MACX MCR-EX-TC-I-C
   - 
  Temperature measuring transducer
    
      1052458
      
      
    
  
      Ex i temperature transducer: converts signals from thermocouples installed in Ex areas and mV sources and transmits a 0/4…20 mA signal to a load in the safe area. Order configuration, freely programmable. 3-way isolation, SIL.
      Free download available.
      Downloads
    
  Product details
| Utilization restriction | |
| EMC note | EMC: class A product, see manufacturer's declaration in the download area | 
| Product type | Temperature transmitter | 
| Product family | MACX Analog | 
| Application | Temperature | 
| No. of channels | 1 | 
| Configuration | Software | 
| Functionality | |
| Configuration | Software | 
| Electrical isolation | 3-way isolation | 
| Electrical isolation between input and output | yes | 
| Cold point error, max. | ± 2 K | 
| Step response (0–99%) | ≤ 1.7 s | 
| Temperature coefficient, typical | 0.01 %/K | 
| Transmission error, typical | 0.1 % (For full identification of transmission errors, see the data sheet) | 
| Electrical isolation | |
| Test voltage | 2.5 kV AC (50 Hz, 60 s) | 
| Overvoltage category | II | 
| Pollution degree | 2 | 
| Electrical isolation Input/output/power supply IEC/EN 61010-1 | |
| Standards/regulations | IEC/EN 61010-1 | 
| Rated insulation voltage | 300 Vrms | 
| Insulation | Safe isolation | 
| Electrical isolation Input/output IEC/EN 60079-11 | |
| Standards/regulations | IEC/EN 60079-11 | 
| Rated insulation voltage | 375 VPP | 
| Electrical isolation Input/power supply IEC/EN 60079-11 | |
| Standards/regulations | IEC/EN 60079-11 | 
| Rated insulation voltage | 375 VPP | 
| Supply | |
| Nominal supply voltage | 24 V DC -20 % ... +25 % | 
| Supply voltage range | 19.2 V DC ... 30 V DC | 
| Max. current consumption | < 40 mA (24 V DC) | 
| Power dissipation | ≤ 0.76 W | 
| Power consumption | ≤ 1 W | 
| Signal | |
| Number of inputs | 1 | 
| Input signal | Temperature | 
| Voltage | |
| Measurement | |
| Description of the input | intrinsically safe | 
| Sensor types that can be used (TC) | B, E, J, K, N, R, S, T, L, U, C, D, A-1, A-2, A-3, M, Lr | 
| Temperature measuring range | -250 °C ... 2500 °C (Range depending on the sensor type) | 
| Temperature measuring range: Thermoelement Typ B | 500 °C ... 1820 °C | 
| Temperature measuring range: Thermoelement Typ E | -230 °C ... 1000 °C | 
| Temperature measuring range: Thermoelement Typ J | -210 °C ... 1200 °C | 
| Temperature measuring range: Thermoelement Typ K | -250 °C ... 1372 °C | 
| Temperature measuring range: Thermoelement Typ N | -200 °C ... 1300 °C | 
| Temperature measuring range: Thermoelement Typ R | -50 °C ... 1768 °C | 
| Temperature measuring range: Thermoelement Typ S | -50 °C ... 1768 °C | 
| Temperature measuring range: Thermoelement Typ T | -200 °C ... 400 °C | 
| Temperature measuring range: Thermoelement Typ L | -200 °C ... 900 °C | 
| Temperature measuring range: Thermoelement Typ U | -200 °C ... 600 °C | 
| Temperature measuring range: Thermoelement Typ C | 0 °C ... 2315 °C | 
| Temperature measuring range: Thermoelement Typ D | 0 °C ... 2315 °C | 
| Temperature measuring range: Thermoelement Typ A1 GOST | 0 °C ... 2500 °C | 
| Temperature measuring range: Thermoelement Typ A2 GOST | 0 °C ... 1800 °C | 
| Temperature measuring range: Thermoelement Typ A3 GOST | 0 °C ... 1800 °C | 
| Temperature measuring range: Thermoelement Typ M GOST | -200 °C ... 100 °C | 
