Lightning/surge arrester type 1/2 - VAL-MS-T1/T2 335/12.5/3+1-FM
2800183

Universal varistor-based plug-in lightning/surge arrester for 3-phase power supply networks with separate N and PE (5-conductor system: L1, L2, L3, N, PE), for Lightning Protection Levels III and IV, with remote indication contact.


Product Details




IEC test classification I / II
T1 / T2
EN type T1 / T2
IEC power supply system TT
TN-S
Type DIN rail module, two-section, divisible
Product type Arrester combination
Number of positions 4
Surge protection fault message Optical, remote indicator contact
Insulation characteristics
Overvoltage category III
Pollution degree 2

Nominal frequency fN 50 Hz (60 Hz)
Indicator/remote signaling
Connection name Remote fault indicator contact
Switching function Changeover contact
Operating voltage 5 V AC ... 250 V AC
30 V DC
Operating current 5 mA AC ... 1.5 A AC
1 A DC

Connection method Screw connection
Screw thread M5
Tightening torque 3 Nm (1.5 mm² ... 16 mm²)
4.5 Nm (25 mm² ... 35 mm²)
Stripping length 16 mm
Conductor cross section flexible 1.5 mm² ... 25 mm²
Conductor cross section solid 1.5 mm² ... 35 mm²
Conductor cross section AWG 15 ... 2
Connection method Fork-type cable lug
Conductor cross section flexible 1.5 mm² ... 16 mm²

Dimensional drawing
Width 71.2 mm
Height 98.7 mm
Depth 77.5 mm (incl. DIN rail 7.5 mm)
Horizontal pitch 4 Div.

Color jet black RAL 9005
Flammability rating according to UL 94 V-0
CTI value of material 600
Insulating material PA 6.6/PBT
Material group I
Housing material PA 6.6
PBT

Mechanical data
Open side panel No

Mode of protection L-N
L-PE
N-PE
Direction of action 3L-N & N-PE
Nominal voltage UN 240/415 V AC (TN-S)
240/415 V AC (TT)
Nominal frequency fN 50 Hz (60 Hz)
Maximum continuous operating voltage UC (L-N) 335 V AC
Maximum continuous operating voltage UC (L-PE) 335 V AC
Maximum continuous operating voltage UC (N-PE) 264 V AC
Rated load current IL 80 A
Residual current IPE ≤ 5 µA
Standby power consumption PC ≤ 810 mVA
Nominal discharge current In (8/20) µs (L-N) 12.5 kA
Nominal discharge current In (8/20) µs (L-PE) 12.5 kA
Nominal discharge current In (8/20) µs (N-PE) 50 kA
Maximum discharge current Imax (8/20) µs 50 kA
Impulse discharge current (10/350) µs (L-N), charge 6.25 As
Impulse discharge current (10/350) µs (L-N), specific energy 39 kJ/Ω
Impulse discharge current (10/350) µs (L-N), peak current value Iimp 12.5 kA
Impulse discharge current (10/350) µs (L-PE), charge 6.25 As
Impulse discharge current (10/350) µs (L-PE), specific energy 39 kJ/Ω
Impulse discharge current (10/350) µs (L-PE), peak current value Iimp 12.5 kA
Impulse discharge current (10/350) µs (N-PE), charge 25 As
Impulse discharge current (10/350) µs (N-PE), specific energy 625 kJ/Ω
Impulse discharge current (10/350) µs (N-PE), peak current value Iimp 50 kA
Total discharge current Itotal (8/20) µs 50 kA
Total discharge current Itotal (10/350) µs 50 kA
Follow current interrupt rating Ifi (N-PE) 100 A
Short-circuit current rating ISCCR 25 kA
Voltage protection level Up (L-N) ≤ 1.2 kV
≤ 1.6 kV (30 kA - 8/20 µs)
Voltage protection level Up (L-PE) ≤ 2 kV
Voltage protection level Up (N-PE) ≤ 1.7 kV
Residual voltage Ures (L-N) ≤ 1.2 kV (at In)
≤ 1.1 kV (at 10 kA)
≤ 1 kV (at 5 kA)
≤ 0.9 kV (at 3 kA)
Residual voltage Ures (L-PE) ≤ 2 kV (at In)
≤ 1.5 kV (at 10 kA)
≤ 1.2 kV (at 5 kA)
≤ 1.1 kV (at 3 kA)
Residual voltage Ures (N-PE) ≤ 0.6 kV (at In)
≤ 0.5 kV (at 10 kA)
≤ 0.5 kV (at 5 kA)
≤ 0.4 kV (at 3 kA)
TOV behavior at UT (L-N) 415 V AC (5 s / withstand mode)
457 V AC (120 min / safe failure mode)
TOV behavior at UT (N-PE) 1200 V AC (200 ms / withstand mode)
Response time tA (L-N) ≤ 25 ns
Response time tA (L-PE) ≤ 100 ns
Response time tA (N-PE) ≤ 100 ns
Max. backup fuse with V-type through wiring 80 A (gG - 16 mm²)
Max. backup fuse with branch wiring 160 A (gG)
Additional technical data
Maximum discharge current Imax (8/20) µs 65 kA

