TRIO3-UPS/1AC/24DC/10
-
Uninterruptible power supply
1359610
TRIO UPS - UPS with integrated power supply, DIN rail mounting, Push-in connection, output: 24 V DC / 10 A
Product details
Input voltage range | 100 V AC ... 240 V AC -15 % ... +10 % |
115 V AC ... 240 V AC ±10 % (UL) | |
Voltage type of supply voltage | AC |
Inrush current integral (I2t) | typ. < 1 A2s |
Inrush current limitation | typ. < 21 A |
Frequency range (fN) | 50 Hz ... 60 Hz ±10 % |
Mains buffering time | typ. 45 ms (120 V AC) |
Static Boost (IStat.Boost) | 10 A |
Switch-on time during battery operation (Bat.-Start) | ≤ 5 ms |
Discharge current to PE | < 3.5 mA |
Current consumption | typ. 4.23 A (100 V AC) |
Current consumption IN (UN, IOUT = IN, Icharge = 0) | 2.3 A (120 V AC) |
Current consumption Imax (UN, IOUT = IStat.Boost, ICharge = max) | 3.7 A (120 V AC) |
Current consumption INo-Load(UN, IOUT = 0, Icharge = 0) | 0.11 A (120 V AC) |
Current consumption Icharge (UN, IOUT = 0, Icharge = max) | 1.4 A (120 V AC) |
Power consumption PN (UN, IOUT = IN, Icharge = 0) | 259 W (120 V AC) |
Power consumption Pmax (UN, IOUT = IStat.Boost, Icharge = max) | 421 W (120 V AC) |
Power consumption PNo-Load (UN, IOUT = 0, Icharge = 0) | 7.6 W (120 V AC) |
Power consumption Pcharge (UN, IOUT = 0, Icharge = max) | 166 W (120 V AC) |
Input fuse | 10 A (internal (device protection)) |
Recommended breaker for input protection | 6 A ... 16 A |
Efficiency | typ. 93.17 % (120 V AC) |
typ. 93.5 % (230 V AC) | |
Short-circuit-proof | yes |
No-load proof | yes |
Crest factor | typ. 1.72 (120 V AC) |
typ. 2.04 (230 V AC) | |
Switch-over time | < 3 ms |
Output current limit | 10 A |
UPS connection in parallel | yes, with diode module uncoupled |
UPS connection in series | no |
Energy storage device connection in parallel | yes, max. 3 |
Energy storage device connection in series | no |
Feedback voltage resistance | ≤ 35 V DC |
Protection against overvoltage at the output (OVP) | ≤ 35 V DC |
Residual ripple | < 25 mV |
Rise time | ≤ 1 s (UOut = 10 % ... 90 %) |
Mains operation | |
Output voltage | 24 V DC |
Output voltage range | 24 V DC ... 28 V DC (>24 V, performance-limited) |
max. 240 W | |
Output current IN | 10 A |
Dynamic BOOST IDyn.Boost (IDyn.Boost) | 15 A (5 s) |
Output power PN | 240 W |
Output power PDyn. Boost | 360 W (5 s) |
Maximum no-load power dissipation | ≤ 10 W (120 V AC) |
≤ 10 W (230 V AC) | |
Power loss nominal load max. | ≤ 20 W (120 V AC) |
≤ 20 W (230 V AC) | |
Battery operation | |
Output voltage | UBAT -0,2 V DC |
Output voltage range | 19.2 V DC ... 32 V DC |
Output current IN | 10 A |
Dynamic BOOST IDyn.Boost (IDyn.Boost) | 15 A (5 s) |
Output power PN | 240 W |
Output power PDyn. Boost | 360 W (5 s) |
Output power POUT (UN, IOUT = Idyn.Boost) | 360 W (5 s) |
Maximum no-load power dissipation | ≤ 1.5 W (120 V AC) |
≤ 1.5 W (230 V AC) | |
Power loss nominal load max. | ≤ 4 W (120 V AC) |
≤ 4 W (230 V AC) |
Nominal voltage UN | 24 V DC |
Charging voltage | max. 32 V DC |
Charging current (Preset) | 2 A |
Charging current (Configurable) | 0.2 A ... 5 A (-25 °C ... 55 °C 5K) |
Charging current (Reduced) | 5 A ... 3.75 A (55°C ... 65°C 5K) |
Charging current (max.) | 5 A |
Nominal capacity range | 4 Ah ... 110 Ah |
Battery technology | VRLA-AGM |
Charge characteristic curve | IU0U |
Input | |
Position | 1.x |
Connection technology | |
Position marking | 1.1 (L/+), 1.2 (N/-), 1.3 () |
Conductor connection | |
Connection method | Push-in connection |
rigid | 0.2 mm² ... 4 mm² |
1.5 mm² | |
flexible | 0.2 mm² ... 2.5 mm² |
1.5 mm² | |
flexible with ferrule without plastic sleeve | 0.25 mm² ... 2.5 mm² |
1.5 mm² | |
flexible with ferrule with plastic sleeve | 0.25 mm² ... 2.5 mm² |
1.5 mm² | |
AWG | 24 ... 12 |
16 | |
Stripping length | 10 mm |
Output | |
Position | 2.x |
Connection technology | |
Position marking | 2.1 (+), 2.2 (+), 2.3 (-), 2.4 (-) |
