PV arrester - VAL-MS 1000DC-PV/2+V-FM 2800627

Surge protective device for 2-pos. isolated and grounded 1,000 V DC PV systems, for DIN rail mounting, 3-pos. base element with remote indication contact, three pluggable temperature-monitored protective elements, status message on each plug.


Product Details




General
Note The device is intended for touch proof installation in a housing. Ensure that there is a gap of at least 8 mm between the active and grounded parts in the connection area.

IEC test classification PV II
PV T2
EN type T2
Type DIN rail module, two-section, divisible
Distance between live and grounded parts 8 mm
Installation location Interior
Installation location of the disconnect device Internal
Accessibility Accessible
Connection configuration Y configuration
SPD failure behavior OCM (Open-circuit mode)
Surge protection fault message Optical, remote indicator contact
Insulation characteristics
Overvoltage category III
Pollution degree 2

Mounting type DIN rail: 35 mm

Color jet black RAL 9005
Flammability rating according to UL 94 V-0
CTI value of material 600
Insulating material PA 6.6-FR
PBT-FR
Material group I
Housing material PA 6.6-FR
PBT-FR

Connection method Screw connection
Screw thread M5
Tightening torque 3 Nm (1.5 mm² ... 16 mm²)
4.5 Nm (25 mm² ... 35 mm²)
Stripping length 16 mm
Conductor cross section flexible 1.5 mm² ... 25 mm²
Conductor cross section solid 1.5 mm² ... 35 mm²
Conductor cross section AWG 15 ... 2
Connection method Fork-type cable lug
Conductor cross section flexible 1.5 mm² ... 16 mm²

Dimensional drawing
Width 53.4 mm
Height 98.7 mm
Depth 65.7 mm (incl. DIN rail 7.5 mm)
Horizontal pitch 3 Div.

Mode of protection (L+) - (L-)
(L+) - PE
(L-) - PE
Direction of action (L+)-PE & (L-)-PE & (L+)-(L-)
Rated load current IL 80 A
Residual current IPE ≤ 20 µA DC
≤ 250 µA AC
Standby power consumption PC ≤ 25 mVA
Nominal discharge current In (8/20) µs 15 kA
Maximum discharge current Imax (8/20) µs 40 kA
Total discharge current Itotal (8/20) µs 40 kA
Voltage protection level Up ≤ 3.7 kV
Residual voltage Ures ≤ 3.7 kV (at In)
≤ 3.1 kV (at 5 kA)
≤ 3.5 kV (at 10 kA)
≤ 4 kV (at 20 kA)
≤ 4.6 kV (at 30 kA)
≤ 5 kV (at 40 kA)
Response time tA ≤ 25 ns
PV protective circuit
Connection configuration Y configuration
SPD failure behavior OCM (Open-circuit mode)
Protective circuit DC voltage side (DC)
Open circuit voltage UOCSTC ≤ 970 V DC
Maximum discharge current Imax (8/20) µs 40 kA
Response time tA ≤ 25 ns
Total discharge current Itotal (8/20) µs 40 kA
Insulation resistance Riso > 5 GΩ (at 500 V DC)
Nominal discharge current In (8/20) µs 15 kA
Rated load current IL 80 A
Continuous operating current ICPV < 20 µA
Maximum continuous operating voltage UCPV 1170 V DC
Short-circuit current rating ISCPV 2000 A
Residual voltage Ures ≤ 3.7 kV (at In)
≤ 3.1 kV (at 5 kA)
≤ 3.5 kV (at 10 kA)
≤ 4 kV (at 20 kA)
≤ 4.6 kV (at 30 kA)
≤ 5 kV (at 40 kA)
Residual current IPE ≤ 20 µA DC
≤ 250 µA AC
Voltage protection level Up ≤ 3.7 kV
Standby power consumption PC ≤ 25 mVA

Mechanical data
Open side panel No

UL specifications
Maximum continuous operating voltage MCOV 1170 V DC
Short-circuit current rating (SCCR) 50 kA
Voltage protection rating VPR 3 kV
Nominal discharge current In 10 kA
Mode of protection (L+) - (L-)
(L+) - G
(L-) - G
Nominal voltage 1170 V DC
Power distribution system DC PV
SPD Type 1CA
UL indicator/remote signaling
AC operating voltage 125 V AC
AC operating current 1 A AC
UL connection data
Tightening torque 30 lbf-in.
Conductor cross section AWG 10 ... 2

Indicator/remote signaling
Connection name Remote fault indicator contact
Switching function Changeover contact
Operating voltage 5 V AC ... 250 V AC
30 V DC
Operating current 5 mA AC ... 1.5 A AC
1 A DC

Standards/specifications EN 50539-11

Ambient conditions
Degree of protection IP20 (only when all terminal points are used)
Ambient temperature (operation) -40 °C ... 80 °C
Ambient temperature (storage/transport) -40 °C ... 80 °C
Altitude ≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation) 5 % ... 95 %
Shock (operation) 60g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation) 7.5g (5-500 Hz/2.5 h/XYZ)


Order Key 2800627
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key CL1
Catalog Page Page 73 (C-4-2019)
GTIN 4046356615075
Weight per Piece (including packing) 332.5 GRM
Weight per Piece (excluding packing) 330.0 GRM
Customs tariff number 85363030
Country of origin IN



UL Recognized

KEMA-KEUR

cUL Recognized

EAC

cULus Recognized


China RoHS Environmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values


Your advantages

Increased safety, thanks to compliance with standard EN 50539-11
Reliable contact, thanks to integrated rotating latch
Easy replacement, thanks to plug-in arresters
Optimum inverter protection, thanks to low protection level
Efficient replacement of defective plugs, thanks to visual status indicator
Protection against mismatching, thanks to keyed plugs and base elements
Optimized maintenance planning, thanks to remote signaling