MACX-MR-C-10-PT
   - 
  Monitoring relay
    
      1336512
      
      
    
  
      Current monitoring relay, 24 V AC/DC … 240 V AC/DC wide range power supply, with adjustable threshold values, response delay, and the functions can be selected by configuration.
      Free download available.
      Downloads
    
  Product details
| Product type | Current monitoring relay | 
| Operating mode | Closed circuit or wire break | 
| Insulation characteristics: Railway standard | |
| Overvoltage category | III | 
| Pollution degree | 3 | 
| Rated impulse withstand voltage | 6 kV | 
| Service life electrical | approx. 1x 105 cycles, resistive load 2000 V A | 
| Maximum power dissipation for nominal condition | 15 W | 
| Mains type | 1-phase | 
| Railway standard | |
| Rated insulation voltage | 600 V | 
| Electrical isolation | |
| Electrical isolation | 300 V | 
| Supply | |
| Supply voltage range | 24 V AC ... 240 V AC -15 % ... +10 % | 
| 24 V DC ... 240 V DC -25 % ... +30 % | |
| Nominal power consumption | 15 VA (1.5 W) | 
| Frequency range | 48 Hz ... 400 Hz | 
| Input name | Measuring input | 
| Measured value | DC, AC sine (40 Hz ... 500 Hz) | 
| Input current range | 0 A AC/DC ... 10 A AC/DC | 
| Overload capacity | 15 A AC/DC | 
| Input resistance current input | 5 mΩ | 
| Frequency range | 48 Hz ... 400 Hz | 
| Maximum temperature coefficient | 0.05 %/K | 
| Setting range for response delay | 0 s ... 99.9 s | 
| Function | Undercurrent | 
| Overcurrent | |
| Window | |
| Basic accuracy | 1 % (>1A, ±10mA (0…1A)) | 
| Repeat accuracy | 0.5 % | 
| Recovery time | 200 ms | 
| Switching | |
| Contact switching type | 2 floating changeover contacts | 
| Maximum switching voltage | 250 V AC | 
| Interrupting rating (ohmic load) max. | 2000 VA (8 A/250 V AC) | 
| Output fuse | 8 A (fast-blow) | 
| Connection method | Push-in connection | 
| Stripping length | 10 mm | 
| Conductor cross-section rigid | 0.2 mm² ... 2.5 mm² | 
| Conductor cross-section flexible | 0.2 mm² ... 2.5 mm² | 
| Conductor cross-section AWG | 24 ... 14 | 
| Tightening torque | 0.5 Nm ... 0.6 Nm (5 lb in ... 7 lb in) | 
| Width | 22.5 mm | 
| Height | 109 mm | 
| Depth | 114 mm | 
| Flammability rating according to UL 94 | V0 | 
| Housing insulation material | PBT | 
| Ambient conditions | |
| Degree of protection | IP40 (Housing) | 
| IP20 (Connection terminal blocks) | |
| Ambient temperature (operation) | -25 °C ... 70 °C | 
| Ambient temperature (storage/transport) | -40 °C ... 85 °C | 
| Permissible humidity (operation) | 10 % ... 95 % | 
| CE | |
| Identification | CE-compliant | 
| UL, USA/Canada | |
| Identification | UL/C-UL Listed UL 508 | 
| CCC | |
| Identification | GB/T 14048.5 | 
| Electronic devices in rail vehicles | |
| Operating temperature class | OT4 | 
| Class of extended operating temperature upon activation | ST2 | 
| Temperature change class | H1 | 
| Interruption of the power supply/supply changeover | S2 | 
| S3/C1 | |
| C2 | |
| Hazard levels | HL1 | 
| HL2 | |
| HL3 | |
| Protective coating | PC2 | 
| Shock (operation) | Category 1 | 
| Vibration (operation) | Class B | 
| Electromagnetic compatibility | Conformance with EMC directive | 
| Low Voltage Directive | Conformance with Low Voltage Directive | 
| Noise immunity | EN 61000-6-2 | 
| Noise emission | |
| Standards/regulations | EN 61000-6-4 | 
| Railway standard | |
| Standard designation | EN 50155, GB/T 25119 | 
| Assembly note | on standard DIN rail NS 35 in accordance with EN 60715 | 
| Mounting position | any | 
| Item number | 1336512 | 
| Packing unit | 1 pc | 
| Minimum order quantity | 1 pc | 
| Sales key | DK6612 | 
| Product key | DK6612 | 
| GTIN | 4063151636784 | 
| Weight per piece (including packing) | 197.2 g | 
| Weight per piece (excluding packing) | 195 g | 
| Customs tariff number | 85364900 | 
| Country of origin | CN | 
ECLASS
| ECLASS-13.0 | 27371802 | 
| ECLASS-15.0 | 27371802 | 
ETIM
| ETIM 9.0 | EC001440 | 
UNSPSC
| UNSPSC 21.0 | 41113600 | 
| EU RoHS | |
| Fulfills EU RoHS substance requirements | Yes | 
| Exemption | 7(a), 7(c)-I | 
| China RoHS | |
| Environment friendly use period (EFUP) | EFUP-50 An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required. | 
| EU REACH SVHC | |
| REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) | 
| SCIP | 48765132-694d-4f0e-93ba-bde28a9605c1 | 
Compatible products
Frequently searched
PHOENIX CONTACT AG
        
        Zürcherstrasse 22, CH-8317 Tagelswangen