| Temperature measuring range: Thermoelement Typ L GOST | -200 °C ... 800 °C | 
| Linear mV signal range | -1000 mV ... 1000 mV | 
| Temperature measuring range | Min. 50 K with thermocouple, 10% of the nominal span of the respective range with mV sources | 
| Signal: Current | |
| Number of outputs | 1 | 
| Configurable/programmable | Yes | 
| Current output signal | 0 mA ... 20 mA | 
| 4 mA ... 20 mA (SIL) | |
| Load/output load current output | ≤ 600 Ω | 
| Output ripple (current) | < 15 µAPP | 
| < 10 µArms | |
| Behavior in the event of a sensor error | Freely definable | 
| Connection method | Screw connection | 
| Stripping length | 7 mm | 
| Screw thread | M3 | 
| Conductor cross-section rigid | 0.2 mm² ... 2.5 mm² | 
| Conductor cross-section flexible | 0.2 mm² ... 2.5 mm² | 
| Conductor cross-section AWG | 24 ... 14 | 
| Tightening torque | 0.5 Nm ... 0.6 Nm | 
| Test socket | |
| Max. diameter | 2 mm | 
| Ex installation (EPL) | Gc | 
| Div. 2 | |
| Ex i circuits (EPL) | Ga | 
| Da | |
| Ma | |
| Div. 1 | |
| Safety data: Terminals: 4.1, 4.2, 5.1, 5.2 | |
| Max. internal capacitance Ci | 44 nF | 
| Max. output voltage Uo | 6 V | 
| Max. output current Io | 4.3 mA (mV) | 
| 7.1 mA (TC with internal cold junction compensation) | |
| 16.8 mA (TC with external cold junction, TC and cold junction connected) | |
| Max. output power Po | 25.2 mW (Linear) | 
| Safety-related maximum voltage Um | 253 V AC | 
| 125 V DC | |
| 30 V DC (Zone 2: 3.1, 3.2) | |
| IIA/I (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 850 mH / 1000 µF | 
| IIB/IIIC (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 460 mH / 1000 µF | 
| IIC (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 100 mH / 40 µF | 
| IIB/IIA (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co | 100 mH / 950 nF | 
| IIIC/I (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co | 100 mH / 950 nF | 
| IIC (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co | 100 mH / 555 nF | 
| Status display | Green LED (supply voltage) | 
| Red LED, flashing 2.8 Hz (cable error, sensor error on input or output, ERR) | |
| Red LED, flashing 1.2 Hz (simulation mode, ERR) | |
| Red LED, permanently on (module error, ERR) | 
| Dimensional drawing |  | 
| Width | 12.5 mm | 
| Height | 112.5 mm | 
| Depth | 113.7 mm | 
| Depth NS 35/7,5 | 114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715) | 
| Color | gray (RAL 7042) | 
| Flammability rating according to UL 94 (Housing) | V0 (Housing) | 
| Housing material | PA 6.6-FR | 
| Ambient conditions | |
| Degree of protection | IP20 | 
| Ambient temperature (operation) | -40 °C ... 70 °C (Any mounting position) | 
| Ambient temperature (storage/transport) | -40 °C ... 80 °C | 
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) | 
| Altitude range (≤ 2000 m) | |
| Altitude | ≤ 2000 m (The technical data refers to altitudes ≤2000 m above mean sea level. For altitudes >2000 m above mean sea level, refer to the data sheet.) | 
| Ambient temperature (operation) | -40 °C ... 70 °C | 
| Test voltage | 2.5 kV | 
| Rated insulation voltage | 300 Vrms (IEC/EN 60079-11) | 
| 375 VPP (IEC/EN 60079-11) | |
| Altitude range (≤ 3000 m) | |
| Height range | > 2000 m ... 3000 m | 
| Ambient temperature (operation) | -40 °C ... 60 °C | 
| Test voltage | 2.25 kV | 
| Safety-related maximum voltage Um | 190 V AC | 
| 110 V DC | |
| Rated insulation voltage | 190 Vrms (IEC/EN 60079-11) | 
| Altitude range (≤ 4000 m) | |
