FO converters - PSI-MOS-PROFIB/FO 850 E
2708274

FO converter with integrated optical diagnostics, alarm contact, for PROFIBUS up to 12 Mbps, terminal device with one FO interface (BFOC), 850 nm, for PCF/fiberglass cable (multimode)


Product Details


The PSI-MOS-PROFIB/FO... devices convert copper-based PROFIBUS interfaces to fiber optics. The integrated optical diagnostics allow permanent monitoring of the FO paths during installation and also during operation. The floating switch contact is activated when the signal output on the fiber optic paths drops to a critical level. The PSI-MOS-PROFIB/FO... E terminal devices convert a PROFIBUS interface for a FO cable. They are ideal for point-to-point connections.



Utilization restriction
EMC note EMC: class A product, see manufacturer's declaration in the download area
Utilization restriction
CCCex note Use in potentially explosive areas is not permitted in China.

Product type Media converter
MTTF 247 Years (SN 29500 standard, temperature 25°C, operating cycle 21%)
200 Years (SN 29500 standard, temperature 40°C, operating cycle 34.25%)
130 Years (SN 29500 standard, temperature 40°C, operating cycle 100%)
MTBF 252 Years (Telcordia standard, 25°C temperature, 21% operating cycle (5 days a week, 8 hours a day))
42 Years (Telcordia standard, 40°C temperature, 34.25% operating cycle (5 days a week, 12 hours a day))

Electrical isolation VCC // RS-485
Maximum power dissipation for nominal condition 2.88 W
Test voltage data interface/power supply 1.5 kVrms (50 Hz, 1 min.)
Supply
Supply voltage range 18 V DC ... 30 V DC (via pluggable COMBICON screw terminal block)
Nominal supply voltage 24 V DC (in acc. with UL)
Typical current consumption 120 mA (24 V DC)
Max. current consumption 130 mA
≤ 2 A (For operation in a connection station, via the DIN rail connector)
Connection method COMBICON plug-in screw terminal block

Output name Relay output
Output description Alarm output
Number of outputs 1
Maximum switching voltage 60 V DC (Resistive Load, General Load)
30 V AC (Resistive load)
42 V AC (peak, resistive load)
Limiting continuous current 0.46 A

Supply
Connection method COMBICON plug-in screw terminal block
Torque 0.56 Nm ... 0.79 Nm

Bit distortion, input ± 35 % (permitted)
Bit distortion, output < 6.25 %
Bit delay < 1 bit (DIP 7 = OFF, standard operation)
11 bit (DIP 7 = ON, redundancy operation)
Signal PROFIBUS
Data: optical FO
No. of channels 1
Transmit capacity, minimum -4.2 dBm (200/230 µm)
-17.8 dBm (50/125 µm)
-14.6 dBm (62,5/125 µm)
Transmission length incl. 3 dB system reserve 2600 m (with F-G 50/125 2.5 dB/km)
3300 m (with F-G 62,5/125 3.0 dB/km)
800 m (With F-K 200/230 10 dB/km with quick mounting connector)
Transmission protocol Protocol-transparent to the RS-485 interface
Connection method B-FOC (ST®)
Wavelength 850 nm
Minimum receiver sensitivity -30 dBm (50/125 µm)
Maximum receiver sensitivity -3 dBm (200/230 µm)
Transmission medium PCF fiber
Multi-mode fiberglass
Data: PROFIBUS acc. to IEC 61158, RS-485 2-wire, half duplex, automatic control
Serial transmission speed ≤ 12 Mbps
Connection method D-SUB-9 female connector
Transmission length ≤ 1200 m (depending on the data rate, with shielded, twisted pair data cable)
Conductor cross section flexible max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section solid min. 0.2 mm²
Conductor cross section AWG max. 14
Conductor cross section AWG min. 24
Transmission medium Copper
File format/coding UART (11 Bit, NRZ)
Data direction switching Automatic control
Output nominal voltage 5 V ±0.25 (50 mA)

Width 35 mm
Height 99 mm
Depth 106 mm

Color green
Material PA 6.6-FR (Housing)

FO cable
Fiber types 50/125 µm
62.5/125 µm
Fiberglass

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -20 °C ... 60 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Altitude ≤ 5000 m (For restrictions, see the manufacturer's declaration for altitude operation)
≤ 2000 m (Hazardous locations)
Permissible humidity (operation) 30 % ... 95 % (non-condensing)

