The power supply duplicator with plug-in connection technology supplies the transmitter in the field and electrically isolates the input signal transmitted to two loads. HART data protocols can be transmitted bi-directionally via both outputs. You can use the device in signal and power supply duplicator mode with a transmitter supply voltage of >19.5 V. On the output side, the module can be connected to passive input cards. For a maximum load of ≤500 Ω per channel, electrically isolated analog standard signals 0 mA ... 20 mA or 4 mA ... 20 mA are available. The measuring transducer supports fault monitoring and NFC communication.
MINI MCR-2-RPSS-I-2I-PT
-
Repeater power supply
2905629
4-way power supply doubler with plug-in connection technology. HART-transparent, 0(4) mA ... 20 mA input signal, 0(4) mA ... 20 mA output signals. The device can be used in both signal and power supply doubler modes. Push-in connection technology.
Free download available.
Downloads
Product details
Utilization restriction | |
EMC note | EMC: class A product, see manufacturer's declaration in the download area |
Product type | Repeater power supplies |
Product family | MINI Analog Pro |
No. of channels | 2 |
Type | Signal conditioner |
Configuration | DIP switches |
Insulation characteristics: GB Standard | |
Overvoltage category | II |
Pollution degree | 2 |
No. of channels | 2 |
Electrical isolation | 4-way isolation |
Limit frequency (3 dB) | > 1 kHz |
Signal transmission behavior | In = Out |
Step response (10-90%) | < 400 µs |
Maximum temperature coefficient | 0.0075 %/K |
Maximum transmission error | 0.05 % (of final value) |
Electrical isolation Input/output/power supply | |
Rated insulation voltage | 300 Vrms |
Test voltage | 3 kV AC (50 Hz, 60 s) |
Insulation | Reinforced insulation according to IEC/EN 61010-1 |
Supply | |
Nominal supply voltage | 24 V DC |
Supply voltage range | 9.6 V DC ... 30 V DC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN 60715) |
Typical current consumption | 40 mA (For 24 V DC and in signal duplicator mode) |
65 mA (For 24 V DC and in power supply duplicator mode) | |
75 mA (For 12 V DC and in signal duplicator mode) | |
130 mA (For 12 V DC and in power supply duplicator mode) | |
Power consumption | 1.6 W (at IOUT = 20 mA, 500 Ω load) |
Signal: Current | |
Description of the input | Sensor circuit |
Number of inputs | 1 |
Current input signal | 0 mA ... 20 mA (Signal duplicator mode) |
4 mA ... 20 mA (Power supply and signal duplicator mode) | |
Input resistance current input | 90 Ω (+1.6 V) |
Transmitter supply voltage | > 19.5 V |
Signal: Current | |
Number of outputs | 2 |
Non-load voltage | < 20 V |
Current output signal | 0 mA ... 20 mA (Signal duplicator mode) |
4 mA ... 20 mA (Power supply and signal duplicator mode) | |
Max. current output signal | 25 mA |
Load/output load current output | ≤ 500 Ω (per channel) |
Ripple | < 20 mVPP (500 Ω) |
Connection method | Push-in connection |
Stripping length | 10 mm |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² (with ferrule) |
0.14 mm² ... 2.5 mm² (without ferrule) | |
Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 12 (flexible) |
Ex installation (EPL) | Gc |
Div. 2 |
Data communication (bypass) | |
HART function | Yes |
Limit frequency (3 dB) | 1 kHz |
Status display | Green LED (supply voltage) |
Width | 6.2 mm |
Height | 109.81 mm |
Depth | 119.2 mm |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
Housing material | PBT |
Ambient conditions | |
Degree of protection | IP20 (not assessed by UL) |
Ambient temperature (operation) | -40 °C ... 70 °C |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Altitude | ≤ 2000 m |
Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
CE | |
Certificate | CE-compliant |
ATEX | |
Identification | II 3 G Ex ec ic IIC T4 Gc |
Certificate | BVS 19 ATEX E 047 X |
UKCA Ex (UKEX) | |
Identification | II 3 G Ex ec ic IIC T4 Gc |
Certificate | PxCIF21UKEX2902000X |
IECEx | |
Identification | Ex ec ic IIC T4 Gc |
Certificate | IECEx BVS 19.0041X |
CCC / China-Ex | |
Identification | Ex nA ic IIC T4 Gc |
UL, USA/Canada | |
Identification | UL 508 Listed |
