TRIO-PS67/1AC/24DC/3.75/M12-A
-
Power supply unit
1376306
Primary-switched power supply unit TRIO POWER, M12 circular connector, Wall mounting, input: 1-phase, output: 24 V DC / 3.75 A
Product details
AC operation | |
Supply system configuration | Star network (TN, TT, IT (PE)) |
Nominal input voltage range | 100 V AC ... 277 V AC |
Input voltage range | 100 V AC ... 277 V AC -15 % ... +10 % |
115 V AC ... 277 V AC ±10 % (UL) | |
Derating | < 100 V AC ... 85 V AC (1 %/V) |
Switch-on voltage | ≥ 80 V AC |
Shut-down voltage | < 75 V AC |
Typical national grid voltage | 120 V AC |
230 V AC | |
Voltage type of supply voltage | AC/DC |
Inrush current | ≤ 35 A (typical) |
Inrush current integral (I2t) | < 0.45 A2s |
AC frequency range | 50 Hz ... 60 Hz ±10 % |
Frequency range (fN) | 50 Hz ... 60 Hz ±10 % |
Mains buffering time | > 25 ms (120 V AC) |
> 25 ms (230 V AC) | |
Current consumption | 1 A (100 V AC) |
0.4 A (277 V AC) | |
Protective circuit | Transient surge protection; Varistor |
Power factor (cos phi) | > 0.92 |
Switch-on time | < 0.2 s |
Input fuse | 4 A (internal (device protection)) |
Recommended breaker for input protection | 6 A ... 16 A (Characteristic B, C, D, K or comparable) |
Discharge current to PE | < 0.5 mA |
DC operation | |
Nominal input voltage range | 110 V DC ... 250 V DC |
Input voltage range | 110 V DC ... 250 V DC -20 % ... +10 % |
120 V DC ... 250 V DC ±10 % (UL) | |
Derating | < 110 V DC ... 88 V DC (1 %/V) |
Switch-on voltage | ≥ 75 V DC |
Shut-down voltage | < 70 V DC |
Voltage type of supply voltage | AC/DC |
Current consumption | 0.88 A (110 V DC) |
0.38 A (250 V DC) |
Efficiency | typ. 93 % (120 V AC) |
typ. 94 % (230 V AC) | |
Nominal output voltage | 24 V DC ±2 % |
Nominal output current (IN) | 3.75 A (Class 2 Output) |
Derating | > 60 °C ... 70 °C (2.0 %/K) |
Feedback voltage resistance | ≤ 35 V DC |
Protection against overvoltage at the output (OVP) | ≤ 35 V DC |
Control deviation | < 1 % (change in load, static 10 % ... 90 %) |
< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz) | |
< 0.1 % (change in input voltage ±10 %) | |
Residual ripple | ≤ 10 mVPP |
Short-circuit-proof | yes |
No-load proof | yes |
Output power | 90 W |
Peak switching voltages nominal load | < 100 mV |
Maximum no-load power dissipation | < 0.25 W (120 V AC) |
< 0.28 W (230 V AC) | |
Power loss nominal load max. | < 7.4 W (120 V AC) |
< 6 W (230 V AC) | |
Rise time | typ. 100 ms (UOUT (10 % ... 90 %)) |
Connection in parallel | yes, for increasing power and redundancy with diode |
Connection in series | yes, for increased output voltage |
Signal: DC OK | |
Continuous load current | 100 mA |
Input | |
Connection method | M12 circular connector |
Coding | S |
Type of locking | M12 screw locking |
Number of positions | 3 |
Output | |
Connection method | M12 circular connector |
Coding | A |
Type of locking | M12 screw locking |
Number of positions | 4 |
Types of signaling | LED |
Status display | 2 x green LEDs |
Signal output: LED status indicator | |
Signalization designation | AC OK |
Status display | LED |
Color | green |
AC OK | ACIn > 0.76 x ACN (ACN = 100 V AC) |
Signal output: LED status indicator | |
Signalization designation | DC OK |
Status display | LED |
Color | green |
DC OK | UOUT > 0.9 x UN (UN = 24 V DC) |
Number of phases | 1.00 |
Insulation voltage input/output | 4 kV AC (type test) |
3 kV AC (routine test) |
Product type | Power supply |
Product family | TRIO POWER |
MTBF (IEC 61709, SN 29500) | > 1475000 h (25 °C) |
> 1000000 h (40 °C) | |
> 500000 h (60 °C) | |
Insulation characteristics | |
Protection class | I |
Degree of pollution | 3 |
Item dimensions | |
Width | 100 mm |
Height | 164 mm |
Depth | 53 mm |
Drill hole | |
Diameter | 4.2 mm |
Installation dimensions | |
Installation distance right/left | 20 mm / 20 mm |
Installation distance top/bottom | 50 mm / 100 mm |
Mounting type | Wall mounting |
Assembly instructions | Alignable: 20 mm horizontally, 50 mm vertically above, 100 mm vertically below |
With protective coating | No |
Flammability rating according to UL 94 (housing / terminal blocks) | V0 |
Housing material | Metal |
Type of housing | Aluminum (AlMg3) |
Ambient conditions | |
Degree of protection | IP67 |
Ambient temperature (operation) | -25 °C ... 70 °C (Derating > 60 °C: 2 %/K) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Maximum altitude | ≤ 4000 m (> 2000 m, Derating: 10 %/1000 m) |
Climatic class | 4K26 (EN 60721-3-4) |
Max. permissible relative humidity (operation) | ≤ 100 % (at 25 °C, non-condensing) |
Permissible humidity (operation) | ≤ 100 % (at 25 °C, non-condensing) |
Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
Vibration (operation) | 10 Hz ... 59.6 Hz, amplitude ±0.35 mm (in accordance with IEC 60068-2-6) |
59.6 Hz ... 150 Hz, 5g, 20 cycles |
Overvoltage category | |
EN 61010-1 | II (≤ 4000 m) |