CE
Certificate CE-compliant
CE
Identification EAC
CE
Identification  II 3 G Ex nA nC IIC T4 Gc X
Note Please follow the special installation instructions in the documentation!
CE
Identification  II (2) G [Ex op is Gb] IIC
 II (2) D [Ex op is Db] IIIC
Certificate PTB 06 ATEX 2042 U
Note Please follow the special installation instructions in the documentation!
CE
Identification Class I, Zone 2, AEx nc IIC T5
Class I, Zone 2, Ex nC nL IIC T5 X
Class I, Div. 2, Groups A, B, C, D
CE
Note Tested by independent PNO test laboratory (PN059-485-01)
CE
Identification IndustrialIT enabled
Note This certification is a trademark of ABB.
CE
Identification ISA-S71.04-1985 G3 Harsh Group A
CE
Identification DNV GL
DNV GL data
Temperature B
Humidity A
Vibration A
EMC B
Enclosure Required protection according to the Rules shall be provided upon installation on board

Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Noise emission EN 55011
Noise immunity EN 61000-6-2:2005
Electrostatic discharge
Standards/regulations EN 61000-4-2
Electrostatic discharge
Contact discharge ± 6 kV
Discharge in air ± 8 kV
Comments Criterion B
Electromagnetic HF field
Standards/regulations EN 61000-4-3
Electromagnetic HF field
Field intensity 10 V/m
Comments Criterion A
Fast transients (burst)
Standards/regulations EN 61000-4-4
Fast transients (burst)
Input ± 2 kV
Signal ± 2 kV
Comments Criterion B
Surge current load (surge)
Standards/regulations EN 61000-4-5
Surge current load (surge)
Input ± 0.5 kV
Signal ± 1 kV
Comments Criterion B
Conducted interference
Standards/regulations EN 61000-4-6
Conducted interference
Comments Criterion A
Voltage 10 V
Emitted interference
Standards/regulations EN 55011
Comments Class A, industrial applications
Criterion A Normal operating behavior within the specified limits.
Criterion B Temporary impairment to operational behavior that is corrected by the device itself.

Free from substances that could impair the application of coating according to P-VW 3.10.7 57 65 0 VW-AUDI-Seat central standard
Air clearances and creepage distances
Standards/regulations DIN EN 60664-1
VDE 0110-1
DIN EN 50178
EN 60950

Mounting type DIN rail mounting

Item number 2708274
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key C19
Product Key DNC211
Catalog Page Page 431 (C-6-2019)
GTIN 4017918973971
Weight per Piece (including packing) 260 g
Weight per Piece (excluding packing) 250 g
Customs tariff number 85176200
Country of origin DE


ECLASS

ECLASS-9.0 19170114
ECLASS-10.0.1 19170132
ECLASS-11.0 19170411

ETIM

ETIM 8.0 EC001467

UNSPSC

UNSPSC 21.0 43201500

cUL Recognized

Approval ID: FILE E 238705

UL Recognized

Approval ID: FILE E 238705

EAC

Approval ID: EAC-Zulassung

DNV GL

Approval ID: TAA00001KR

UL Recognized

Approval ID: FILE E 238705

EAC

Approval ID: EAC-Zulassung

cUL Recognized

Approval ID: FILE E 238705

DNV GL

Approval ID: TAA00001KR

EAC

Approval ID: RU *-DE.A*30.B.01735

EAC

Approval ID: RU *-DE.A*30.B.01735

ATEX

Approval ID: PTB 06 ATEX 2042U

ATEX

Approval ID: PxCIF06ATEX2708261X

cUL Listed

Approval ID: FILE E 199827

UL Listed

Approval ID: FILE E 199827

UL Listed

Approval ID: FILE E 199827

cUL Listed

Approval ID: FILE E 199827

ATEX

Approval ID: PxCIF06ATEX2708261X

ATEX

Approval ID: PTB 06 ATEX 2042U

REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”

Compatible Products



Your advantages

Can be combined with the PSI copper repeater in a modular way using DIN rail connectors
Supply voltage and data signals routed through the DIN rail connectors
Connections can be plugged in via a COMBICON screw terminal block
Automatic data rate detection or fixed data rate setting via DIP switches
Redundant power supply
High-quality electrical isolation between all interfaces (PROFIBUS // fiber optic ports // power supply // DIN rail connector)
Approved for use in zone 2
Integrated optical diagnostics for continuous monitoring of FO paths
Intrinsically safe fiber optic interface (Ex op is) for direct connection to devices in zone 1
Floating switch contact for advance warning of critical FO paths
Suitable for all data rates up to 12 Mbps
Bit retiming for any cascading depth
Shipbuilding approval in accordance with DNV GL