UM- 8 RM-S-G24/21/PLC-MSTB
-
Active module
2311030
Relay module, with 8 miniature relays, one changeover contact each, plugged in, for 24 V DC (incl. relay)
Product details
Notes on operation | For proper use, the specifications of the installation directive (see Downloads) must be observed. For applications or use with third-party products, the specifications, and the safety and warning instructions of the respective third-party manufacturer must also be met. |
Product type | Relay Module |
With components | yes |
Insulation characteristics: Air clearances and creepage distances, input/output | |
Insulation | Reinforced insulation |
Overvoltage category | III |
Pollution degree | 2 |
Insulation characteristics: Air and creepage distances, output/output | |
Insulation | Functional insulation |
Overvoltage category | II |
Pollution degree | 2 |
Air clearances and creepage distances, input/output | |
Rated insulation voltage | 260 V |
Rated surge voltage | 6 kV (1.2/50 μs) |
Air and creepage distances, output/output | |
Rated insulation voltage | 260 V |
Rated surge voltage | 2.3 kV (1.2/50 μs) |
Nominal input voltage UN | 24 V DC (±10 %) |
Typical input current at UN | 200 mA (200 mA supply / ≤ 20 mA input current per signal) |
Switching | |
Contact switching type | Single contact, 1 changeover contact |
Maximum switching voltage | 150 V AC/DC (Maximum switching voltage of 230 V AC: the maximum switching voltage of 230 V is only permitted if the same fuse circuit is used. The outputs are not suitable for switching different outer conductors.) |
Limiting continuous current | 4 A |
Controller level | |
Connection in acc. with standard | IEC 60603-13 |
Connection method | IDC/FLK pin strip |
Number of connections | 1 |
Number of positions | 14 |
Field level | |
Connection method | Screw connection |
Number of connections | 1 |
Number of positions | 12 |
Conductor cross-section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross-section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross-section AWG | 24 ... 12 |
Supply | |
Connection method | Screw connection |
Number of connections | 1 |
Number of positions | 2 |
Conductor cross-section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross-section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross-section AWG | 24 ... 12 |
DEROG | |
Connection method | Screw connection |
Number of connections | 1 |
Number of positions | 3 |
Conductor cross-section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross-section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross-section AWG | 24 ... 12 |
Width | 61 mm |
Height | 126 mm |
Depth | 146 mm |
Ambient conditions | |
Degree of protection | IP00 |
Degree of protection (Installation location) | ≥ IP54 (Installation location) |
Ambient temperature (operation) | -20 °C ... 50 °C |
Altitude | ≤ 2000 m |
Air clearances and creepage distances, input/output | |
Standards/regulations | DIN EN 50178: 1998-04 |
Air and creepage distances, output/output | |
Standards/regulations | DIN EN 50178: 1998-04 |
Mounting type | DIN rail mounting |
Mounting position | any |
Item number | 2311030 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Sales key | DK2A91 |
Product key | DK2A91 |
GTIN | 4046356134958 |
Weight per piece (including packing) | 505,1 g |
Weight per piece (excluding packing) | 505 g |
Customs tariff number | 85369010 |
Country of origin | DE |
ECLASS
ECLASS-13.0 | 27141152 |
ECLASS-15.0 | 27141152 |
ETIM
ETIM 9.0 | EC002780 |
UNSPSC
UNSPSC 21.0 | 39121400 |
EU RoHS | |
Fulfills EU RoHS substance requirements | Yes |
Exemption | 6(c), 7(a), 7(c)-I |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-50
An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required.
|
EU REACH SVHC | |
REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) |
SCIP | 90b00a4a-de71-45f3-9f97-0b9b56758dd0 |
Compatible products