FB-ET
-
Trunk module
2316048
Trunk module for Foundation Fieldbus and PROFIBUS PA expansions with terminator
Product details
Product type | Device coupler |
Supply | |
Supply voltage range | 24 V DC ... 32 V DC |
Nominal supply voltage | 24 V DC (IIC) |
32 V DC (IIB) | |
Typical current consumption | 8 mA (without termination resistor) |
Max. current consumption | 12 mA (with terminator) |
Safety data | |
Input voltage Ui | 17.5 V (for FB-2SP in a FNICO/FISCO ic system) |
Signal | PROFIBUS |
FOUNDATION Fieldbus | |
Data: Foundation Fieldbus and PROFIBUS PA Segment | |
Connection method | Pluggable COMBICON screw connection for each spur |
Termination resistor | 100 Ω, external removable plug included |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section, rigid max. | 2.5 mm² |
Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section AWG max. | 12 |
Conductor cross section AWG min. | 24 |
Surge protection | Active if voltage exceeds 39 V (typ.) or 41 V (max.) |
Voltage drop trunk line / outputs | ≤ 0.2 V |
Dimensional drawing |
|
Width | 17.5 mm |
Height | 99.1 mm |
Depth | 70.4 mm |
Color | green |
Corrosive resistance in accordance with ANSI-ISA 71.04-1985 - Severity level G3 | : |
Ambient conditions | |
Degree of protection | IP20 |
Ambient temperature (operation) | -40 °C ... 85 °C |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
Shock | 15g, 11 ms |
Vibration (operation) | 10 Hz ... 150 Hz, 1g |
Conformity/Approvals | |
Conformance | CE-compliant, additionally EN 61326 |
IEC | IEC 60529, IEC 61158-2 |
CSA, USA/Canada | Class I, Zone 2, AEx nA IIC T4 |
Class I, Division 2, Groups A,B,C,D | |
Fieldbus Foundation | FF-846 |
EN | EN 61326, EN 60068-2-27, EN 60068-2-6 |
NE | NAMUR NE 21 |
Ex data | |
ATEX | Sira 08ATEX4302X; II 3G Ex nA IIC T4 Gc II 3G Ex ic IIC T4 Gc, FISCO ic II 3G Ex nL IIC T4 Gc, FNICO |
IECEx | IECEx SIR 08.0109X; Ex nA IIC T4 Gc; Ex ic IIC T4 Gc, FISCO ic; Ex nL IIC T4 Gc, FNICO |
CSA, USA/Canada | Class I, Division 2, Groups A,B,C,D; Ex nA IIC T4 Class I, Zone 2, AEx nA IIC T4 |
Standards | |
Standards/regulations | IEC 60529, IEC 61158-2 |
NE21 | |
EN 61326, EN 60068-2-27, EN 60068-2-6 | |
FF-846 | |
Standards/regulations | |
Standards/regulations | Ring wave noise immunity in acc. with IEC 61000-4-12 |
Standards/regulations | |
Standards/regulations | Dry heat in acc. with IEC 61131-2 |
Standards/regulations | |
Standards/regulations | Damp heat in acc. with IEC 61131-2 |
Standards/regulations | |
Standards/regulations | Shock and vibration in acc. with EN 61131-2 and EN 50178 |
Standards/regulations | IEC 61158-2 |
Mounting type | DIN rail mounting |
Mounting position | On horizontal DIN rail NS 35 in acc. with EN 60715 |
Item number | 2316048 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Sales key | DNC144 |
Product key | DNC144 |
Catalog page | Page 425 (C-8-2015) |
GTIN | 4046356466165 |
Weight per piece (including packing) | 106,2 g |
Weight per piece (excluding packing) | 102,7 g |
Customs tariff number | 85389099 |
Country of origin | US |
ETIM
ETIM 8.0 | EC001600 |
UNSPSC
UNSPSC 21.0 | 32151600 |
EU RoHS | |
Fulfills EU RoHS substance requirements | Yes |
Exemption | 7(a), 7(c)-I |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-50
An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required.
|
EU REACH SVHC | |
REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) |