Class I, Div. 2, Groups A, B, C, D T5 | |
Class I, Zone 2, Group IIC T5 | |
Shipbuilding approval | |
Certificate | DNV GL TAA000021E Rev. 1 |
EAC Ex | |
Identification | 2Ex ec ic IIC T4 Gc |
Certificate | BY/112 02.01 TP012 103.01 00081 |
DNV GL data | |
Temperature | B |
Humidity | B |
Vibration | A |
EMC | A |
Enclosure | Required protection according to the Rules shall be provided upon installation on board |
Noise immunity | EN 61000-6-2 |
Note | When being exposed to interference, there may be minimal deviations. |
Electromagnetic compatibility | Conformance with EMC directive |
Noise emission | EN 61000-6-4 |
Electrostatic discharge | |
Standards/regulations | EN 61000-4-2 |
Electrostatic discharge | |
Comments | Safety measures must be taken to prevent electrostatic discharge. |
Electromagnetic HF field | |
Designation | Electromagnetic RF field |
Standards/regulations | EN 61000-4-3 |
Fast transients (burst) | |
Designation | Fast transients (burst) |
Standards/regulations | EN 61000-4-4 |
Surge current load (surge) | |
Standards/regulations | EN 61000-4-5 |
Conducted interference | |
Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 |
Electrical isolation | 4-way isolation |
GB Standard | |
Standards/regulations | GB 3836.1 |
GB 3836.4 | |
GB 3836.8 |
Mounting type | DIN rail mounting |
Assembly instructions | The DIN rail connector can be used for bridging the supply voltage. It can be snapped onto a 35 mm EN 60715 DIN rail. |
Mounting position | any |
Item number | 2905629 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Sales key | C404 |
Product key | CK1411 |
Catalog page | Page 78 (C-5-2019) |
GTIN | 4046356999441 |
Weight per piece (including packing) | 120.6 g |
Weight per piece (excluding packing) | 120 g |
Customs tariff number | 85437090 |
Country of origin | DE |
ECLASS
ECLASS-11.0 | 27210120 |
ECLASS-12.0 | 27210120 |
ECLASS-13.0 | 27210120 |
ETIM
ETIM 8.0 | EC002653 |
UNSPSC
UNSPSC 21.0 | 39121000 |
DNV GL
Approval ID: TAA000021EUL Listed
Approval ID: FILE E 238705CCC
Approval ID: 2021322303003858cUL Listed
Approval ID: FILE E 238705IECEx
Approval ID: IECEx BVS 19.0041XcUL Listed
Approval ID: FILE E 196811UL Listed
Approval ID: FILE E 196811ATEX
Approval ID: BVS 19 ATEX E 047 XcULus Listed
cULus Listed
REACh SVHC | Lead 7439-92-1 |
China RoHS | Environmentally Friendly Use Period = 50 years |
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads” |
Compatible products
-
ME 6,2 TBUS-2 1,5/5-ST-3,81 GY - DIN rail bus connectors 2695439
-
ME 6,2 TBUS-2 1,5/5-ST-3,81 GN - DIN rail bus connectors 2869728
-
GW HART USB MODEM - Cable adapter 1003824
-
TC-D37SUB-AIO16-MP-PS-UNI - Module carrier 2906640
-
TC-D37SUB-ADIO16-MP-P-UNI - Module carrier 2906639
-
MINI MCR-2-V8-FLK 16 - System adapter 2901993
-
MINI MCR-2-V8-MOD-RTU - Communication module 2905634
-
MINI MCR-2-V8-MOD-TCP - Communication module 2905635
-
MINI MCR-2-V8-PB-DP - Communication module 2905636
-
MINI MCR-2-V8-PN - Communication module 2905637
-
FASTCON PRO-SET - Connector set 2906227
-
FASTCON PRO-SET-PT - Connector set 2906228
-
UCT-EM (30X5) - Marker for end clamp 0801505
-
UCT-EM (30X5) CUS - Marker for end clamp 0801589
-
SK 5,0 WH:REEL - Marker strip 0805221
-
UC-EMLP (15X5) - Plastic label 0819301
-
UC-EMLP (15X5) YE - Plastic label 0822615
-
UC-EMLP (15X5) CUS - Plastic label 0824550
-
UC-EMLP (15X5) YE CUS - Plastic label 0824551
-
UC-EMLP (15X5) SR - Plastic label 0828095
-
UC-EMLP (15X5) SR CUS - Plastic label 0828099
-
US-EMLP (15X5) - Plastic label 0828790
-
US-EMLP (15X5) YE - Plastic label 0828873
-
US-EMLP (15X5) SR - Plastic label 0828874
-
US-EMLP (15X5) CUS - Plastic label 0830076
-
US-EMLP (15X5) YE CUS - Plastic label 0830077
-
US-EMLP (15X5) SR CUS - Plastic label 0830078
-
UCT-EM (30X5) YE - Marker for end clamp 0830340
-
UCT-EM (30X5) YE CUS - Marker for end clamp 0830348
-
MINI MCR-2-PTB - Power terminal block 2902066
-
MINI MCR-2-PTB-PT - Power terminal block 2902067
-
QUINT4-SYS-PS/1AC/24DC/2.5/SC - Power supply unit 2904614
-
MINI MCR-2-FM-RC - Monitoring module 2904504
-
MINI MCR-2-FM-RC-PT - Monitoring module 2904508
-
SZS 0,6X3,5 - Screwdriver 1205053