Distribution block - PTFIX 10/6X4-SI (5X20)
1172135

Distribution block, fuse type: G / 5 x 20, nom. voltage: 250 V, nominal current: 6.3 A, connection method: Push-in connection, Load contact, Rated cross section: 4 mm2, cross section:  0.2 mm2- 6 mm2, connection method: Push-in connection, Line contact, Rated cross section: 10 mm2, cross section:  0.5 mm2- 16 mm2, mounting type: for snapping onto a DIN rail adapter, Direct mounting with flange, color: black


Product Details




General
Note The current is determined by the fuse used, the voltage by the fuse or selected light indicator.
The maximum load current of a single clamping unit must not be exceeded.
For power distribution applications, IEC 60364-4-43.2008; modified + corrigendum Okt. 2008 (DIN VDE 0100-430:2010-10) section 433.2 ff must be observed!

Product type Distributor terminal block
Number of connections 7
Number of rows 1
Insulation characteristics
Overvoltage category III
Degree of pollution 3

Rated surge voltage 8 kV
Maximum power dissipation for nominal condition 1.02 W
Fuse G / 5 x 20
Maximum power dissipation max. 1.6 W (with single arrangement of the fuse terminal block in the event of overload)
max. 1.6 W (With interconnected arrangement of several fuse terminal blocks in the event of overload)
max. 4 W (with single arrangement of the fuse terminal block in the event of a short-circuit)
max. 2.5 W (With interconnected arrangement of several fuse terminal blocks in the event of a short-circuit)

Number of connections per level 7
Load contact
Stripping length 10 mm ... 12 mm
Internal cylindrical gage A4
Conductor cross section solid 0.2 mm² ... 6 mm²
Cross section AWG 24 ... 10
Conductor cross section flexible 0.2 mm² ... 4 mm²
Conductor cross section, flexible [AWG] 24 ... 12
Flexible conductor cross section flexible (ferrule, w/o plastic sleeve) 0.2 mm² ... 0.4 mm²
Flexible conductor cross section (ferrule with plastic sleeve) 0.2 mm² ... 4 mm²
2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve 0.5 mm² ... 1 mm²
Nominal current 6.3 A (the current is determined by the fuse used)
Maximum load current 6.3 A (with 4 mm² conductor cross section)
Maximum total current 37.8 A (The maximum load current of the individual terminal point must not be exceeded.)
Nominal voltage 250 V (the voltage is determined by the fuse used)
Nominal cross section 4 mm²
Line contact
Stripping length 12 mm ... 14 mm
Conductor cross section solid 0.5 mm² ... 16 mm²
Cross section AWG 20 ... 6
Conductor cross section flexible 0.5 mm² ... 10 mm²
Conductor cross section, flexible [AWG] 20 ... 8
Flexible conductor cross section flexible (ferrule, w/o plastic sleeve) 0.5 mm² ... 10 mm²
Flexible conductor cross section (ferrule with plastic sleeve) 0.5 mm² ... 10 mm²
2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve 0.5 mm² ... 4 mm²
Nominal current 37.8 A
Maximum load current 37.8 A (with 10 mm² conductor cross section)
Maximum total current The maximum load current of the individual terminal point must not be exceeded.
Nominal cross section 10 mm²
Load contact Connection cross sections directly pluggable
Conductor cross section solid 0.5 mm² ... 6 mm²
Flexible conductor cross section flexible (ferrule, w/o plastic sleeve) 0.5 mm² ... 4 mm²
Flexible conductor cross section (ferrule with plastic sleeve) 0.5 mm² ... 4 mm²
Line contact Connection cross sections directly pluggable
Conductor cross section solid 1.5 mm² ... 10 mm²
Conductor cross section, solid [AWG] 16 ... 8
Flexible conductor cross section flexible (ferrule, w/o plastic sleeve) 1.5 mm² ... 10 mm²
Flexible conductor cross section (ferrule with plastic sleeve) 1.5 mm² ... 10 mm²

Width 87.8 mm
Height 35.4 mm
Length 28.6 mm

Color black
Flammability rating according to UL 94 V0
Insulating material group I
Insulating material PA
Static insulating material application in cold -60 °C
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) 130 °C
Relative insulation material temperature index (Elec., UL 746 B) 130 °C
Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26 HL 1 - HL 3
Calorimetric heat release NFPA 130 (ASTM E 1354) 27,5 MJ/kg
Surface flammability NFPA 130 (ASTM E 162) passed
Specific optical density of smoke NFPA 130 (ASTM E 662) passed
Smoke gas toxicity NFPA 130 (SMP 800C) passed

Mechanical data
Open side panel No

Oscillation/broadband noise
Specification DIN EN 50155 (VDE 0115-200):2018-05
Spectrum Service life test category 2, bogie-mounted
Frequency f1 = 5 Hz to f2 = 250 Hz
ASD level 6.12 (m/s²)²/Hz
Acceleration 3.12g
Test duration per axis 5 h
Test directions X-, Y- and Z-axis
Result Test passed
Shocks
Specification DIN EN 50155 (VDE 0115-200):2018-05
Pulse shape Half-sine
Acceleration 30g
Shock duration 18 ms
Number of shocks per direction 3
Test directions X-, Y- and Z-axis (pos. and neg.)
Result Test passed
Ambient conditions
Ambient temperature (operation) -60 °C ... 105 °C (max. short-term operating temperature RTI Elec.)
Ambient temperature (storage/transport) -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Ambient temperature (assembly) -5 °C ... 70 °C
Ambient temperature (actuation) -5 °C ... 70 °C
Permissible humidity (storage/transport) 30 % ... 70 %

Connection in acc. with standard IEC 60947-7-3
IEC 60947-7-3

Mounting type for snapping onto a DIN rail adapter
Direct mounting with flange

Item number 1172135
Packing unit 8 pc
Minimum order quantity 8 pc
Sales Key BEA135
Product Key BEA135
GTIN 4063151197995
Weight per Piece (including packing) 77 g
Weight per Piece (excluding packing) 48.175 g
Customs tariff number 85369010
Country of origin PL


ECLASS

ECLASS-11.0 27141116

ETIM

ETIM 8.0 EC000899

UNSPSC

UNSPSC 21.0 39121400

CSA

Approval ID: 13631
Approval Specification Data
Nominal Voltage UN Nominal Current IN Cross Section AWG Cross Section mm2
Use group B
Output 300 V 6.3 A 24 - 10
Input 300 V 40 A 20 - 8

IECEE CB Scheme

Approval ID: NL-77613
Approval Specification Data
Nominal Voltage UN Nominal Current IN Cross Section AWG Cross Section mm2
500 V

cULus Recognized

Approval ID: E60425
Approval Specification Data
Nominal Voltage UN Nominal Current IN Cross Section AWG Cross Section mm2
Use group B
Output 300 V 6.3 A 24 - 10
Input 300 V 40 A 20 - 8
Use group F
Output 250 V 6.3 A 24 - 10
Input 250 V 40 A 20 - 8

KEMA-KEUR

Approval ID: 71-121479
Approval Specification Data
Nominal Voltage UN Nominal Current IN Cross Section AWG Cross Section mm2
500 V

China RoHS Environmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values