CN-LAMBDA/4-2.2-SB
-
Surge protection device
2800025
Attachment plug with Lambda/4 technology as surge protection for coaxial signal interfaces. Connection: N connectors plug/socket
Product details
Product type | Surge protection for transceiver systems |
IEC test classification | C2 |
C3 | |
D1 | |
VDE requirement class | C2 |
C3 | |
D1 | |
Type | Intermediate plug |
Surge protection fault message | none |
Connection method | N connector 50 Ω |
Tightening torque | 1.4 Nm ... 1.7 Nm (N coupling nut) |
Width | 26.1 mm |
Height | 66 mm |
Depth | 89 mm |
Color | nickel color |
Seal material | Silicon |
Housing material | Brass (CuZn) |
Housing surface material | Ni |
Inner conductor material | BeCu |
Inner conductor surface material | Gold |
Insulation body material | PTFE |
Mechanical data | |
Open side panel | No |
Direction of action | Line-Shield/Earth Ground |
Nominal discharge current In (8/20) µs (line-ground) | 50 kA |
Nominal discharge current In (8/20) µs (line-shield) | 50 kA |
Pulse discharge current Iimp (10/350) µs | 20 kA |
Pulse discharge current Iimp (10/350) µs (line-earth) | 20 kA |
Total surge current (8/20) µs | 60 kA |
Total surge current (10/350) µs | 20 kA |
Max. discharge current Imax (8/20) µs maximum (line-earth) | 60 kA |
Max. discharge current Imax (8/20) µs maximum (line-shield) | 60 kA |
Impulse discharge current (10/350) µs, peak value limp | 20 kA |
Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 12 V (6 kV / 3 kA) |
Output voltage limitation at 1 kV/µs (line-shield) spike | ≤ 12 V (6 kV / 3 kA) |
Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 12 V (6 kV / 3 kA) |
Output voltage limitation at 1 kV/µs (line-shield) static | ≤ 12 V (6 kV / 3 kA) |
Voltage protection level Up (line-earth) | ≤ 12 V (6 kV / 3 kA) |
Voltage protection level Up (line-shield) | ≤ 12 V (6 kV / 3 kA) |
Input attenuation aE, asym. | typ. 0.05 dB (≤ 0.15 dB) |
Frequency range | 0.82 GHz ... 2.2 GHz |
Voltage standing wave ratio VSWR in a 50 Ω system | typ. 1.10 (≤ 1.20 (0.82 GHz...2.2 GHz)) |
Permissible HF power Pmax at VSWR = xx (50 ohm system) | ≤ 500 W |
≤ 4 kW (peak) | |
Surge protection fault message | none |
Impulse durability (line-earth) | C2 - 10 kV / 5 kA |
D1 - 2.5 kA | |
Impulse durability (line-shield) | C2 - 10 kV/5 kA |
D1 - 2.5 kA |
Ambient conditions | |
Degree of protection | IP68 |
Ambient temperature (operation) | -40 °C ... 90 °C |
VDE requirement class | C2 |
C3 | |
D1 | |
Standards Information technology specification | |
Standards/regulations | IEC 61643-21 |
IEC 61643-21 | |
Standards/specifications | IEC 61643-21 |
Note | 2005 |
Mounting type | Connection-specific intermediate plugging |
Item number | 2800025 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Sales key | 31BCL |
Product key | CL3312 |
GTIN | 4046356410076 |
Weight per piece (including packing) | 211.4 g |
Weight per piece (excluding packing) | 211.4 g |
Customs tariff number | 85363010 |
Country of origin | US |
EU RoHS | |
Fulfills EU RoHS substance requirements | Yes (No exemptions) |
EU REACH SVHC | |
REACH candidate substance (CAS No.) | No substance above 0.1 wt% |