Ambient conditions
Degree of protection IP20 (only when all terminal points are used)
Ambient temperature (operation) -40 °C ... 80 °C
Ambient temperature (storage/transport) -40 °C ... 80 °C
Altitude ≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation) 5 % ... 95 %
Shock (operation) 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation) 7.5g (10 ... 500 Hz / 2.5 h / X, Y, Z)

UL specifications
Maximum continuous operating voltage MCOV (L-L) 670 V AC
Maximum continuous operating voltage MCOV (L-N) 335 V AC
Maximum continuous operating voltage MCOV (L-G) 335 V AC
Maximum continuous operating voltage MCOV (N-G) 264 V AC
Nominal discharge current In (L-L) 20 kA
Nominal discharge current In (L-N) 20 kA
Nominal discharge current In (L-G) 20 kA
Nominal discharge current In (N-G) 20 kA
Mode of protection L-L
L-N
L-G
N-G
Nominal voltage 240/415 V AC
Power distribution system Wye
Nominal frequency 50/60 Hz
Measured limiting voltage MLV (L-L) 3570 V
Measured limiting voltage MLV (L-N) 2630 V
Measured limiting voltage MLV (L-G) 3600 V
Measured limiting voltage MLV (N-G) 2600 V
SPD Type 4CA
AC operating voltage 125 V AC
AC operating current 1 A AC
UL connection data
Tightening torque 30 lbf-in.
Conductor cross section AWG 14 ... 2

Standards/specifications IEC 61643-11
Standards/specifications EN 61643-11

Mounting type DIN rail: 35 mm

Item number 2800183
Packing unit 1 pc
Minimum order quantity 1 pc
Product Key CL1151
Catalog Page Page 46 (C-4-2019)
GTIN 4046356518550
Weight per Piece (including packing) 677 g
Weight per Piece (excluding packing) 643.8 g
Customs tariff number 85363030
Country of origin DE


ECLASS

ECLASS-9.0 27130802
ECLASS-10.0.1 27130802
ECLASS-11.0 27130802

ETIM

ETIM 8.0 EC000381

UNSPSC

UNSPSC 21.0 39121600

cUL Recognized

Approval ID: FILE E 330181

UL Recognized

Approval ID: FILE E 330181

IECEE CB Scheme

Approval ID: AT 2584

EAC

Approval ID: EAC-Zulassung

CCA

Approval ID: NTR-AT 1906
Approval Specification Data
Nominal Voltage UN Nominal Current IN Cross Section AWG Cross Section mm2

KEMA-KEUR

Approval ID: 2162496-01

DNV GL

Approval ID: TAE00001N9
Approval Specification Data
Nominal Voltage UN Nominal Current IN Cross Section AWG Cross Section mm2

EAC

Approval ID: RU C-DE.*09.B.00169

ÖVE

Approval ID: 18583-009-08

cULus Recognized


China RoHS Environmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Your advantages

Quality proven millions of times over in the widest range of applications
Rapid installation with bridges, thanks to industry-standard overall width of 1 HP
Easy testing and insulation measurement, thanks to pluggable protection modules
Can be used in lightning protection level III and IV due to discharge capacity of 12.5 kA per position
Vibration-resistant latching ensures the plug remains firmly in place
With floating remote indication contact
Plugs can be checked with CHECKMASTER
Secure hold of plugs in the event of high lightning current loads and strong vibrations thanks to new latching