Power supply unit - TRIO-PS/1AC/24DC/10
2866323

Primary-switched TRIO POWER power supply for DIN rail mounting, input: 1-phase, output: 24 V DC/10 A


Product Details


TRIO POWER power supplies with standard functionality
TRIO POWER is particularly suited to standard machine production, thanks to 1- and 3-phase versions up to 960 W. The wide-range input and the international approval package enable worldwide use.
The robust metal housing, the high electric strength, and the wide temperature range ensure a high level of power supply reliability.



AC operation
Nominal input voltage range 100 V AC ... 240 V AC
Input voltage range 85 V AC ... 264 V AC (Derating < 90 V AC: 2,5 %/V)
Derating < 90 V AC (2.5 %/V)
Input voltage range AC 85 V AC ... 264 V AC (Derating < 90 V AC: 2,5 %/V)
Electric strength, max. 300 V AC
Voltage type of supply voltage AC
Inrush current < 15 A
Inrush current integral (I2t) 0.7 A2s
AC frequency range 45 Hz ... 65 Hz
Mains buffering time > 24 ms (120 V AC)
> 24 ms (230 V AC)
Current consumption 3 A (100 V AC)
1.5 A (240 V AC)
Nominal power consumption 272 VA
Protective circuit Transient surge protection; Varistor
Power factor (cos phi) 0.99
Typical response time < 1 s
Input fuse 6.3 A (slow-blow, internal)
Permissible backup fuse B10 B16
Recommended breaker for input protection 10 A ... 16 A (Characteristics B, C, D, K)
Discharge current to PE < 3.5 mA

Efficiency 89 % (for 230 V AC and nominal values)
Output characteristic U/I
Nominal output voltage 24 V DC ±1 %
Setting range of the output voltage (USet) 22.5 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN) 10 A (UOUT = 24 V DC)
Derating 55 °C ... 70 °C (2.5%/K)
Feedback voltage resistance 35 V DC
Protection against overvoltage at the output (OVP) < 35 V DC
Max. capacitive load unlimited
Active current limitation Approx. 14 A (for short-circuit)
Control deviation < 1 % (change in load, static 10 % ... 90 %)
< 2 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %)
Residual ripple < 10 mVPP
Output power 240 W
Peak switching voltages nominal load < 50 mVPP
Maximum power dissipation in no-load condition 6.7 W
Power loss nominal load max. 30 W
Rise time < 2 ms (UOUT (10 % ... 90 %))
Connection in parallel yes, for redundancy and increased capacity
Connection in series yes

Input
Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Stripping length 9 mm
Screw thread M2,5
Tightening torque, min 0.4 Nm
Tightening torque max 0.5 Nm
Output
Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Stripping length 9 mm
Screw thread M2,5
Tightening torque, min 0.4 Nm
Tightening torque max 0.5 Nm

Types of signaling LED
Operating voltage display Green LED
Signal output
Status display "DC OK" LED green
Note on status display UOUT < 0.9 x UN: LED flashing

Insulation voltage input/output 4 kV AC (type test)
2 kV AC (routine test)
Insulation voltage output / PE 500 V DC (type test)
Insulation voltage input / PE 2 kV AC (type test)
2 kV AC (routine test)

MTBF (IEC 61709, SN 29500) > 981000 h (40 °C)
Insulation characteristics
Protection class I (with PE connection)
Overvoltage category III
Degree of pollution 2

Dimensional drawing
Width 60 mm
Height 130 mm
Depth 152.5 mm
Installation dimensions
Installation distance right/left 0 mm / 0 mm
Installation distance top/bottom 50 mm / 50 mm

Mounting type DIN rail mounting
Assembly instructions alignable: horizontally 0 mm, vertically 50 mm
Mounting position horizontal DIN rail NS 35, EN 60715

Color aluminium
Type of housing Steel sheet, zinc-plated
Side element version Aluminum

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C ... 70 °C (> 55° C derating : 2.5%/K)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Climatic class 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min.

Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)
Standard – Limitation of mains harmonic currents EN 61000-3-2
Standard - Electrical safety EN 60950-1/VDE 0805 (SELV)
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment EN 50178
Standard – Safety extra-low voltage EN 60950-1 (SELV)
EN 60204 (PELV)
Standard - Safe isolation DIN VDE 0100-410

UL approvals UL/C-UL listed UL 508
UL/C-UL Recognized UL 60950-1
Conformity/Approvals
SIL in accordance with IEC 61508 0

Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
EMC requirements for noise emission EN 61000-6-3
EN 61000-6-4
EMC requirements for noise immunity EN 61000-6-1
EN 61000-6-2
Noise immunity EN 61000-6-2:2005
Electrostatic discharge
Standards/regulations EN 61000-4-2
Electrostatic discharge
Contact discharge 6 kV (Test Level 3)
Discharge in air 8 kV (Test Level 3)
Comments Criterion A
Electromagnetic HF field
Standards/regulations EN 61000-4-3
Electromagnetic HF field
Frequency range 80 MHz ... 1 GHz
Test field strength 10 V/m
Frequency range 1 GHz ... 2 GHz
Test field strength 10 V/m
Frequency range 2 GHz ... 3 GHz
Test field strength 10 V/m
Comments Criterion A
Fast transients (burst)
Standards/regulations EN 61000-4-4
Fast transients (burst)
Input 4 kV (Test Level 4 - asymmetrical)
Output 4 kV (Test Level 4 - asymmetrical)
Signal 2 kV (Test Level 3 - asymmetrical)
Comments Criterion A
Surge voltage load (surge)
Standards/regulations EN 61000-4-5
Input 2 kV (Test Level 3 - symmetrical)
4 kV (Test Level 4 - asymmetrical)
Output 1 kV (Test Level 2 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Comments Criterion A
Conducted interference
Standards/regulations EN 61000-4-6
Conducted interference
Frequency range 0.15 MHz ... 80 MHz
Comments Criterion A
Voltage 10 V (Test Level 3)
Conducted interference
Frequency range 0.15 MHz ... 80 MHz
Comments Criterion A
Voltage 10 V (Test Level 3)
Voltage dips
Standards/regulations EN 61000-4-11
Emitted interference
Standards/regulations EN 61000-6-3
Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential

Order Key 2866323
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key 0904*
Product Key CMPT13
Catalog Page Page 175 (C-6-2013)
GTIN 4046356046657
Weight per Piece (including packing) 1,554 g
Weight per Piece (excluding packing) 1,400 g
Customs tariff number 85044030
Country of origin CN


ECLASS

ECLASS-9.0 27040701
ECLASS-10.0.1 27040701
ECLASS-11.0 27040701

ETIM

ETIM 6.0 EC002540

UNSPSC

UNSPSC 19.0 39121004
UNSPSC 20.0 39121004
UNSPSC 21.0 39121004

cUL Recognized

UL Recognized

EAC

EAC

UL Listed

cUL Listed

EAC

cULus Recognized

cULus Listed


REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 25;
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Your advantages

Use the third negative terminal block as a grounding terminal block and minimize installation costs
Rugged design with metal housing and wide temperature range from -25 to +70°C
Maximum operational reliability thanks to high MTBF (mean time between failures) of more than 500,000 hours and high dielectric strength of up to 300 V AC
Compensation of voltage drops by means of output voltage that can be adjusted on the front