Power supply unit - QUINT-PS-100-240AC/24DC/ 5
2938581

DIN rail power supply unit 24 V DC/5 A, primary-switched, 1-phase.
Please use the following item in new systems: 2904600


Product Details


QUINT POWER power supply units for plant and special engineering reliably start heavy loads with high inrush currents using the POWER BOOST. Thanks to the wide-range input and extensive package of approvals, they can be used in all sectors of industry the world over. The switching output or floating relay contact are used for remote diagnostics.



AC operation
Nominal input voltage range 100 V AC ... 240 V AC
Input voltage range 85 V AC ... 264 V AC
90 V DC ... 350 V DC
Input voltage range AC 85 V AC ... 264 V AC
Input voltage range DC 90 V DC ... 350 V DC
Voltage type of supply voltage AC/DC
Inrush current < 20 A (typical)
Inrush current integral (I2t) < 2.5 A2s
AC frequency range 45 Hz ... 65 Hz
Frequency range DC 0 Hz
Mains buffering time > 30 ms (120 V AC)
> 130 ms (230 V AC)
Current consumption approx. 1.6 A (120 V AC)
approx. 0.84 A (230 V AC)
Nominal power consumption 134 W
Protective circuit Transient surge protection; Varistor
Typical response time < 1 s
Input fuse 5 A (slow-blow, internal)
Permissible backup fuse B6 B10 B16
Permissible DC backup fuse DC: Connect a suitable fuse upstream
Recommended breaker for input protection 6 A ... 16 A (Characteristics B, C, D, K)

Efficiency > 89 %
Nominal output voltage 24 V DC ±1 %
Setting range of the output voltage (USet) 22.5 V DC ... 28.5 V DC
Nominal output current (IN) 5 A (up to 60 °C)
POWER BOOST (IBoost) 7.5 A
Derating 60 °C ... 70 °C (2.5%/K)
Feedback voltage resistance 35 V DC
Protection against overvoltage at the output (OVP) ≤ 35 V DC
Max. capacitive load unlimited
Active current limitation Approx. IBOOST = 7.5 A (for short-circuit)
Control deviation < 1 % (change in load, static 10 % ... 90 %)
< 2 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %)
Residual ripple < 10 mVPP (with nominal values)
Output power 120 W
Peak switching voltages nominal load < 30 mVPP (20 MHz)
Maximum no-load power dissipation < 2 W
Power loss nominal load max. < 14 W
Rise time < 2 ms (UOUT (10 % ... 90 %))
Connection in parallel yes, for redundancy and increased capacity
Connection in series yes
Signal: DC OK active
Output description UOUT > 0.9 x UN: High signal
Maximum switching voltage ≤ 24 V
Output voltage + 24 V DC (Signal)
Maximum inrush current ≤ 40 mA
Continuous load current ≤ 40 mA
Signal: DC OK floating
Output description Relay contact, UOUT > 0.9 x UN: Contact closed
Maximum switching voltage ≤ 30 V AC/DC
Maximum inrush current ≤ 1 A
Continuous load current ≤ 1 A
Signal: DC OK active
Output description UOUT > 0.9 x UN: High signal
Maximum switching voltage ≤ 24 V
Output voltage + 24 V DC (Signal)
Maximum inrush current ≤ 40 mA
Continuous load current ≤ 40 mA
Signal: DC OK floating
Output description Relay contact, UOUT > 0.9 x UN: Contact closed
Maximum switching voltage ≤ 30 V AC/DC
Maximum inrush current ≤ 1 A
Continuous load current ≤ 1 A

Input
Connection method Pluggable screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Stripping length 7 mm
Screw thread M3
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm
Output
Connection method Pluggable screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Stripping length 7 mm
Screw thread M3
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm
Signal
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Screw thread M3
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm

Types of signaling LED
Active switching output
Relay contact
Operating voltage display Green LED
Signal output: DC OK active
Status display "DC OK" LED green
Note on status display UOUT < 0.9 x UN: LED flashing
Signal output: DC OK floating
Status display "DC OK" LED green

Insulation voltage input/output 4 kV AC (type test)
2 kV AC (routine test)
Insulation voltage output / PE 500 V DC (routine test)
Insulation voltage input / PE 3.5 kV AC (type test)
2 kV AC (routine test)

Product type Power supply
MTBF (IEC 61709, SN 29500) > 500000 h
Insulation characteristics
Protection class I (with PE connection)
Degree of pollution 2

Width 55 mm
Height 130 mm
Depth 125 mm
Alternative assembly
Width 122 mm
Height 130 mm
Depth 58 mm

Assembly instructions alignable: horizontally 0 mm, vertically 50 mm
Mounting position horizontal DIN rail NS 35, EN 60715

Color aluminium
Housing material Metal
Type of housing AluNox (AlMg1)

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) 95 % (at 25 °C, non-condensing)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min.

Standard – Limitation of mains harmonic currents EN 61000-3-2
Standard - Electrical safety EN 62368-1
Standard - Equipment safety GS (tested safety)
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment EN 62368-1
Standard – Safety extra-low voltage EN 62368-1 (SELV)
EN 60204 (PELV)
Standard - Safe isolation DIN VDE 0100-410
Overvoltage category
EN 62477-1 III

Shipbuilding approval DNV GL (EMC A)
UL approvals UL/C-UL Recognized UL 60950-1
UL/C-UL listed UL 508
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)

Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
EMC requirements for noise emission EN 61000-6-3
EN 61000-6-4
EMC requirements for noise immunity EN 61000-6-1
EN 61000-6-2
Noise emission EN 55011 (EN 55022)
Noise immunity EN 61000-6-2
Electrostatic discharge
Standards/regulations EN 61000-4-2
Housing Level 4
Electrostatic discharge
Contact discharge 8 kV
Discharge in air 15 kV
Comments Criterion B
Electromagnetic HF field
Standards/regulations EN 61000-4-3
Electromagnetic HF field
Frequency range 80 MHz ... 2 GHz
Test field strength 10 V/m
Comments Criterion A
Fast transients (burst)
Standards/regulations EN 61000-4-4
Fast transients (burst)
Input 4 kV (level 4 - asymmetrical)
Output 2 kV (Level 3 - asymmetrical)
Signal 1 kV (Level 2 - asymmetrical)
Surge voltage load (surge)
Standards/regulations EN 61000-4-5
Conducted interference
Standards/regulations EN 61000-4-6
Conducted interference
I/O/S Level 3 - asymmetrical
Frequency range 0.15 MHz ... 80 MHz
Comments Criterion A
Voltage 10 V
Voltage dips
Standards/regulations EN 61000-4-11
Emitted interference
Standards/regulations EN 61000-6-3
Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential

Item number 2938581
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key 0904*
Product Key CMPP13
Catalog Page Page 480 (IF-2007)
GTIN 4017918890520
Weight per Piece (including packing) 1,172.6 g
Weight per Piece (excluding packing) 830 g
Customs tariff number 85044030
Country of origin TH


ECLASS

ECLASS-9.0 27040701
ECLASS-10.0.1 27040701
ECLASS-11.0 27040701

ETIM

ETIM 8.0 EC002540

UNSPSC

UNSPSC 21.0 39121000

IECEE CB Scheme

EAC

DNV GL

Approval Specification Data
Nominal Voltage UN Nominal Current IN Cross Section AWG Cross Section mm2

cUL Listed

UL Listed

cULus Listed


REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 25;
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”