| Height range | > 3000 m ... 4000 m | 
| Ambient temperature (operation) | -40 °C ... 55 °C | 
| Test voltage | 2 kV | 
| Safety-related maximum voltage Um | 60 V AC/DC | 
| Rated insulation voltage | 60 Vrms (IEC/EN 60079-11) | 
| Altitude range (≤ 5000 m) | |
| Height range | > 4000 m ... 5000 m | 
| Ambient temperature (operation) | -40 °C ... 49 °C | 
| Test voltage | 1.75 kV | 
| Safety-related maximum voltage Um | 60 V AC/DC | 
| Rated insulation voltage | 60 Vrms (IEC/EN 60079-11) | 
| CE | |
| Certificate | CE-compliant | 
| Note | and EN 61326 | 
| ATEX | |
| Identification |  I (M1) [Ex ia Ma] I | 
|  II (1) G [Ex ia Ga] IIC | |
|  II (1) D [Ex ia Da] IIIC | |
|  II 3(1) G Ex ec ic [ia Ga] IIC T4 Gc | |
| Certificate | IBExU19ATEX1006 X | 
| IECEx | |
| Identification | [Ex ia Ma] I | 
| [Ex ia Ga] IIC | |
| [Ex ia Da] IIIC | |
| Ex ec ic [ia Ga] IIC T4 Gc | |
| Certificate | IECEx IBE 19.0001 X | 
| UL, USA/Canada | |
| Identification | UL 61010 Listed | 
| Class I Div 2; IS for Class I, II, III Div 1 | |
| Certificate | , C.D.-No 83104549 | 
| Shipbuilding approval | |
| Certificate | DNV GL TAA00000AG | 
| Safety Integrity Level (SIL, IEC 61508) | |
| Identification | 2 | 
| Certificate | SEBS-A.150520/17, V2.0 | 
| Systematic Capability | |
| Identification | 2 | 
| INMETRO | |
| Identification | [Ex ia Ma] I | 
| [Ex ia Ga] IIC | |
| [Ex ia Da] IIIC | |
| Ex ec ic [ia Ga] IIC T4 Gc | |
| Certificate | DNV 21.0064 X | 
| EAC Ex | |
| Identification |  2Ex ec ic [ia Ga] IIC T4 Gc | 
| Certificate | BY/112 02.01 TP012 103.01 00082 | 
| Shipbuilding data | |
| Temperature | B | 
| Humidity | B | 
| Vibration | A | 
| EMC | B | 
| Enclosure | Required protection according to the Rules shall be provided upon installation on board | 
| Electromagnetic compatibility | Conformance with EMC directive | 
| Noise immunity | EN 61000-6-2 | 
| Note | When being exposed to interference, there may be minimal deviations. | 
| Noise emission | |
| Standards/regulations | EN 61000-6-4 | 
| Electromagnetic HF field | |
| Designation | Electromagnetic RF field | 
| Standards/regulations | EN 61000-4-3 | 
| Typical deviation from the measuring range final value | 1 % | 
| Fast transients (burst) | |
| Designation | Fast transients (burst) | 
| Standards/regulations | EN 61000-4-4 | 
| Typical deviation from the measuring range final value | 1 % | 
| Conducted interference | |
| Designation | Conducted interferences | 
| Standards/regulations | EN 61000-4-6 | 
| Typical deviation from the measuring range final value | 1 % | 
| Electrical isolation | 3-way isolation | 
| Mounting type | DIN rail mounting | 
| Item number | 1052458 | 
| Packing unit | 1 pc | 
| Minimum order quantity | 1 pc | 
| Note | Made to order (non-returnable) | 
| Sales key | CK3121 | 
| Product key | DK1215 | 
| Weight per piece (including packing) | 181.5 g | 
| Weight per piece (excluding packing) | 150 g | 
| Customs tariff number | 85437090 | 
| Country of origin | DE | 
ECLASS
| ECLASS-13.0 | 27210129 | 
| ECLASS-15.0 | 27210129 | 
ETIM
| ETIM 9.0 | EC002919 | 
UNSPSC
| UNSPSC 21.0 | 41112100 | 
| EU RoHS | |
| Fulfills EU RoHS substance requirements | Yes | 
| Exemption | 7(a), 7(c)-I | 
| China RoHS | |
| Environment friendly use period (EFUP) | EFUP-50 An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required. | 
| EU REACH SVHC | |
| REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) | 
Compatible products
- 
    
