Type 1+2 combined lightning current and surge arrester - FLT-SEC-P-T1-3S-264/50-FM
2909589

Plug-in lightning current arrester, in accordance with Type 1/Class I, for 3-phase power supply networks, with separate N and PE (L1, L2, L3, PE, N).


Product Details




IEC test classification I / II
T1 / T2
EN type T1 / T2
IEC power supply system TN-S
TT
Type DIN rail module, two-section, divisible
Product type Combination type
Number of positions 4
Surge protection fault message Optical, remote indicator contact
Insulation characteristics
Overvoltage category III
Pollution degree 2

Nominal frequency fN 50 Hz (60 Hz)
Indicator/remote signaling
Connection name Remote fault indicator contact
Switching function Changeover contact
Operating voltage 12 V AC ... 250 V AC
125 V DC (200 mA DC)
Operating current 10 mA AC ... 1 A AC
1 A DC (30 V DC)

Connection method Screw connection
Screw thread M5
Tightening torque 4.5 Nm
Stripping length 18 mm
Conductor cross section flexible 2.5 mm² ... 35 mm²
Conductor cross section solid 2.5 mm² ... 35 mm²
Conductor cross section AWG 13 ... 2
Connection method Fork-type cable lug
Conductor cross section flexible 1.5 mm² ... 16 mm²
Remote fault indicator contact
Connection method Plug-in/screw connection via COMBICON
Screw thread M2
Tightening torque 0.25 Nm
Conductor cross section flexible 0.14 mm² ... 1.5 mm²
Conductor cross section solid 0.14 mm² ... 1.5 mm²
Conductor cross section AWG 28 ... 16

Dimensional drawing
Width 142.4 mm
Height 95.2 mm
Depth 74.5 mm
Horizontal pitch 8 Div.

Color light grey RAL 7035
traffic grey A RAL 7042
Flammability rating according to UL 94 V-0
CTI value of material 600
Insulating material PA6.6-FR 20% GF
PBT-FR
Material group I
Housing material PA 6.6-FR 20 % GF
PBT-FR

Mechanical data
Open side panel No

Mode of protection L-N
L-PE
N-PE
Direction of action 3L-N & N-PE
Nominal voltage UN 240/415 V AC (TN-S)
240/415 V AC (TT)
Nominal frequency fN 50 Hz (60 Hz)
Maximum continuous operating voltage UC (L-N) 264 V AC
Maximum continuous operating voltage UC (L-PE) 264 V AC
Maximum continuous operating voltage UC (N-PE) 350 V AC
Rated load current IL 125 A (< 55 °C)
Residual current IPE ≤ 0.01 mA
Nominal discharge current In (8/20) µs (L-N) 50 kA
Nominal discharge current In (8/20) µs (L-PE) 50 kA
Nominal discharge current In (8/20) µs (N-PE) 100 kA
Maximum discharge current Imax (8/20) µs 100 kA
Impulse discharge current (10/350) µs (L-N), charge 25 As
Impulse discharge current (10/350) µs (L-N), specific energy 625 kJ/Ω
Impulse discharge current (10/350) µs (L-N), peak current value Iimp 50 kA
Impulse discharge current (10/350) µs (L-PE), charge 25 As
Impulse discharge current (10/350) µs (L-PE), specific energy 625 kJ/Ω
Impulse discharge current (10/350) µs (L-PE), peak current value Iimp 50 kA
Impulse discharge current (10/350) µs (N-PE), charge 50 As
Impulse discharge current (10/350) µs (N-PE), specific energy 2500 kJ/Ω
Impulse discharge current (10/350) µs (N-PE), peak current value Iimp 100 kA
Total discharge current Itotal (10/350) µs 100 kA
Follow current quenching capacity Ifi (L-N) 50 kA
Follow current interrupt rating Ifi (N-PE) 100 A
Short-circuit current rating ISCCR 50 kA
Voltage protection level Up (L-N) ≤ 2.5 kV
Voltage protection level Up (L-PE) ≤ 3 kV
Voltage protection level Up (N-PE) ≤ 1.5 kV
Residual voltage Ures (L-N) ≤ 2.5 kV (at In)
Residual voltage Ures (L-PE) ≤ 3 kV (at In)
Residual voltage Ures (N-PE) ≤ 1.5 kV (at In)
TOV behavior at UT (L-N) 415 V AC (5 s / withstand mode)
760 V AC (120 min / withstand mode)
TOV behavior at UT (N-PE) 1200 V AC (200 ms / withstand mode)
Response time tA ≤ 100 ns
Max. backup fuse with V-type through wiring 125 A (gG)
Max. backup fuse with branch wiring 500 A (gG)

Ambient conditions
Degree of protection IP20 (only when all terminal points are used)
Ambient temperature (operation) -40 °C ... 80 °C
Ambient temperature (storage/transport) -40 °C ... 80 °C
Altitude ≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation) 5 % ... 95 %
Shock (operation) 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation) 5g (5 - 500 Hz/2.5 h/X, Y, Z)

UL specifications
Maximum continuous operating voltage MCOV (L-L) 528 V AC
Maximum continuous operating voltage MCOV (L-N) 264 V AC
Maximum continuous operating voltage MCOV (L-G) 264 V AC
Maximum continuous operating voltage MCOV (N-G) 350 V AC
Short-circuit current rating (SCCR) 50 kA
Voltage protection rating VPR (L-L) 2500 V
Voltage protection rating VPR (L-N) 1500 V
Voltage protection rating VPR (L-G) 1800 V
Voltage protection rating VPR (N-G) 1200 V
Mode of protection L-L
L-N
L-G
N-G
Nominal voltage 240/415 V AC
Rated load current IL 50 A
Power distribution system Wye
Nominal frequency 50/60 Hz
SPD Type 2CA
AC operating voltage 125 V AC
AC operating current 1 A AC
UL connection data
Tightening torque 40 lbf-in.
Conductor cross section AWG 3 ... 2

Standards/specifications IEC 61643-11
Standards/specifications EN 61643-11

Mounting type DIN rail: 35 mm

Item number 2909589
Packing unit 1 pc
Minimum order quantity 1 pc
Product Key CL1173
Catalog Page Page 40 (C-4-2019)
GTIN 4055626368795
Weight per Piece (including packing) 1,575 g
Weight per Piece (excluding packing) 1,397 g
Country of origin DE


ECLASS

ECLASS-9.0 27130802
ECLASS-10.0.1 27130802
ECLASS-11.0 27130802

ETIM

ETIM 8.0 EC000381

UNSPSC

UNSPSC 21.0 39121600

cUL Recognized

Approval ID: FILE E 330181

UL Recognized

Approval ID: FILE E 330181

EAC

Approval ID: RU C-DE.*09.B.00169

cULus Recognized


REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”