VAL-SPP-T2-385-1+0-UT-R
   - 
  Type 2 surge arrester
    
      1466606
      
      
    
  
      Plug-in surge protective device, in accordance with type 2/class II, for 1-phase power supply networks with combined installation of PE and N in one conductor (2-conductor system: L, N/PEN), with remote indication contact.
Product details
| General | |
| Note | For pollution degree 3 and wiring with fork cable lugs, an additional minimum lateral distance of 1 mm to earthed conductive surfaces must be maintained for cross-sections ≥ 16 mm². No additional lateral distances are required for pollution degree 2.  | 
            
| Product type | Surge arrester | 
| Product family | VAL-SPP | 
| IEC test classification | II | 
| T2 | |
| EN type | T2 | 
| IEC power supply system | TN | 
| TT | |
| Type | DIN rail module, two-section, divisible | 
| Number of positions | 1 | 
| Surge protection fault message | Optical, remote indicator contact | 
| Insulation characteristics | |
| Overvoltage category | III | 
| Pollution degree | 3 | 
| Maximum power dissipation for nominal condition | ≤ 175 mVA | 
| Nominal frequency fN | 50 Hz (60 Hz) | 
| Indicator/remote signaling | |
| Connection name | Remote fault indicator contact | 
| Switching function | Changeover contact | 
| Max. required back-up fuse | 1 A (gG) | 
| AC operating voltage | 5 V AC ... 250 V AC (≤ 2000 m (amsl) at pollution degree 2) | 
| 5 V AC ... 150 V AC (≤ 5000 m (amsl)) | |
| AC operating current | 5 mA AC ... 1 A AC | 
| DC operating voltage | 30 V DC (≤ 5000 m (amsl)) | 
| DC operating current | 1 A DC | 
| DC operating voltage | 125 V DC (≤ 5000 m (amsl)) | 
| DC operating current | 200 mA DC | 
| Insulation type | The product has double/reinforced insulation between the main and auxiliary circuit. | 
| Connection method | Screw connection | 
| Screw thread | M5 | 
| Tightening torque | 3 Nm ... 3.5 Nm | 
| Stripping length | 18 mm | 
| Conductor cross-section flexible | 1.5 mm² ... 35 mm² (without ferrule) | 
| 2x 1.5 mm² ... 16 mm² (2 conductors with the same cross-section) | |
| Conductor cross-section rigid | 1.5 mm² ... 50 mm² | 
| 2x 1.5 mm² ... 16 mm² (2 conductors with the same cross-section) | |
| Conductor cross-section AWG | 15 ... 2 | 
| 2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve | 1.5 mm² ... 16 mm² | 
| Conductor cross-section, flexible, with ferrule, with plastic sleeve | 1.5 mm² ... 35 mm² | 
| 2x 1.5 mm² ... 10 mm² (2 conductors with the same cross-section) | |
| Conductor cross-section flexible, with ferrule without plastic sleeve | 1.5 mm² ... 25 mm² | 
| 2x 1.5 mm² ... 16 mm² (2 conductors with the same cross-section) | |
| Connection method | Fork-type cable lug | 
| Conductor cross-section flexible | 1.5 mm² ... 25 mm² | 
| Remote fault indicator contact | |
| Connection method | Push-in connection | 
| Stripping length | 8 mm | 
| Conductor cross-section flexible | 0.25 mm² ... 1.5 mm² | 
| Conductor cross-section rigid | 0.25 mm² ... 1.5 mm² | 
| Conductor cross-section AWG | 24 ... 16 | 
| Conductor cross-section, flexible, with ferrule, with plastic sleeve | 0.25 mm² ... 1.5 mm² | 
| Conductor cross-section flexible, with ferrule without plastic sleeve | 0.25 mm² ... 0.75 mm² | 
| Dimensional drawing | 
                 | 
            