      ME 6,2 TBUS-2 1,5/5-ST-3,81 GY - DIN rail bus connector 2695439
- 
    
      ME 6,2 TBUS-PR-ADAPTER - DIN rail bus connector 1136500
- 
    
      MCR-DP - Separating plate 1430594
- 
    
      IOA MCR-CJC-PT100 - Plug 1085776
- 
    
      EA-MSTB 2,5/ 5 - Accessories 1831016
- 
    
      TC-D37SUB-AIO16-EX-PS-UNI - Module carrier 2902932
- 
    
      TC-D37SUB-ADIO16-EX-P-UNI - Module carrier 2924854
- 
    
      IFS-USB-PROG-ADAPTER - Programming adapter 2811271
- 
    
      IFS-BT-PROG-ADAPTER - Adapter 2905872
- 
    
      MPS-IH WH - Insulating sleeve 0201663
- 
    
      MPS-IH RD - Insulating sleeve 0201676
- 
    
      MPS-IH BU - Insulating sleeve 0201689
- 
    
      MPS-IH YE - Insulating sleeve 0201692
- 
    
      MPS-IH GN - Insulating sleeve 0201702
- 
    
      MPS-IH GY - Insulating sleeve 0201728
- 
    
      MPS-IH BK - Insulating sleeve 0201731
- 
    
      MPS-MT - Test plug 0201744
- 
    
      UC-EMLP (11X9) - Plastic label 0819291
- 
    
      UC-EMLP (11X9) YE - Plastic label 0822602
- 
    
      UC-EMLP (11X9) CUS - Plastic label 0824547
- 
    
      UC-EMLP (11X9) YE CUS - Plastic label 0824548
- 
    
      UC-EMLP (11X9) SR - Plastic label 0828094
- 
    
      UC-EMLP (11X9) SR CUS - Plastic label 0828098
- 
    
      US-EMLP (11X9) - Plastic label 0828789
- 
    
      US-EMLP (11X9) YE - Plastic label 0828871
- 
    
      US-EMLP (11X9) SR - Plastic label 0828872
- 
    
      LS-EMLP (11X9) WH - Device marker 0831678
- 
    
      LS-EMLP (11X9) SR - Device marker 0831705
- 
    
      LS-EMLP (11X9) YE - Device marker 0831732
- 
    
      MACX MCR-PTB - Power and error message module 2865625
- 
    
      MACX MCR-PTB-SP - Power and error message module 2924184
- 
    
      QUINT4-SYS-PS/1AC/24DC/2.5/SC - Power supply 2904614
- 
    
      SZS 0,6X3,5 - Screwdriver 1205053
Your advantages
Input for thermocouples and mV sources
        Power supply possible via DIN rail connector
        Programming during operation with Ex measuring circuit connected and also voltage-free using IFS-USB-PROG-ADAPTER programming adapter
        Installation in zone 2, protection type "ec" (EN 60079-7) permitted
        3-way electrical isolation
        Status indicator for supply voltage, cable, sensor, and module errors
        Configuration via software (FDT/DTM): sensor type, connection technology, measuring range, measuring unit, filter, alarm signal, and output range
        Output: 0 mA ... 20 mA or 4 mA ... 20 mA
        PHOENIX CONTACT AS
        
        Strømsveien 344; N-1081 Oslo