FLS CO M12 DO 8 M12-2A
-
Distributed I/O device
2736084
The stand-alone device for CANopen® has 8 digital outputs each with a load capacity of 2 A. The M12 connection is established using fast connection technology. The 24 V DC supply is protected against short circuit and overload.
Free download available.
Downloads
Product details
Dimensional drawing |
|
Width | 60 mm |
Height | 178 mm |
Depth | 49.3 mm |
Drill hole spacing | 168 mm |
Utilization restriction | |
EMC note | EMC: class A product, see manufacturer's declaration in the download area |
CANopen® | |
Connection method | 2 M12 connectors, A-coded |
Number of positions | 5 |
Transmission speed | 10, 20, 50, 125, 250, 500, 1000 kBit/s (Automatic baud rate detection) |
Transmission physics | Copper cable with optional power supply in acc. with CAN standard |
Address area assignment | 1 ... 126, adjustable |
System limits | |
Number of local bus devices that can be connected | 0 |
Number of devices with parameter channel | 0 |
Module | |
Input address area | 4 bit |
Output address area | 0 bit |
Register length | 8 bit |
Digital: | |
Output name | Digital outputs |
Connection method | M12 connector |
Connection technology | 2-, 3-conductor |
Number of outputs | 8 |
Protective circuit | Short-circuit protection |
Output voltage | 24 V DC |
Maximum output current per channel | 2 A |
Product type | I/O component |
Product family | Fieldline |
Type | Block design |
No. of channels | 8 |
Potentials | |
Voltage supply UL | 24 V DC |
Power supply at UL | 4 A |
Current consumption from UL | typ. 80 mA |
max. 100 mA | |
Voltage supply US | 24 V DC |
Power supply at US | max. 4 A |
Current consumption from US | typ. 3.5 mA |
max. 700 mA | |
Voltage supply UA11 | 24 V DC |
Power supply at UA11 | max. 4 A |
Current consumption at UA11 | typ. 12 mA (plus actuator current) |
max. 4 A | |
Voltage supply UA12 | 24 V DC |
Power supply at UA12 | max. 4 A |
Current consumption at UA12 | typ. 12 mA (plus actuator current) |
max. 4 A | |
Voltage supply UA21 | 24 V DC |
Power supply at UA21 | max. 4 A |
Current consumption at UA21 | typ. 12 mA (plus actuator current) |
max. 4 A | |
Voltage supply UA22 | 24 V DC |
Power supply at UA22 | max. 4 A |
Current consumption at UA22 | typ. 12 mA (plus actuator current) |
max. 4 A | |
Supply: Module electronics | |
Connection method | M12 connector, A-coded |
Designation | UL |
Supply voltage | 24 V DC |
Supply voltage range | 18 V DC ... 30 V DC (including ripple) |
Electrical isolation/isolation of the voltage ranges | |
Test voltage: 24 V supply (bus logics) / Digital outputs (actuator supply) | 500 V AC, 50 Hz, 1 min |
Test voltage: FE / Digital outputs (actuator supply) | 500 V AC, 50 Hz, 1 min |
Connection method | M12 connector |
Ambient conditions | |
Ambient temperature (operation) | -25 °C ... 60 °C |
Degree of protection | IP65/IP67 |
Air pressure (operation) | 80 kPa ... 106 kPa (up to 2000 m above sea level) |
Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Ambient temperature (storage/transport) | -25 °C ... 85 °C |
Permissible humidity (storage/transport) | 95 % |
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Mounting type | Panel mounting |
Item number | 2736084 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Product key | DRI4A3 |
GTIN | 4017918904555 |
Weight per piece (including packing) | 392,2 g |
Weight per piece (excluding packing) | 350 g |
Country of origin | DE |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-E
No hazardous substances above the limits
|
EU REACH SVHC | |
REACH candidate substance (CAS No.) | No substance above 0.1 wt% |
Compatible products
-
-
SAC-5P-M12MS/ 5,0-920 - Bus system cable 1507434
-
SAC-5P-M12MS/10,0-920 - Bus system cable 1507447
-
SAC-5P-M12MS/15,0-920 - Bus system cable 1507450
-
SAC-5P- 2,0-920/M12FS - Bus system cable 1507476
-
SAC-5P- 5,0-920/M12FS - Bus system cable 1507489
-
SAC-5P-10,0-920/M12FS - Bus system cable 1507492
-
SAC-5P-15,0-920/M12FS - Bus system cable 1507502
-
SAC-5P-M12MS/ 0,3-920/M12FS - Bus system cable 1507528
-
SAC-5P-M12MS/ 0,5-920/M12FS - Bus system cable 1507531
-
SAC-5P-M12MS/ 1,0-920/M12FS - Bus system cable 1507544
-
SAC-5P-M12MS/ 2,0-920/M12FS - Bus system cable 1507557
-
SAC-5P-M12MS/ 5,0-920/M12FS - Bus system cable 1507560
-
SAC-5P-M12MS/10,0-920/M12FS - Bus system cable 1507573
-
SAC-5P-M12MS/15,0-920/M12FS - Bus system cable 1507586
-
SAC-4P-M12MS/ 2,0-186 - Sensor/actuator cable 1509445
-
SAC-4P-M12MS/ 5,0-186 - Sensor/actuator cable 1509458
-
SAC-4P-M12MS/10,0-186 - Sensor/actuator cable 1509461
-
SAC-4P-M12MS/15,0-186 - Sensor/actuator cable 1509474
-
SAC-4P- 2,0-186/M12FS - Sensor/actuator cable 1509487
-
SAC-4P- 5,0-186/M12FS - Sensor/actuator cable 1509490
-
SAC-4P-10,0-186/M12FS - Sensor/actuator cable 1509500
-
SAC-4P-15,0-186/M12FS - Sensor/actuator cable 1509513
-
SAC-4P-M12MS/ 0,3-186/M12FS - Sensor/actuator cable 1509526
-
SAC-4P-M12MS/ 0,5-186/M12FS - Sensor/actuator cable 1509539
-
SAC-4P-M12MS/ 1,0-186/M12FS - Sensor/actuator cable 1509542
-
SAC-4P-M12MS/ 2,0-186/M12FS - Sensor/actuator cable 1509555
-
SAC-4P-M12MS/ 5,0-186/M12FS - Sensor/actuator cable 1509568
-
SAC-4P-M12MS/10,0-186/M12FS - Sensor/actuator cable 1509571
-
SAC-4P-M12MS/15,0-186/M12FS - Sensor/actuator cable 1509584
-
SAC-4P-M12Y/2X0,3-PUR/M12FS VP - Sensor/actuator cable 1510722
-
SACC-M12MS-5CON-PG 9 SH AU - Data connector 1508352
-
SACC-M12FS-5CON-PG 9 SH AU - Data connector 1508365
-
SAC-M12T/2XM12 CAN - T distributor 1507793
-
SAC-5P-M12MS CAN TR - Termination resistor 1507816
-
ZBF 12:UNBEDRUCKT - Zack Marker strip, flat 0809735
-
PROT-M12 - Screw plug 1680539
Your advantages
Consistent connection via M12 connectors
Directly accessible address encoding switch
Diagnostic and status indicators
SPEEDCON fast locking system
Short-circuit and overload protection
Flexible power supply concept