EAC
Approval ID: RU*C-DE.*08.B.00010CSA
Approval ID: LR 13631Nominal voltage UN | Nominal current IN | Cross section AWG | Cross section mm2 | |
---|---|---|---|---|
keine | ||||
120 V | 16 A |
16-channel output relay module with screw connection and 50-pos. system connection, coil side is protected and non-isolated (optional), for Yokogawa SDV 541 cards, module width: 425 mm
Product type | Interface module |
Insulation characteristics: Air clearances and creepage distances, input/output | |
Insulation | Safe isolation, reinforced insulation |
Overvoltage category | III |
Pollution degree | 2 |
Insulation characteristics: Air and creepage distances, output/output | |
Insulation | Basic insulation |
Overvoltage category | III |
Pollution degree | 2 |
Air clearances and creepage distances, input/output | |
Rated insulation voltage | 300 V |
Rated surge voltage | 6 kV (1.2/50 μs) |
Air and creepage distances, output/output | |
Rated insulation voltage | 300 V |
Rated surge voltage | 4 kV (1.2/50 μs) |
Supported controller YOKOGAWA ProSafe-RS | |
Suitable I/O card | SDV541 |
Nominal input voltage UN | 24 V DC |
Input voltage range in reference to UN | 0.9 ... 1.1 |
Input voltage range | 21.6 V DC ... 26.4 V DC |
Typical input current at UN | 40 mA |
Protective circuit | Freewheeling diode |
Status display/channel | Yellow LED |
Switching | |
Contact switching type | 1 N/O contact per channel |
Contact material | AgNi (90/10) gold-plated |
Maximum switching voltage | 230 V AC |
63 V DC | |
Limiting continuous current | 4 A (pluggable fuse) |
Maximum inrush current | Supply 24 V DC/2 A, (P1+, P2+), pluggable fuse (IEC 60127-3/IV, 2AT) |
Supply | |
Connection method | Screw connection |
Number of positions | 6 |
Conductor cross-section rigid | 0.34 mm² ... 2.5 mm² |
Conductor cross-section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross-section AWG | 24 ... 12 |
Field level | |
Connection method | Screw connection with disconnect knife |
Number of connections | 2 |
Number of positions | 20 |
Conductor cross-section rigid | 0.2 mm² ... 4 mm² |
Conductor cross-section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross-section AWG | 24 ... 12 |
Controller level | |
Connection method | Yokogawa, KS compatible |
Number of connections | 2 |
Number of positions | 50 |
Tightening torque | 0.5 Nm |
Status display present | no |
Width | 424.5 mm |
Height | 127.5 mm |
Depth | 67 mm |
Ambient conditions | |
Degree of protection | IP00 |
Degree of protection (Installation location) | ≥ IP54 (Installation location) |
Ambient temperature (operation) | -20 °C ... 50 °C |
Altitude | ≤ 2000 m |
Air clearances and creepage distances, input/output | |
Standards/regulations | EN 61010-2-201 |
Air and creepage distances, output/output | |
Standards/regulations | EN 61010-2-201 |
Mounting type | DIN rail mounting |
Mounting position | any |
Notes on operation | Observe the maximum switching capacity of the relays used |
Notes on operation | Do not connect adjacent channels to SELV/ PELV and voltages dangerous to the touch. |
Notes on operation | The outputs are not suitable for switching different line conductors. The sum of the switching voltages used for adjacent outputs must not exceed the rated insulation voltage value |
Notes on operation | The necessary requirements for insulation (basic insulation or reinforced insulation) from adjacent modules (in DIN-rail direction) must be realized by applying suitable measures (e. g., partition plates). |
Notes on operation | For proper use, the specifications of the installation directive (see Downloads) must be observed. For applications or use with third-party products, the specifications, and the safety and warning instructions of the respective third-party manufacturer must also be met. |
Item number | 2319430 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Sales key | DK2A9N |
Product key | DK2A9N |
GTIN | 4046356550031 |
Weight per piece (including packing) | 1’516 g |
Weight per piece (excluding packing) | 1’516 g |
Customs tariff number | 85369000 |
Country of origin | DE |
ECLASS-13.0 | 27141152 |
ECLASS-15.0 | 27141152 |
ETIM 9.0 | EC002780 |
UNSPSC 21.0 | 39121400 |
Nominal voltage UN | Nominal current IN | Cross section AWG | Cross section mm2 | |
---|---|---|---|---|
keine | ||||
120 V | 16 A |
EU RoHS | |
Fulfills EU RoHS substance requirements | Yes |
Exemption | 6(c), 7(a), 7(c)-I |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-50
An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required.
|
EU REACH SVHC | |
REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) |
SCIP | 425b662e-32af-464a-bc5e-6deef06a6b3b |