Conductor connection | |
Connection method | Push-in connection |
rigid | 0.2 mm² ... 4 mm² |
1.5 mm² | |
flexible | 0.2 mm² ... 2.5 mm² |
1.5 mm² | |
flexible with ferrule without plastic sleeve | 0.25 mm² ... 2.5 mm² |
1.5 mm² | |
flexible with ferrule with plastic sleeve | 0.25 mm² ... 2.5 mm² |
1.5 mm² | |
AWG | 24 ... 12 |
16 | |
Stripping length | 10 mm |
Battery | |
Position | 4.x |
Connection technology | |
Position marking | 4.1 (+), 4.2 (-) |
Conductor connection | |
Connection method | Push-in connection |
rigid | 0.2 mm² ... 10 mm² |
2.5 mm² | |
flexible | 0.2 mm² ... 6 mm² |
2.5 mm² | |
flexible with ferrule without plastic sleeve | 0.25 mm² ... 6 mm² |
2.5 mm² | |
flexible with ferrule with plastic sleeve | 0.25 mm² ... 4 mm² |
2.5 mm² | |
AWG | 24 ... 8 |
14 | |
Stripping length | 12 mm |
Signal | |
Position | 3.x |
Conductor connection | |
Connection method | Push-in connection |
rigid | 0.2 mm² ... 1.5 mm² |
0.5 mm² | |
flexible | 0.2 mm² ... 1.5 mm² |
0.5 mm² | |
flexible with ferrule without plastic sleeve | 0.2 mm² ... 1.5 mm² |
0.5 mm² | |
flexible with ferrule with plastic sleeve | 0.2 mm² ... 0.75 mm² |
0.5 mm² | |
AWG | 24 ... 16 |
20 | |
Stripping length | 8 mm |
LED signaling | |
Types of signaling | LED: DC output |
Function | Visualization of the operating state of the DC output voltage (DC OK) |
Color | red, yellow, green (multicolor LED) |
LED off | Device off (Off) |
LED on (green), DC OK | Output power in operation < 90% (On (green), DC OK) |
LED on (yellow), IOut > 90 % | Output power in operation > 90% (On (yellow), IOut > 90% ) |
LED on (red), ISHORT | Output power overload > 150% (On (red), ISHORT) |
LED on (flashing red) OVP | UOUT > OVP (Over voltage protection) (on (flashing red 50%)) |
LED signaling | |
Types of signaling | LED: device state |
Function | Visual display of the operating state of the UPS |
Color | red, yellow, green (multicolor LED) |
LED off | Device off (Off) |
LED on (green) | Device on (on (green)) |
LED on (flashing green 90%) | Remote contact is short-circuited with Output (-). (on (flashing green 90%)) |
LED on (flashing green 10 %) | Signaling time after shutdown in battery operation (on (flashing green 10%)) |
LED on (yellow) | Battery operation (on (yellow)) |
LED on (flashing yellow) | Battery charging (on (flashing yellow 50%)) |
LED on (red) | Group alarm, device (on (red)) |
LED on (flashing red) | Service mode for battery (on (flashing red 50%)) |
LED signaling | |
Types of signaling | LED: battery condition |
Function | Visual display of the operating state of the battery |
Color | red, yellow, green (multicolor LED) |
LED off | Device off (Off) |
LED on (green) | Battery SOH > 6 months (on (green)) |
LED on (yellow) | Battery SOH < 6 months (on (yellow)) |
LED on (red) | Group alarm, battery (on (red)) |
LED on (flashing red) | Battery SOH = 0 months (on (flashing red 50%)) |
Signal input Bat.-Start | |
Signalization designation | Bat.-Start |
Position | 3.x |
Position marking | 3.6 (Bat.-Start) |
Low signal | Connection to Output (-) with < 2.7 kΩ |
High signal | Open (> 200 kΩ between Bat.-Start and Output (-)) |
Signal input Remote | |
Signalization designation | Remote |
Position | 3.x |
Position marking | 3.7 (Remote) |
Low signal | Connection to Output (-) with < 2.7 kΩ |
High signal | Open (> 200 kΩ between Remote and Output (-)) |
Signal input Temp.-Sensor | |
Signalization designation | Temp.-Sensor |
Position | 3.x |
Position marking | 3.8 (Temp.-Sensor), 3.9 (Temp.-Sensor) |
Voltage | max. 3.5 V (when the sensor is not connected) |
Short-circuit current rating | max. 3 mA |
Signal output DC OK | |
Position | 3.x |
Signalization designation | DC OK |
Position marking | 3.1 (DC OK) |
State condition (Contact closed (battery operation)) | UOut > 20.4 V; UOut < 32 V |
