The module is designed for use within an Axioline F station. It is used to acquire data from absolute encoders with SSI interface with a maximum resolution of up to 56 bits. The module supports encoders with gray and binary code. Transmission speeds of up to 2 MHz are supported. In addition, the module has an analog output which allows for specifying setpoints, e.g., for electrical and hydraulic drives.
AXL F SSI1 AO1 1H
-
Function module
2688433
Axioline F function module, 1 SSI interface for absolute encoder, 1 analog output: 0 - 10 V, ±10 V, 0 - 5 V, ±5 V, 0 - 20 mA, 4 - 20 mA, ±20 mA, 2-conductor connection technology (including bus base module and connectors)
Free download available.
Downloads
Product details
Dimensional drawing |
|
Width | 35 mm |
Height | 126.1 mm |
Depth | 54 mm |
Note on dimensions | The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715). |
Note on application | |
Note on application | Only for industrial use |
Axioline F local bus | |
Number of interfaces | 2 |
Connection method | Bus base module |
Transmission speed | 100 Mbps |
Module | |
ID code (hex) | none |
Input address area | 12 Byte |
Output address area | 12 Byte |
Required parameter data | 29 Byte |
Required configuration data | 7 Byte |
Encoder | |
Number of inputs | 1 |
Input name | SSI interface |
Description of the input | RS-422 interface in accordance with SSI specification |
Encoder signals | Single-turn and multi-turn encoder, length measuring sticks |
Input frequency | to 2 MHz (Can be parameterized: 62.5 kHz, 125 kHz (default), 250 kHz, 500 kHz, 1 MHz, 2 MHz) |
Parity | Even, odd or no parity |
Transmission frequency | 2.00 MHz |
Adjustable resolution | 8 ... 56 bit |
Encoder supply voltage | 24 V DC (UI - 0.5 V) |
Analog: | |
Output name | Analog outputs |
Connection method | Push-in connection |
Connection technology | 2-conductor (shielded, twisted pair) |
Number of outputs | 1 |
D/A conversion time | 5 µs |
D/A converter resolution | 16 bit |
Protective circuit | Surge protection; Electronic (35 V, permanent) |
Short-circuit and overload protection; electronic | |
Transient protection; Suppressor diode | |
Data formats | IB IL, S7-compatible, standardized representation |
Measured value representation | 16 bits |
Representation of output values | 16 bits (15 bits + sign) |
Current output signal | 0 mA ... 20 mA |
4 mA ... 20 mA | |
-20 mA ... 20 mA | |
Load/output load current output | max. 500 Ω |
Voltage output signal | 0 V ... 5 V |
-5 V ... 5 V | |
0 V ... 10 V | |
-10 V ... 10 V | |
Load/output load voltage output | > 2 kΩ |
Permissible cable length | max. 250 m |
Product type | I/O component |
Product family | Axioline F |
Type | block modular |
Mounting position | any (no temperature derating) |
Scope of supply | including bus base module and Axioline F connectors |
Special properties | Analog output: 1 |
Insulation characteristics | |
Overvoltage category | II (IEC 60664-1, EN 60664-1) |
Pollution degree | 2 (IEC 60664-1, EN 60664-1) |
Maximum power dissipation for nominal condition | 2.15 W |
Encoder | |
Nominal output voltage | 24 V DC (UI - 0.5 V) |
Voltage range | 19.5 V DC ... 30 V DC (including all tolerances, including ripple) |
Current carrying capacity | max. 500 mA |
Protective circuit | Surge protection; electronic (35 V, 0.5 s) |
Short-circuit/overload protection; electronic | |
Transient protection; Shielding | |
Potentials: Axioline F local bus supply (UBus) | |
Supply voltage | 5 V DC (via bus base module) |
Current draw | max. 140 mA |
Potentials: Feed-in of supply voltage (UI) | |
Supply voltage | 24 V DC |
Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Current draw | max. 60 mA (Supply of the SSI interface and the analog output (20 mA), without sensor supply) |
Protective circuit | Surge protection; electronic (35 V, 0.5 s) |
Reverse polarity protection; Polarity protection diode | |
Transient protection; Suppressor diode | |
Electrical isolation/isolation of the voltage ranges | |
Test voltage: Logic | 500 V AC, 50 Hz, 1 min |
Test voltage: SSI I/O (24 V supply) | 500 V AC, 50 Hz, 1 min |
Test voltage: Functional ground | 500 V AC, 50 Hz, 1 min |
Test voltage: Analog I/O | 500 V AC, 50 Hz, 1 min |
Connection technology | |
Connection name | Axioline F connector |
Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual. |
Conductor connection | |
Connection method | Push-in connection |
Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Stripping length | 8 mm |
Axioline F connector | |
Connection method | Push-in connection |
Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual. |
Conductor cross section, rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Stripping length | 8 mm |
Ambient conditions | |
Ambient temperature (operation) | -25 °C ... 60 °C |
Degree of protection | IP20 |
Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
Permissible humidity (storage/transport) | 5 % ... 95 % (non-condensing) |
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Mounting type | DIN rail mounting |
Mounting position | any (no temperature derating) |
Item number | 2688433 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Sales key | DRI261 |
Product key | DRI261 |
Catalog page | Page 93 (C-6-2019) |
GTIN | 4046356644952 |
Weight per piece (including packing) | 182,2 g |
Weight per piece (excluding packing) | 135 g |
Customs tariff number | 85389091 |
Country of origin | DE |
ECLASS
ECLASS-13.0 | 27242605 |
ETIM
ETIM 9.0 | EC001601 |
UNSPSC
UNSPSC 21.0 | 32151600 |
EU RoHS | |
Fulfills EU RoHS substance requirements | Yes |
Exemption | 7(a), 7(c)-I |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-50
An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required.
|
EU REACH SVHC | |
REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) |
SCIP | a27cdddc-6a84-45b2-8822-7a9bf5cd1847 |
Compatible products
Your advantages
Permanent surge protection against 24 V DC for all interfaces
Permanent short-circuit protection for all interfaces
1 SSI interface
Monitoring of the 24 V encoder supply
Supports transmission speeds from 62.5 kHz to 2 MHz for SSI
8 bit ... 56 bit resolution
Supports Gray and binary code
1 analog, bipolar output channel for the connection of either voltage or current signals
Connection of actuators in 2-conductor technology
Voltage ranges: 0 V ... 10 V, ±10 V, 0 V ... 5 V, ±5 V
Current ranges: 0 mA ... 20 mA, 4 mA ... 20 mA, ±20 mA
Device rating plate stored
PHOENIX CONTACT A/S
Hammerholmen 43C, 1. tv. 2650 Hvidovre