 5 mA (with Us/Ix at S10/S12/S13) |
> -5 mA (with Us/Ix to S22) | |
Digital: Start circuit (S34, S35) | |
Description of the input | non-safety-related |
Number of inputs | 2 |
Inrush current | < 10 mA (Δt = 330 ms) |
Max. permissible overall conductor resistance | 150 Ω |
Protective circuit | Suppressor diode |
Voltage at input/start and feedback circuit | 24 V DC -20 % / +25 % |
Current consumption | typ. 2.5 mA (S34) |
typ. 1 mA (S35) |
Relay: Enabling current paths (13/14, 23/24, 33/34) | |
Output description | safety-related N/O contacts |
Number of outputs | 3 (undelayed) |
Contact switching type | 3 enabling current paths |
Contact material | AgSnO2 |
Switching voltage | min. 5 V AC/DC |
max. 250 V AC/DC (Observe the load curve) | |
Switching capacity | min. 50 mW |
Inrush current | min. 10 mA |
max. 6 A | |
Switching capacity in accordance with IEC 60947-5-1 | 5 A (24 V (DC13)) |
5 A (250 V (AC15)) | |
Limiting continuous current | 6 A (observe derating) |
Sq. Total current | 72 A2 (observe derating) |
Switching frequency | max. 1 Hz |
Mechanical service life | 10x 106 cycles |
Interrupting rating (ohmic load) max. | 1500 VA (250 V AC, τ = 0 ms) |
For additional values, see load curve | |
Maximum interrupting rating (inductive load) | 48 W (24 V DC, τ = 40 ms) |
40 W (48 V DC, τ = 40 ms) | |
36 W (60 V DC, τ = 40 ms) | |
35 W (110 V DC, τ = 40 ms) | |
33 W (220 V DC, τ = 40 ms) | |
1500 VA (250 V AC, τ = 40 ms) | |
Output fuse | 6 A gL/gG |
4 A gL/gG (for low-demand applications) | |
Relay: Signaling current path (41/42) | |
Output description | non-safety-related N/C contact |
Number of outputs | 1 (undelayed) |
Contact switching type | 1 signaling current path |
Contact material | AgSnO2 |
Switching voltage | min. 5 V AC/DC |
max. 250 V AC/DC | |
Switching capacity | min. 50 mW |
Inrush current | min. 10 mA |
max. 6 A | |
Limiting continuous current | 6 A |
Switching frequency | 1 Hz |
Mechanical service life | 10x 106 cycles |
Output fuse | 6 A gL/gG |
4 A gL/gG (for low-demand applications) |
Connection technology | |
pluggable | yes |
Conductor connection | |
Connection method | Screw connection |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross-section AWG | 24 ... 12 |
Stripping length | 7 mm |
Screw thread | M3 |
Status display | 3 x LED (green) |
Operating voltage display | 1 x green LED |
Width | 22.5 mm |
Height | 112.2 mm |
Depth | 114.5 mm |
Color (Housing) | yellow (RAL 1018) |
Housing material | Polyamide |
Safety data | |
Stop category | 0 |
Safety data: EN ISO 13849 | |
Category | 4 |
Performance level (PL) | e |
Safety data: IEC 61508 - High demand | |
Safety Integrity Level (SIL) | 3 |
Safety data: IEC 61508 - Low demand | |
Safety Integrity Level (SIL) | 3 |
Safety data: EN IEC 62061 | |
Safety Integrity Level (SIL) | 3 |
Ambient conditions | |
Degree of protection | IP20 |
Min. degree of protection of inst. location | IP54 |
Ambient temperature (operation) | -40 °C ... 55 °C (observe derating) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Maximum altitude | ≤ 2000 m (Above sea level) |
Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
Shock | 15g |
Vibration (operation) | 10 Hz ... 150 Hz, 2g |
CE | |
Identification | CE-compliant |
Air clearances and creepage distances between the power circuits | |
Standards/regulations | EN 60947-1 |
Mounting type | DIN rail mounting |
Assembly note | See derating curve |
Mounting position | vertical or horizontal |
Item number | 2700524 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Sales key | DN01 |
Product key | DNA181 |
Catalog page | Page 221 (C-6-2019) |
GTIN | 4046356912693 |
Weight per piece (including packing) | 243.8 g |
Weight per piece (excluding packing) | 243.8 g |
Customs tariff number | 85371098 |
Country of origin | DE |
ECLASS
ECLASS-11.0 | 27371819 |
ECLASS-13.0 | 27371819 |
ECLASS-12.0 | 27371819 |
ETIM
ETIM 9.0 | EC001449 |
UNSPSC
UNSPSC 21.0 | 39122200 |
EU RoHS | |
Fulfills EU RoHS substance requirements | Yes |
Exemption | 7(a), 7(c)-I |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-50
An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required.
|
EU REACH SVHC | |
REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) |
SCIP | 21cea9ff-7e80-4410-97b3-0c2f7f6afd45 |
Compatible products
Your advantages
Up to Cat. 4/PL e in accordance with EN ISO 13849-1, SIL 3 in accordance with EN IEC 62061
1 or 2-channel control
3 enabling current paths, 1 signaling current path
Manually monitored and automatic activation in a single device
Cross-circuit detection
PHOENIX CONTACT
586 Fulling Mill Road, Middletown, PA 17057