Measuring transducer repeater power supply and input signal conditioner, HART-transparent. Transmits supplied or active 0/4 mA … 20 mA electrically isolated signals from the field to two loads. 4-way electrical isolation, Push-in connection, SIL, PL.
Utilization restriction | |
EMC note | EMC: class A product, see manufacturer's declaration in the download area |
Product type | Repeater power supplies |
No. of channels | 1 |
Type | Signal conditioners with SIL and PL Functional Safety |
Insulation characteristics | |
Overvoltage category | II |
Pollution degree | 2 |
No. of channels | 1 |
Electrical isolation | 3-way isolation |
Electrical isolation between input and output | yes |
Maximum power dissipation for nominal condition | 1.45 W (24 V DC / 20 mA) |
Step response (10-90%) | 1.3 ms (for jump 4 mA ... 20 mA, typical) |
Maximum temperature coefficient | < 0.01 %/K |
Maximum transmission error | < 0.1 % (of final value) |
Transmission error, typical | < 0.05 % (of final value) |
Electrical isolation Input/output/power supply | |
Rated insulation voltage | 300 Vrms |
Test voltage | 2.5 kV AC (50 Hz, 60 s) |
Insulation | Safe isolation in accordance with IEC/EN 61010-1 |
Electrical isolation Output 1/output 2 | |
Test voltage | 1.5 kV AC (50 Hz, 60 s) |
Supply | |
Designation | Repeater power supply operation |
Nominal supply voltage | 24 V DC |
Supply voltage range | 19.2 V DC ... 30 V DC (24 V DC, -20 % ... +25 %) |
Max. current consumption | < 75 mA (24 V DC / 20 mA) |
Power dissipation | < 1.45 W (24 V DC / 20 mA) |
Supply | |
Designation | Signal conditioner operation |
Nominal supply voltage | 24 V DC |
Nominal supply voltage range | 19.2 V DC ... 30 V DC (24 V DC, -20 % ... +25 %) |
Max. current consumption | < 46 mA (24 V DC / 20 mA) |
Power dissipation | < 1.2 W (24 V DC / 20 mA) |
Signal | |
Description of the input | Repeater power supply operation |
Number of inputs | 1 |
Current input signal | 4 mA ... 20 mA |
Transmitter supply voltage | > 21.5 V (20 mA) |
> 21 V (23 mA) | |
Underload/overload signal range | 0 mA ... 24 mA (Extended transmission range for diagnostics) |
Signal | |
Description of the input | Signal conditioner operation |
Current input signal | 0 mA ... 20 mA |
4 mA ... 20 mA | |
Voltage drop | < 3.9 V (in input isolating amplifier operation) |
Underload/overload signal range | 0 mA ... 24 mA (Extended transmission range for diagnostics) |
Signal: Repeater power supply operation | |
Output description | Repeater power supply operation |
Number of outputs | 2 |
Current output signal | 4 mA ... 20 mA (active) |
0 mA ... 20 mA | |
Load/output load current output | < 450 Ω (20 mA) |
< 380 Ω (23 mA) | |
Output ripple | < 20 mVrms |
Output behavior in the event of an error | 0 mA (Cable break in the input) |
≥ 23 mA (Cable short-circuit in the input) | |
Underload/overload signal range | 0 mA ... 24 mA (Extended transmission range for diagnostics) |
Signal: Signal conditioner operation | |
Output description | Signal conditioner operation |
Current output signal | 0 mA ... 20 mA (active) |
4 mA ... 20 mA (active) | |
Load/output load current output | < 450 Ω (20 mA) |
< 380 Ω (23 mA) | |
Output ripple | < 20 mVrms |
Output behavior in the event of an error | 0 mA (Cable break in the input) |
0 mA (Cable short-circuit in the input) | |
Underload/overload signal range | 0 mA ... 24 mA (Extended transmission range for diagnostics) |
Connection method | Push-in connection |
Stripping length | 8 mm |
Conductor cross section solid | 0.2 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Data communication (bypass) | |
HART function | Yes |
Protocols supported | HART |
Status display | Green LED (supply voltage) |
Width | 12.5 mm |
Height | 116 mm |
Depth | 113.7 mm |
114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715) |
Flammability rating according to UL 94 | V0 (Housing) |
Housing material | PA 6.6-FR |
Ambient conditions | |
Degree of protection | IP20 (not assessed by UL) |
Ambient temperature (operation) | -20 °C ... 60 °C (Any mounting position) |
Ambient temperature (storage/transport) | -40 °C ... 80 °C |
Altitude | ≤ 2000 m |
Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
CE | |
Certificate | CE-compliant |
Note | and EN 61326-1 |
CE | |
Identification | II 3 G Ex nA IIC T4 Gc X |
Certificate | PxCCIF11ATEX2924825 |
CE | |
Identification | II 3 G Ex nA IIC T4 Gc |
Certificate | PxCIF21UKEX2924825X |
CE | |
Identification | UL 508 Listed |
UL 61010 Listed | |
Class I, Div. 2, Groups A, B, C, D T4 | |
Class I, Zone 2, Groups IIC, IIB, IIA T4 | |
CE | |
Identification | UL 61010 Listed |
Class I, Div. 2, Groups A, B, C, D T4 | |
Class I, Zone 2, Group IIC T4 | |
CE | |
Identification | C, EMC2 |
Certificate | DNV GL TAA000020C |
CE | |
Identification | 2 |
CE | |
Identification | d |
CE | |
Identification | 2Ex nA IIC T4 Gc |
Certificate | BY/112 02.01 TP012 103.01 00078 |
DNV GL data | |
Temperature | B |
Humidity | B |
Vibration | A |
EMC | A |
Enclosure | Required protection according to the Rules shall be provided upon installation on board |
Electromagnetic compatibility | Conformance with EMC directive |
Noise emission | EN 61000-6-4 |
Noise immunity | EN 61000-6-2 |
Note | When being exposed to interference, there may be minimal deviations. |
Electromagnetic HF field | |
Designation | Electromagnetic RF field |
Standards/regulations | EN 61000-4-3 |
Typical deviation from the measuring range final value | 3 % |
Fast transients (burst) | |
Designation | Fast transients (burst) |
Standards/regulations | EN 61000-4-4 |
Typical deviation from the measuring range final value | 3 % |
Conducted interference | |
Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 |
Typical deviation from the measuring range final value | 3 % |
Electrical isolation | 3-way isolation |
Mounting type | DIN rail mounting |
Item number | 2924838 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Sales Key | C01 |
Product Key | CK1111 |
Catalog Page | Page 121 (C-5-2019) |
GTIN | 4046356572057 |
Weight per Piece (including packing) | 238.2 g |
Weight per Piece (excluding packing) | 153 g |
Customs tariff number | 85437090 |
Country of origin | DE |
ECLASS-9.0 | 27210120 |
ECLASS-10.0.1 | 27210120 |
ECLASS-11.0 | 27210120 |
ETIM 8.0 | EC002653 |
UNSPSC 21.0 | 39121000 |
REACh SVHC | Lead 7439-92-1 |
China RoHS | Environmentally Friendly Use Period = 50 years |
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads” |