The terminal is designed for use within an Inline station. The terminal is used to operate IO-Link-compatible sensors and actuators (devices). It is also used to acquire digital signals. IO-Link is the standard for consistent communication from the controller to the lowest field level. In IO-Link communication, the process data is forwarded during parallel service data transmission. IO-Link is a point-to-point connection between an IO-Link port and the sensor or actuator. IO-Link technology uses the familiar signal technology of the 0 V and 24 V binary interface in order to transmit data using pulse modulation. IO-Link offers full backward compatibility with standard sensors/actuators. Using this terminal, IO-Link-compatible devices from any manufacturer can be operated on INTERBUS, PROFIBUS, and PROFINET.
FLM IOL 4 DI 4 M12
-
Distributed I/O device
2736990
The local bus device has 4 IO-Link ports of 200 mA. Functions: parallel processing of service and process data, 500 kbaud/2 Mbaud selection, short-circuit and overload protection, 800 mA nominal current, M12 fast connection technology.
Free download available.
Downloads
Product details
Dimensional drawing |
|
Width | 70 mm |
Height | 178 mm |
Depth | 50 mm |
Drill hole spacing | 168 mm |
Color | anthracite |
Fieldline local bus | |
Connection method | M12 connector, B-coded |
Designation connection point | Copper cable |
Number of positions | 5 |
Transmission speed | 500 kbps / 2 Mbps |
Module | |
ID code (dec.) | 223 |
ID code (hex) | DF |
Length code (hex) | 06 |
Length code (dec) | 06 |
Process data channel | 80 bit |
Input address area | 80 bit |
Output address area | 80 bit |
Register length | 96 bit |
Required parameter data | 33 Byte |
Required configuration data | 5 Byte |
Digital: | |
Input name | Digital inputs |
Number of inputs | 4 |
Connection method | M12 connector |
Connection technology | 2-, 3-conductor |
Nominal input voltage UIN | 24 V DC |
Digital | |
Number of inputs | max. 4 |
Nominal input current | 8 mA (at 24 V DC) |
Signal delay | < 3 ms (ton, typical) |
3 ms (toff, typical) | |
Permissible cable length | < 20 m |
IO-Link | |
Description of the input | IEC 61131-2 type 1 |
Connection method | M12 plug connection |
Input filter time | typ. 3 ms |
Protective circuit | Reverse polarity protection |
IO-Link | |
Number of ports | 4 |
Connection method | M12 connector |
Connection technology | 3-conductor |
Digital | |
Number of outputs | max. 4 |
Nominal current per channel | 500 mA (INominal) |
Maximum total current consumption | 2 A (observe derating) |
Limitation of the voltage induced on circuit interruption | approx. -1 V |
Protective circuit | Freewheeling diode; Integrated per channel |
Product type | I/O component |
Product family | Fieldline |
Type | modular |
No. of channels | 4 |
Potentials | |
Voltage supply UL | 24 V DC |
Power supply at UL | max. 4 A |
Current consumption from UL | max. 150 mA (At 500 kBaud) |
typ. 75 mA (At 500 kBaud) | |
Voltage supply US | 24 V DC |
Power supply at US | max. 4 A |
Current consumption from US | typ. 25 mA (plus power supply for sensors) |
max. 2 A | |
Supply: IO-Link | |
Nominal current for every IO-Link port | max. 200 mA |
Nominal current per device | 800 mA |
Permissible cable length | < 20 m |
Protective circuit | Overload protection; Electronics in the device |
Short-circuit protection; Electronics in the device | |
Supply: Module electronics | |
Connection method | M12 connector |
Designation | UL |
Supply voltage | 24 V DC |
Supply voltage range | 18 V DC ... 30 V DC (including ripple) |
Connection method | M12 connector |
Ambient conditions | |
Ambient temperature (operation) | -25 °C ... 60 °C |
Degree of protection | IP65/IP67 |
Air pressure (operation) | 80 kPa ... 106 kPa (up to 2000 m above sea level) |
Ambient temperature (storage/transport) | -25 °C ... 85 °C |
Permissible humidity (storage/transport) | 95 % |
Mounting type | Panel mounting |
Item number | 2736990 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Product key | DRI453 |
GTIN | 4046356319393 |
Weight per piece (including packing) | 339,3 g |
Weight per piece (excluding packing) | 280 g |
Country of origin | DE |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-E
No hazardous substances above the limits
|
EU REACH SVHC | |
REACH candidate substance (CAS No.) | No substance above 0.1 wt% |
Compatible products
-
-
ZBF 12:UNBEDRUCKT - Zack Marker strip, flat 0809735
-
SAC-5P-MSB/0,13-PUR/FSB SCO SH - Sensor/actuator cable 1518478
-
SAC-5P-MS/ 0,13-186/FS SCO - Sensor/actuator cable 1518481
-
SAC-5P-MSB/ 0,3-900/FSB SCO - Bus system cable 1517958
-
SAC-5P-MSB/ 0,5-900/FSB SCO - Bus system cable 1517961
-
SAC-5P-MSB/ 1,0-900/FSB SCO - Bus system cable 1517974
-
SAC-5P-MSB/ 2,0-900/FSB SCO - Bus system cable 1517987
-
SAC-5P-MSB/ 5,0-900/FSB SCO - Bus system cable 1517990
-
SAC-5P-MSB/10,0-900/FSB SCO - Bus system cable 1518009
-
SAC-5P-MSB/15,0-900/FSB SCO - Bus system cable 1518012
-
SAC-5P-MS/ 0,3-186/FS SCO - Sensor/actuator cable 1518407
-
SAC-5P-MS/ 0,5-186/FS SCO - Sensor/actuator cable 1518410
-
SAC-5P-MS/ 1,0-186/FS SCO - Sensor/actuator cable 1518423
-
SAC-5P-MS/ 2,0-186/FS SCO - Sensor/actuator cable 1518436
-
SAC-5P-MS/ 5,0-186/FS SCO - Sensor/actuator cable 1518449
-
SAC-5P-MS/10,0-186/FS SCO - Sensor/actuator cable 1518452
-
SAC-5P-MS/15,0-186/FS SCO - Sensor/actuator cable 1518465
Your advantages
4 IO-Link ports and 4 digital inputs
Consistent connection via M12 connectors
Short-circuit and overload protection
Diagnostic and status indicators
SPEEDCON fast locking system
Flexible power supply concept
PHOENIX CONTACT A/S
Hammerholmen 43C, 1. tv. 2650 Hvidovre