Overvoltage category | |
EN 62477-1 | III (≤ 2000 m) |
Electrical safety | |
Standard designation | Electrical safety |
Standards/specifications | IEC 61010-1 (SELV) |
Protective extra-low voltage | |
Standard designation | Protective extra-low voltage |
Standards/specifications | IEC 61010-1 (SELV) |
IEC 61010-2-201 (PELV) | |
Low-voltage power supplies, DC output | |
Standard designation | Low-voltage power supplies, DC output |
Standards/specifications | EN 61204-3 |
Safety requirements for electrical equipment for measurement, control, and laboratory use | |
Standard designation | Safety requirements for electrical equipment for measurement, control, and laboratory use |
Standards/specifications | IEC 61010-1 |
Limit values for harmonic currents | |
Standard designation | Limit values for harmonic currents |
Standards/specifications | EN 61000-3-2 |
Degrees of protection provided by enclosures (IP code) | |
Standard designation | Degrees of protection provided by enclosures (IP code) |
Standards/specifications | EN/IEC 60529 |
Mains variation/undervoltage | |
Standard designation | Mains variation/undervoltage |
Standards/specifications | SEMI F47 - 0706 |
UL | |
Identification | NEC Class 2 according to UL 1310 |
UL | |
Identification | UL/C-UL Listed UL 61010-1 |
UL | |
Identification | UL/C-UL Listed UL 61010-2-201 |
Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
Interference emission | Interference emission in accordance with EN 61000-6-3 (residential and commercial) and EN 61000-6-4 (industrial) |
Noise immunity | Immunity in accordance with EN 61000-6-1 (residential), EN 61000-6-2 (industrial) |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Conducted noise emission | EN 55016 |
EN 61000-6-3 (Class B) | |
Noise emission | EN 55011 (EN 55022) |
Noise emission | EN 55016 |
EN 61000-6-3 (Class B) | |
Harmonic currents | |
Standards/regulations | EN 61000-3-2 |
EN 61000-3-2 (Class A) | |
Electrostatic discharge | |
Standards/regulations | EN 61000-4-2 |
Electrostatic discharge | |
Contact discharge | 6 kV (Test Level 3) |
Comments | Criterion A |
Electromagnetic HF field | |
Standards/regulations | EN 61000-4-3 |
Electromagnetic HF field | |
Frequency range | 80 MHz ... 1 GHz |
Test field strength | 10 V/m (Test Level 3) |
Frequency range | 1 GHz ... 2 GHz |
Test field strength | 10 V/m (Test Level 3) |
Frequency range | 2 GHz ... 6 GHz |
Test field strength | 10 V/m (Test Level 3) |
Comments | Criterion A |
Fast transients (burst) | |
Standards/regulations | EN 61000-4-4 |
Fast transients (burst) | |
Input | 4 kV (Test Level 3 - asymmetrical) |
Output | 2 kV (Test Level 3 - asymmetrical) |
Comments | Criterion A |
Surge voltage load (surge) | |
Standards/regulations | EN 61000-4-5 |
Input | 2 kV (Test Level 4 - symmetrical) |
4 kV (Test Level 4 - asymmetrical) | |
Output | 1 kV (Test Level 3 - symmetrical) |
2 kV (Test Level 3 - asymmetrical) | |
Comments | Criterion A |
Conducted interference | |
Standards/regulations | EN 61000-4-6 |
Conducted interference | |
Input/Output | asymmetrical |
Frequency range | 0.15 MHz ... 80 MHz |
Comments | Criterion A |
Voltage | 10 V (Test Level 3) |
Voltage dips | |
Standards/regulations | EN 61000-4-11 |
Voltage | 230 V AC |
Frequency | 50 Hz |
Voltage dip | 70 % |
Number of periods | 25 periods |
Comments | Criterion A |
Voltage dip | 40 % |
Number of periods | 10 periods |
Comments | Criterion B |
Voltage dip | 0 % |
Number of periods | 1 period |
Comments | Criterion A |
Emitted interference | |
Standards/regulations | EN 61000-6-3 |
Radio interference voltage in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential |
Emitted radio interference in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential |
Criteria | |
Criterion A | Normal operating behavior within the specified limits. |
Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
Criterion C | Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements. |
Item number | 1376306 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Sales key | CM08 |
Product key | CMPF13 |
GTIN | 4063151740160 |
Weight per piece (including packing) | 933.6 g |
Weight per piece (excluding packing) | 690 g |
Customs tariff number | 85044095 |
Country of origin | VN |
ECLASS
ECLASS-11.0 | 27040701 |
ECLASS-12.0 | 27040701 |
ECLASS-13.0 | 27040701 |
ETIM
ETIM 9.0 | EC002540 |
UNSPSC
UNSPSC 21.0 | 39121000 |
REACh SVHC | Lead 7439-92-1 |
Compatible products
-
SAC-3P- 1,0-PVC/M12FSS PE - Power cable 1411644
-
SACC-M12FSS-2PEPL-CM SH - Power connector 1080227
-
SACC-M12MS-4PL M - Connector 1424657
-
SACC-M12MS-4PL SH - Connector 1424666
-
SAC-4P-M12MS/ 1,5-PUR - Sensor/actuator cable 1668043
-
SAC-4P-M12MS/ 5,0-PUR - Sensor/actuator cable 1668069
-
SAC-4P-M12MS/10,0-PUR - Sensor/actuator cable 1682993
-
STEP3-DIODE/5-24DC/2X5/1X10/PT - Redundancy module 1283937