State condition (Contact open (battery operation)) | UOut < 20.4 V; UOut > 32 V |
Switching output | Transistor output, active |
Output voltage | 24 V DC |
Continuous load current | 20 mA |
LED status indicator | green (LED: DC output) |
Signal output Battery Mode | |
Position | 3.x |
Signalization designation | Bat.-Mode |
Position marking | 3.2 (Bat.-Mode) |
State condition (Contact closed) | Device in battery mode |
State condition (Contact open) | Device in mains mode or device off |
Switching output | Transistor output, active |
Output voltage | 24 V DC |
Continuous load current | 20 mA |
LED status indicator | yellow (LED: device state) |
Signal output | |
Position | 3.x |
Signalization designation | Bat.-Service |
Position marking | 3.3 (Bat.-Service) |
State condition (Contact closed) | Device in battery mode |
State condition (Contact open) | Device in mains mode or device off |
Switching output | Transistor output, active |
Output voltage | 24 V DC |
Continuous load current | 20 mA |
LED status indicator | red, flashing (LED: device status) |
Signal output Alarm | |
Position | 3.x |
Signalization designation | Alarm |
Position marking | 3.4 (Alarm) |
State condition (Contact closed) | no alarm |
State condition (Contact open) | Alarm |
Switching output | Transistor output, active |
Output voltage | 24 V DC |
Continuous load current | 20 mA |
LED status indicator | red (LED: battery status) |
Signal output Ready | |
Position | 3.x |
Signalization designation | Ready |
Position marking | 3.5 (Ready) |
State condition (Contact closed (mains operation)) | Battery is fully charged |
State condition (Contact closed (battery operation)) | As long as output voltage > cut-off voltage |
State condition (Contact open (mains operation)) | Battery charging |
State condition (Contact open (battery operation)) | Output voltage < cut-off voltage or device is switched off |
Switching output | Transistor output, active |
Output voltage | 24 V DC |
Continuous load current | 20 mA |
Product type | DC UPS |
Product family | TRIO UPS |
MTBF (IEC 61709, SN 29500) | 1097743 h (25 °C) |
667151 h (40 °C) | |
310917 h (60 °C) | |
Insulation characteristics | |
Protection class | I |
Degree of pollution | 2 |
Item dimensions | |
Width | 88 mm |
Height | 135 mm |
Depth | 132 mm |
Depth (Device depth (DIN rail mounting)) | 125 mm (Device depth (DIN rail mounting)) |
Installation dimensions | |
Installation distance right/left | 0 mm / 0 mm |
Installation distance top/bottom | 50 mm / 50 mm |
Mounting type | DIN rail mounting |
Mounting position | horizontal DIN rail NS 35, EN 60715 |
Material (Housing front) | PS |
Flammability rating according to UL 94 (housing / terminal blocks) | V0 |
Housing material | Aluminum |
Ambient conditions | |
Degree of protection | IP20 |
Ambient temperature (operation) | -25 °C ... 70 °C |
Ambient temperature (operation) (Output power derating) | > 60 °C (2.5 %/K) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Maximum altitude | ≤ 5000 m |
Maximum altitude (Output power derating) | > 2000 m (10 %/1000 m) |
Climatic class | 3K3 (EN 60721) |
Shock | 18 ms, 30g, per spatial direction |
Vibration (operation) | 5 Hz ... 100 Hz, amplitude ±2.5 mm, 2.3g |
30 Hz ... 100 Hz, 2.3g, 90 min. |
Overvoltage category | |
EN 61010-1 | III (≤ 2000 m) / II (≤ 5000 m) |
EN 61010-2-201 | III (≤ 2000 m) / II (≤ 5000 m) |
Safety of power supply units up to 1100 V (insulation distances) | |
Standard designation | Safety of power supply units up to 1100 V (insulation distances) |
Standards/specifications | DIN EN 61558-2-16 |
Electrical safety | |
Standard designation | Electrical safety |
Standards/specifications | IEC 61010-2-201 (SELV) |
Electronic equipment for use in power installations | |
Standard designation | Equipping high voltage installations with electronic equipment |
Standards/specifications | EN 50178/VDE 0160 (PELV) |