| Width | 17.8 mm | 
| Height | 110.8 mm | 
| Depth | 71.5 mm (incl. DIN rail 7.5 mm) | 
| Horizontal pitch | 1 Div. | 
| Color | gray (RAL 7042) | 
| light gray (RAL 7035) | |
| Flammability rating according to UL 94 | V-0 | 
| CTI value of material | 600 | 
| Insulating material | PA 6.6-FR 20 % GF | 
| PBT | |
| Material group | I | 
| Housing material | PA 6.6-FR 20 % GF | 
| PBT | 
| Mode of protection | L-N | 
| L-PEN | |
| Nominal voltage UN | 240 V AC ±10 % (TN) | 
| 240 V AC ±10 % (TT) | |
| Nominal frequency fN | 50 Hz (60 Hz) | 
| Maximum continuous operating voltage UC | 385 V AC | 
| Rated load current IL | 80 A (25 mm²) | 
| Nominal discharge current In (8/20) µs | 20 kA | 
| Maximum discharge current Imax (8/20) µs | 40 kA | 
| Short-circuit current rating ISCCR | 50 kA | 
| Voltage protection level Up | ≤ 1.8 kV | 
| Residual voltage Ures | ≤ 1.8 kV (at In) | 
| ≤ 1.6 kV (at 10 kA) | |
| ≤ 1.4 kV (at 5 kA) | |
| ≤ 1.3 kV (at 3 kA) | |
| TOV behavior at UT | 415 V AC (5 s / withstand mode) | 
| 460 V AC (120 min / safe failure mode) | |
| Response time tA | ≤ 25 ns | 
| Max. backup fuse with V-type through wiring | 80 A (gG) | 
| Max. backup fuse with branch wiring | 315 A (gG) | 
| Additional technical data | |
| Short-circuit current rating ISCCR | 100 kA | 
| Ambient conditions | |
| Degree of protection | IP20C (Installed) | 
| Ambient temperature (operation) | -40 °C ... 85 °C | 
| Ambient temperature (storage/transport) | -40 °C ... 85 °C | 
| Ambient temperature (assembly) | -5 °C ... 50 °C | 
| Altitude | ≤ 5000 m (amsl) | 
| Permissible humidity (operation) | 5 % ... 95 % | 
| Shock (operation) | 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) | 
| Vibration (operation) | 5g (10 ... 500 Hz / 2.5 h / X, Y, Z) | 
| Standards/specifications | IEC 61643-11 | 
| Note | 2011 | 
| Standards/specifications | EN 61643-11 | 
| Note | 2012 + A11:2018 | 
| Mounting type | DIN rail: 35 mm | 
| Item number | 1466606 | 
| Packing unit | 1 pc | 
| Minimum order quantity | 1 pc | 
| Sales key | 31BCL | 
| Product key | CL1381 | 
| GTIN | 4063151860837 | 
| Weight per piece (including packing) | 156.9 g | 
| Weight per piece (excluding packing) | 133.5 g | 
| Customs tariff number | 85366930 | 
| Country of origin | DE | 
ECLASS
| ECLASS-13.0 | 27171202 | 
| ECLASS-15.0 | 27171202 | 
ETIM
| ETIM 9.0 | EC000941 | 
UNSPSC
| UNSPSC 21.0 | 39121600 | 
| EU RoHS | |
| Fulfills EU RoHS substance requirements | Yes (No exemptions) | 
| China RoHS | |
| Environment friendly use period (EFUP) | 
              EFUP-E
               No hazardous substances above the limits 
             | 
          
| EU REACH SVHC | |
| REACH candidate substance (CAS No.) | No substance above 0.1 wt% | 
Compatible products
Your advantages
Easy and safe installation with forward-thinking handling and safety features
        Reliable system protection with maximum performance and endurance
        Can be used in a wide range of applications due to the optimized design and broad portfolio
        Simple planning due to comprehensive digital data and selectors
        PHOENIX CONTACT AS
        
        Strømsveien 344; N-1081 Oslo