Safety for measurement, control, and laboratory equipment | |
Standard designation | Safety for equipment for measurement, control, and laboratory use |
Standards/specifications | IEC 61010-1 |
Protective extra-low voltage | |
Standard designation | Protective extra-low voltage |
Standards/specifications | IEC 61010-1 (SELV) |
IEC 61010-2-201 (PELV) | |
Safe isolation | |
Standard designation | Safe isolation |
Standards/specifications | IEC 61010-2-201 |
Limitation of harmonic line currents | |
Standard designation | Limitation of harmonic line currents |
Standards/specifications | EN 61000-3-2 |
Mains variation/undervoltage | |
Standard designation | Mains variation/undervoltage |
Standards/specifications | SEMI F47 |
EN 61000-4-11 |
UL | |
Identification | UL/C-UL Listed UL 61010-1 |
UL | |
Identification | UL/C-UL Listed UL 61010-2-201 |
ANSI/UL 121201 | |
Identification | UL/C-UL Listed ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C |
Shipbuilding | |
Identification | DNV |
Shipbuilding | |
Identification | LR |
Shipbuilding | |
Identification | Nippon Kaiji Kyokai |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
Interference emission | Interference emission in accordance with EN 61000-6-3 (residential areas), EN 61000-6-4 (industrial areas) and EN 61000-6-8 (commercial areas) |
Noise immunity | Immunity in accordance with EN 61000-6-2 (industrial) |
Conducted noise emission | |
Standards/regulations | EN 61000-6-3 |
Noise emission | |
Standards/regulations | EN 61000-6-3 |
Harmonic currents | |
Standards/regulations | EN 61000-3-2 |
Flicker | |
Standards/regulations | EN 61000-3-3 |
Electrostatic discharge | |
Standards/regulations | EN 61000-4-2 |
Electrostatic discharge | |
Contact discharge | 6 kV (Test Level 3) |
Discharge in air | 8 kV (Test Level 3) |
Electromagnetic HF field | |
Standards/regulations | EN 61000-4-3 |
Electromagnetic HF field | |
Frequency range | 80 MHz ... 6 GHz |
Test field strength | 10 V/m |
Frequency range | 1.4 GHz ... 6 GHz |
Test field strength | 3 V/m |
Fast transients (burst) | |
Standards/regulations | EN 61000-4-4 |
Fast transients (burst) | |
Input | ± 4 kV (100 kHz) |
Output | ± 2 kV (100 kHz) |
Signal | ± 2 kV (100 kHz) |
Voltage (Battery) | ± 2 kV (100 kHz) |
Surge voltage load (surge) | |
Standards/regulations | EN 61000-4-5 |
Surge voltage load (surge) | |
Input | 2 kV (Test Level 4 - symmetrical) |
4 kV (Test Level 4 - asymmetrical) | |
Output | 1 kV (Test Level 3 - symmetrical) |
2 kV (Test Level 3 - asymmetrical) | |
Signal | 1 kV (Test Level 2 - asymmetrical) |
Conducted interference | |
Standards/regulations | EN 61000-4-6 |
Conducted interference | |
Frequency range | 0.15 MHz ... 80 MHz |
Voltage | 10 V |
Item number | 1359610 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Sales key | CMUD13 |
Product key | CMUD13 |
GTIN | 4063151688073 |
Weight per piece (including packing) | 1.343 g |
Weight per piece (excluding packing) | 1.150 g |
Customs tariff number | 85044095 |
Country of origin | CN |
ECLASS
ECLASS-13.0 | 27040705 |
ETIM
ETIM 9.0 | EC000382 |
EU RoHS | |
Fulfills EU RoHS substance requirements | Yes |
Exemption | 34, 6(c), 7(a), 7(c)-I |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-25
An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required.
|
EU REACH SVHC | |
REACH candidate substance (CAS No.) | Hexahydromethylphthalic anhydride (CAS: n/a) |
Lead (CAS: 7439-92-1) |
Compatible products
-
TRIO-BAT/PB/24DC/4AH - Battery module 1394730
-
TRIO-BAT/PB/24DC/7AH - Battery module 1384031
-
TRIO-BAT/PB/24DC/12AH - Battery module 1394727
-
UPS-BAT/PB/24DC/20AH - Battery module 1348516
-
UPS-BAT/PB/24DC/40AH - Battery module 1354641
-
UPS-BAT/PB/24DC/110AH - Battery module 1474660
-
UWA 182/52 - Mounting adapter 2938235
-
SZS 0,4X2,5 VDE - Screwdriver 1205037
-
POTI SEALING PLUG - Sealing plug 1175957
PHOENIX CONTACT A/S